manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Edwards
  6. •
  7. Security Sensor
  8. •
  9. Edwards Signature Series Assembly instructions

Edwards Signature Series Assembly instructions

© 2018 United Technologies Corporation 1 / 2 P/N 3102366-EN • REV 003 • ISS 14FEB18
SIGA-HRD Intelligent Fixed-
Temperature and Rate-of-Rise
Heat Detector Installation Sheet
Description
The Signature Series model SIGA-HRD Intelligent Fixed-Temperature
and Rate-of-Rise Heat Detector is an intelligent device that contains a
rate-of-rise and fixed-temperature heat sensor function to detect fire.
The heat sensor monitors the temperature of the surrounding air and
the detector analyzes the data from the sensor to determine whether to
initiate an alarm. The rate-of-rise heat function quickly detects a fast,
flaming fire. The fixed-temperature heat function detects fire when the
air temperature near the detector exceeds the alarm point.
LED indicator. The LED indicator (see Figure 1) displays the following
states:
•Normal: Green LED indicator flashes, no action.
•Alarm/active: Red LED indicator flashes, evacuate the area.
Figure 1: SIGA-HRD features
(1) Self-locking tab
(2) LED indicator
Installation
Notes
•This detector does not operate without electrical power. As fires
frequently cause power interruption, discuss further safeguards
with the local fire protection specialist.
•This detector does not sense fires in areas where heat cannot
reach the detector. Heat from fires in walls, roofs, or on the
opposite side of closed doors may not reach the detector.
•This heat detector by itself does not provide life safety protection.
Use this detector in conjunction with ionization or photoelectric
smoke detectors, or both for life safety situations.
•This detector does not detect oxygen levels, smoke, toxic gases,
or flames. Use this device as part of a broad-based life safety
program which includes a variety of information sources pertaining
to heat and smoke levels, extinguishment systems, visual and
audible devices, and other safety measures.
•Independent studies indicate that heat detectors should only be
used when property protection alone is involved. Never rely on
heat detectors as the sole means of fire protection.
•To ensure proper operation, store the detector within the
recommended ranges. Allow the detector to stabilize to room
temperature before applying power.
•The dust cover (supplied) must remain on the detector during
installation and be removed prior to commissioning and service.
The dust cover is not a substitute for removing the detector during
new construction or heavy remodeling.
•In Canada, install according to CAN/ULC-S524 Standard for the
Installation of Fire Alarm Systems, CSA C22.1 Canadian Electrical
Code, and the local authority having jurisdiction.
To install the detector:
1. Install and wire the base, as described on the installation sheet
supplied with the base.
2. Remove the serial number label from the detector and attach it to
the project documentation.
3. Attach the detector to the base by rotating the detector clockwise
until it snaps into the locked position.
Testing
Before testing, notify the proper authorities that the fire alarm system is
undergoing maintenance and will be temporarily out of service.
Caution: Heat damage. Excessive heat may damage the detector
outer cover. Do not apply excessive heat when using a hair dryer.
When using a Testifire detector tester, you must install a SIGA2
Testifire Adapter Assembly.
Make sure the SIGA2 Testifire Adapter Assembly (model
SIGA2-TSTSPACER) is installed in the Testifire detector tester before
testing. Refer to the SIGA2-TSTSPACER Testifire Adapter Assembly
Installation Sheet (P/N 3101942-ML) for further details.
To perform an initial installation test:
1. Visually inspect each detector and verify that it is installed in the
correct location. Make sure it is not adversely affected by factors
not apparent on the plans.
2. Remove the detector from its base and verify that the proper
detector address, trouble signals, and messages are reported.
3. If wired for Class A operation, verify that the detector continues to
operate first with the SLC_IN disconnected, and then with the
SLC_OUT disconnected. (Refer to the installation sheet for the
base.)
4. Place a momentary ground fault on the SLC circuit to verify
operation of the ground fault detection circuitry.
5. Perform a sensor function test, as described below.
To perform a function test:
1. If desired, use the fire alarm control panel to put the detector or
zone into a service group for testing. (Refer to the panel technical
reference manual for instructions.)
2
2 / 2 P/N 3102366-EN • REV 003 • ISS 14FEB18
2. Activate the heat sensor using a hair dryer (maintaining a distance
of three inches) or using a Testifire detector tester per the
manufacturer’s instructions.
Maintenance
To ensure proper operation, plan maintenance (regular or selected) of
the detector in accordance with the AHJ and all applicable governing
laws, codes, or standards. Refer to CAN/ULC-S536 Standard for the
Inspection and Testing of Fire Alarm Systems and NFPA 72 National
Fire Alarm and Signaling Code.
Refer to application bulletin P/N 3102403-EN for additional information
and cleaning instructions.
Specifications
Operating voltage
15.20 to 19.95 VDC
Current
Normal operating
Alarm
51 µA
68 µA
Vibration level
10 to 35 Hz, with an amplitude of
0.01 in.
Rate-of-rise
15°F/min (8°C/min)
Maximum spacing [1]
50 ft. (15.2 m) centers
Compatible bases
Standard
Relay
Isolator
Audible
SIGA-SB, SIGA-SB4
SIGA-RB, SIGA-RB4
SIGA-IB, SIGA-IB4
SIGA-AB4G, SIGA-AB4GT,
SIGA-AB4G-LF
Compatible detector testers [2]
Testifire 1000, Testifire 2000
Operating environment
Temperature
Relative humidity
32 to 100°F (0 to 38°C)
0 to 93% noncondensing
Storage temperature
−4 to 140°F (−20 to 60°C)
[1] When replacing SIGA-HRS and SIGA-HFS detectors with the
SIGA-HRD, ensure that the spacing is 50 ft. (15.2 m) or less.
[2] Requires the SIGA2-TSTSPACER Testifire adapter assembly.
Regulatory information
North American
standards
CAN/ULC-S530, UL 521
UL/ULC fixed-temp
alarm rating
135°F (57.2°C)
UL/ULC Actual
alarm point
129 to 141°F (53.9 to 60.6°C)
Response time
index
Quick(evaluated by FM Approvals)
FCC compliance
This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any
interference received, including interference that
may cause undesired operation.
Industry Canada
compliance
This Class A digital apparatus complies with
Canadian ICES-003.
Contact information
For contact information, see www.edwardsfiresafety.com

This manual suits for next models

1

Other Edwards Security Sensor manuals

Edwards SIGA-PHDB Assembly instructions

Edwards

Edwards SIGA-PHDB Assembly instructions

Edwards GasCheck G3 Magshield Installation and operating instructions

Edwards

Edwards GasCheck G3 Magshield Installation and operating instructions

Edwards SIGA2-HRS Owner's manual

Edwards

Edwards SIGA2-HRS Owner's manual

Edwards SIGA-HRD Assembly instructions

Edwards

Edwards SIGA-HRD Assembly instructions

Edwards AB4G Assembly instructions

Edwards

Edwards AB4G Assembly instructions

Edwards 517FH Series User manual

Edwards

Edwards 517FH Series User manual

Edwards SIGA-HRD Assembly instructions

Edwards

Edwards SIGA-HRD Assembly instructions

Edwards ELD500 Series User manual

Edwards

Edwards ELD500 Series User manual

Edwards SIGA-IM Assembly instructions

Edwards

Edwards SIGA-IM Assembly instructions

Popular Security Sensor manuals by other brands

Vega VEGAPULS C 21 operating instructions

Vega

Vega VEGAPULS C 21 operating instructions

Summit Treestands SOP Series instructions

Summit Treestands

Summit Treestands SOP Series instructions

Alarmtech MC 740-E-M14 instruction manual

Alarmtech

Alarmtech MC 740-E-M14 instruction manual

Summit Treestands FBFAHS SU18195-B manual

Summit Treestands

Summit Treestands FBFAHS SU18195-B manual

hyfire ALTAIR LITE Series instructions

hyfire

hyfire ALTAIR LITE Series instructions

EpiSensor ZIO-20 user guide

EpiSensor

EpiSensor ZIO-20 user guide

LEGRAND 488 25 manual

LEGRAND

LEGRAND 488 25 manual

Elko iNels Air AirWD-101 Series manual

Elko

Elko iNels Air AirWD-101 Series manual

Honeywell FS20X Series Installation guide and operating manual

Honeywell

Honeywell FS20X Series Installation guide and operating manual

PEHA SENSOLUX 482 FU-BM DE Installation and operating instructions

PEHA

PEHA SENSOLUX 482 FU-BM DE Installation and operating instructions

Kobold OPT operating instructions

Kobold

Kobold OPT operating instructions

Innova XTIRPA IN-8015 Instruction and safety manual

Innova

Innova XTIRPA IN-8015 Instruction and safety manual

Leviton ZLS10-ILW installation instructions

Leviton

Leviton ZLS10-ILW installation instructions

Maclean Energy MCE243 manual

Maclean Energy

Maclean Energy MCE243 manual

olympia electronics BS-409 quick start guide

olympia electronics

olympia electronics BS-409 quick start guide

Vanderbilt AGB800-AM Instruction and installation manual

Vanderbilt

Vanderbilt AGB800-AM Instruction and installation manual

HAI 61A00-1 installation instructions

HAI

HAI 61A00-1 installation instructions

systemax Poolnanny user guide

systemax

systemax Poolnanny user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.