Ekinex EK-SN2-TP-GAA Instructions for use

Application manual
KNX standard wall presence
detector with
movement function
EK-SN2-TP-GAA
EK-SN2-TP-GAE

Application manual
KNX standard wall presence detector with movement function EK-SN2-TP-…
Rev. 1.0 –29/09/2022 MAEKSN2TP_EN
© Ekinex S.p.A. –All rights reserved Pag. 2
Contents
1Scope of the document.............................................................................................................................. 4
2Product description.................................................................................................................................... 5
3Main features............................................................................................................................................. 5
4Technical data............................................................................................................................................ 5
5Versions..................................................................................................................................................... 6
6Switching, display and detection elements................................................................................................ 6
7Operation................................................................................................................................................... 7
7.1 Brightness measurement...................................................................................................................... 7
7.2 Lighting control channels...................................................................................................................... 7
7.3 Constant ambient brightness regulation............................................................................................... 7
7.4 HVAC control channels......................................................................................................................... 7
8Positioning ................................................................................................................................................. 7
9Limitation of the detection area.................................................................................................................. 9
10 Mounting and installation......................................................................................................................... 11
11 Connection of the KNX bus line............................................................................................................... 13
12 Configuration and commissioning............................................................................................................ 13
13 Operations ............................................................................................................................................... 14
13.1 Slide switch setup............................................................................................................................... 14
13.2 Slide switch functions.......................................................................................................................... 14
13.3 Walk test ............................................................................................................................................. 15
13.4 Auto / Semi-auto mode (absence detection function)......................................................................... 16
13.5 Test mode........................................................................................................................................... 16
13.6 Manual ON / OFF and DIM switching function ................................................................................... 16
13.7 Master / Slave selection...................................................................................................................... 16
13.8 Ambient light appraisal........................................................................................................................ 16
13.9 2-level (Standby Lighting) function ..................................................................................................... 17
13.10 Constant light control................................................................................................................... 17
13.11 Alarm............................................................................................................................................ 17
14 List of ETS®parameters .......................................................................................................................... 18
14.1 Menu: General .................................................................................................................................... 18
14.2 Menu: Motion sensors......................................................................................................................... 19
14.3 Menus: Light control output C1 / C2 ................................................................................................... 20
14.4 Menus: HVAC control output C3 / C4................................................................................................. 22
14.5 Menus: Alarm function........................................................................................................................ 24
15 ETS®Communication Objects list ........................................................................................................... 25
16 Troubleshooting....................................................................................................................................... 27
17 Package contents .................................................................................................................................... 27
18 Dimensions.............................................................................................................................................. 28
19 Markings .................................................................................................................................................. 28
20 Maintenance ............................................................................................................................................ 28
21 Disposal................................................................................................................................................... 28
22 General warnings..................................................................................................................................... 29
23 Other information..................................................................................................................................... 29

Application manual
KNX standard wall presence detector with movement function EK-SN2-TP-…
Rev. 1.0 –29/09/2022 MAEKSN2TP_EN
© Ekinex S.p.A. –All rights reserved Pag. 3
Revision
Changes
Date
Written by
Verified by
1.0
First release
29/09/2022
G. Schiochet

Application manual
KNX standard wall presence detector with movement function EK-SN2-TP-…
Rev. 1.0 –29/09/2022 MAEKSN2TP_EN
© Ekinex S.p.A. –All rights reserved Pag. 4
1 Scope of the document
This application manual describes application details for the ekinex®KNX standard wall presence
detector with movement function EK-SN2-TP.
The document is aimed at the system configurator as a description and reference of device features
and application programming. For installation, mechanical and electrical details of the device please
refer to the technical description datasheet.
Application manual and application programs for ETS®are available for download at
www.ekinex.com.
Item
File name (## = release)
Version
Device rel.
Update
Technical datasheet
STEKSN2TP_EN.pdf
STEKSN2TP_EN.pdf
-
A1.0
29/09/2022
Application manual
MAEKSN2TP_EN.pdf
-
Application program
APEKSN2TP##.knxprod
APEKSN2TP##.knxprod
-

Application manual
KNX standard wall presence detector with movement function EK-SN2-TP-…
Rev. 1.0 –29/09/2022 MAEKSN2TP_EN
© Ekinex S.p.A. –All rights reserved Pag. 5
2 Product description
The ekinex®EK-SN2-TP sensor is a passive infrared (PIR) indoor presence detector based on KNX
standard, with movement function and wall switch. It is designed for the detection of movement /
presence of people in shops, offices, small rooms, residential areas such as corridors, stairs,
bedrooms, etc., in order to drive lighting and HVAC systems.
The detection area has a coverage angle of 200° and it can be extended using other sensors
configured as slave devices. An integrated light sensor, combined with the motion detector, can
manage light switching depending on brightness level as well as presence.
The device has two distinct output channels for lighting control, with independent parameters; the
operation can be automatic or semi automatic.
The device is also capable of maintaining a constant brightness level in the room by controlling a
dimmable light source.
All of the above parameters can be set by the user either through KNX ETS®software.
The device has two additional HVAC channels, which act in a similar way as the Light Control
channels but without the standby time and light level dependence.
An additional alarm channel can switch the load on or off depending on the number of trigger events
(movements) detected in a time frame of configurable duration.
3 Main features
Hidden switch, can fit single round or square wall flush-mounting box
Simple and safe plug-in installation
The presence detector is used to control devices, e.g. lighting and HVAC
Learning function, to configure the device functions by reading the “ambient Lux” parameter
Semi-automatic or fully automatic operation
Evolved lens model, with well-distributed and concentrated detection capabilities: the
detection beams also provide high intensity and sensitivity, so it is possible to detect even a
small shaking movement of the hand
Adjustable sensitivity via ETS®on 4 levels or with "Walk test" to verify detection range
Operating modes: Manual ON / AUTO / OFF
An additional device can be used as slave for any of the channels
Use in the KNX TP bus system (twisted pair) in combination with other KNX devices
Function parameters and settings via ETS®5.0 (Engineering Tool Software) or higher
4 Technical data
Rated voltage: 24 Vdc (21 - 30 Vdc) supplied by KNX bus
Current consumption (on KNX bus): max 10 mA (operation) / 5 mA (Standby)
Connection type: KNX bus with Ø 0.8 mm, single cable
Outputs: 5 channels (2 for lighting, 2 for HVAC, 1 for alarm)
Mounting height: 1.2 - 2.0 m
Detection angle: up to 200 °
Detection range: up to 9 m if mounted at a height between 1.2 - 1.5 m, up to 8 m at a height
between 1.8 - 2.0 m
Light measurement range: 10 ... 2000 Lux
Housing, lens and frame in plastic material
Safety standards: IEC 61000-6-1 / IEC 61000-6-3 / EN 55014 / EN 50491

Application manual
KNX standard wall presence detector with movement function EK-SN2-TP-…
Rev. 1.0 –29/09/2022 MAEKSN2TP_EN
© Ekinex S.p.A. –All rights reserved Pag. 6
Other characteristics
Housing, lens and frame in plastic material
Wall installation in flush mounting box
Protection degree IP20 (installed device)
Climatic classification 3K5 and mechanical 3M2 (according to EN 50491-2)
Pollution degree 2 (according to IEC 60664-1)
Weight 40 g (70 g with mounting support)
Dimensions 80 x 80 x 31 mm
Environmental conditions
Operating temperature: - 20 ... + 40°C
Relative humidity: 95% not condensing
5 Versions
The sensor is supplied in 2 versions: EK-SN2-TP-GAA, in white color, and EK-SN2-TP-GAE in black
color.
6 Switching, display and detection elements
The device is equipped with 2 switching elements, located under the cover:
a KNX programming button (1)
a switch to select the operating mode Manual / ON / OFF (2)
The following signaling and detection elements are also visible through the lens:
a blue programming LED (3),
a red signaling LED (3),
a PIR sensor, a light sensor and an IR receiver
Figure 1 - Switching, display and detection elements

Application manual
KNX standard wall presence detector with movement function EK-SN2-TP-…
Rev. 1.0 –29/09/2022 MAEKSN2TP_EN
© Ekinex S.p.A. –All rights reserved Pag. 7
7 Operation
The sensor reacts to the thermal radiation emitted by moving bodies; the detection area is optically
divided in small sections through a composite lens. A person walking in the detection area across
the sections triggers the sensor.
7.1 Brightness measurement
The measurement of the room brightness is carried out by an integrated light sensor with linear
output and optical filter set on the profile of the human eye. The brightness value, measured in Lux,
can be transmitted on the bus.
7.2 Lighting control channels
The lighting channel has two operation modes, Automatic or Semi-automatic. The automatic mode
controls both switch-on and switch-off, when a movement is detected; the semi-automatic mode
requires manual switch-on, which is maintained until movement is detected; it will swich-off only
when no more movement is detected.
The lighting source can be controlled through two different types of communication objects: On-Off
switch or Absolute dimming percentage.
In automatic mode, a load connected to a lighting channel will be switched on when movement is
detected and (if desired) the ambient light level is below a preset brightness value.
When no movement has been detected for a programmable time duration, a stand-by phase can be
entered, during which thelight can bedimmed to alower intensity;if nofurther movement isdetected,
once stand-by time has expired, the light will be automatically switched off.
Both the light level threshold and stand-by time functions can be disabled if not required.
7.3 Constant ambient brightness regulation
The internal brightness sensor can be used to maintain a constant ambient brightness if a dimmable
light source is available. The light source must be capable of being controlled through a Relative
dimming communication object.
7.4 HVAC control channels
The HVAC channels act in a similar way as the Light Control channels, but without the standby time
and the dependence from the light level.
8 Positioning
The actual detection range of the sensors depends on the mounting height.
The optimal range is achieved walking through several portions of the detection area.
Figure 2 - Positioning
Increased sensitivity if
movement crosses the lens
beam
Less sensitivity if the
movement is towards the lens

Application manual
KNX standard wall presence detector with movement function EK-SN2-TP-…
Rev. 1.0 –29/09/2022 MAEKSN2TP_EN
© Ekinex S.p.A. –All rights reserved Pag. 8
It is recommended to install the device at a height of 1.2 m - 2.0 m. The detection range is 9 m at a
height of 1.2 m - 1.5 m and up to 8 m at a height of 1.8 m - 2.0 m.
Figure 3 - Installation at a height of 1.2 - 1.5 m
Figure 4 - Installation at a height of 1.8 - 2.0 m

Application manual
KNX standard wall presence detector with movement function EK-SN2-TP-…
Rev. 1.0 –29/09/2022 MAEKSN2TP_EN
© Ekinex S.p.A. –All rights reserved Pag. 9
Since the detector responds to temperature change, be aware that following conditions may
cause lower sensitivity:
In very foggy days, the sensitivity may be less due to moisture collecting on
the lens.
In very hot days, the sensitivity may be less since high ambient temperature
is close to body temperature.
In very cold days when heavy clothing is worn, especially if the facial area is
covered, very little heat will be emitted from the body causing the unit to be
less sensitive.
Please also verify the following conditions during installation:
Avoid pointing the detector toward objects with highly reflective surfaces,
such as mirrors, glass, etc.
Avoid mounting the detector very close to heat sources, such as heating
vents, air conditioners, lights, etc.
Avoid pointing the detector toward objects which may sway in air currents,
such as curtains, tall plants, etc.
9 Limitation of the detection area
The detection area can be limited, in order to avoid unwanted activations, by means of the supplied
optical shielding filters. The shield consists of three layers, each divided into four units, capable of
masking an angle of approx. 50 ° each.
Figure 5 - Lens shield with layers
When mounting the device at a height of 1.2 m - 1.5 m, the detection range is:
Layer A: masks the area with a circle from about 0m to 9m.
Layer B: masks the area with a circle from about 0m to 3m.
i

Application manual
KNX standard wall presence detector with movement function EK-SN2-TP-…
Rev. 1.0 –29/09/2022 MAEKSN2TP_EN
© Ekinex S.p.A. –All rights reserved Pag. 10
Layer C: masks the area with a circle from about 0m to 1m.
Figure 6 - Layers scheme
Cut the supplied shield in such a way to remove the sectors corresponding to the desired detection
area.
Figure 7 –Example 1

Application manual
KNX standard wall presence detector with movement function EK-SN2-TP-…
Rev. 1.0 –29/09/2022 MAEKSN2TP_EN
© Ekinex S.p.A. –All rights reserved Pag. 11
Figure 8 - Example 2
Apply the screen by inserting the edge between the lens and the external ring, in the central and
lateral grooves.
Figure 9 - Shield installation
When the device is installed in place, make sure that the shield is in the correct position according
to the required area masking.
To remove the shield, press slightly with a screwdriver in the central groove and remove it carefully
Figure 10 - Shield removal
10 Mounting and installation
Warning! The electrical connection of the device can be carried out only by qualified
personnel. The incorrect installation may result in electric shock or fire. Before
making the electrical connections, make sure the power supply has been turned off.
Warning! In order to supply the KNX bus lines use only KNX bus power supplies
(e.g. ekinex EK-AB1-TP, EK-AG1-TP or EK-AM1-TP). The use of other power
supplies can compromise the communication and damage the devices connected
to the bus.
The device has an IP20 degree of protection and is therefore suitable for use in dry indoor environments. With reference
environments. With reference to
Figure 11, the device can be assembled on a round or square box.

Application manual
KNX standard wall presence detector with movement function EK-SN2-TP-…
Rev. 1.0 –29/09/2022 MAEKSN2TP_EN
© Ekinex S.p.A. –All rights reserved Pag. 12
To assemble the device, carry out the following operations:
disassemble the detector head and the plastic frame from the power box;
insert the plastic adapter (c) on the device (d);
insert the bus terminal, previously connected to the bus cable (see: “Connecting to the KNX
bus line”), in the appropriate seat on the back of the sensor; please provide to strip off 5-6mm
of cable sheathing by using a tool;
put the detector head and the plastic frame together, then fix the adapter-device assembly
(c+d) by means of the pair of screws (e) on the flush-mount wall box (a) with suitable holes,
possibly inserting (if applicable) the frame (b) between the box and the adapter;
snap-fit the plate (f).
Figure 11 - Installation for round and square flush mounting box
Figure 12 - Wire stripping

Application manual
KNX standard wall presence detector with movement function EK-SN2-TP-…
Rev. 1.0 –29/09/2022 MAEKSN2TP_EN
© Ekinex S.p.A. –All rights reserved Pag. 13
Warning:
Do not mount on conductive surface.
Do not open the enclosure frequently.
The sensor is a low voltage circuit; never connect it with the 230V line network.
Do not run the KNX wiring in the same conduit used by line network wiring.
11 Connection of the KNX bus line
The connection of the KNX bus line is made with the terminal block included in delivery and inserted
into the slot of the housing. At this point it is recommended to carry out the commissioning of the
device (see “Commissioning”), or at least the download of the physical address, using the pro-
gramming button placed close to the bus connector.
12 Configuration and commissioning
Nota: The configuration and commissioning of KNX devices require specialized skills.
To acquire these skills, you should attend the workshops at KNX certified training
centers.
Configuration and commissioning of the device require the use of the ETS®(Engineering Tool
Software) program V5 or later releases. These activities must be carried out according to the design
of the building automation system done by a qualified planner.
For the configuration of the device parameters the corresponding application program or the whole
ekinex®product database must be loaded in the ETS®program.
Code
Application program
(## = release)
EK-SN2-TP
APEKSN2TP##.knxprod
For the commissioning of the device the following activities are required:
make the electrical connections as described above;
turn on the bus power supply;
switch the device operation to the programming mode by pressing the programming
pushbutton; the blue programming LED (visible through the device lens) turns ON;
download into the device the physical address and the configuration with the ETS®program.
At the end of the download, the operation of the device automatically returns to normalmode. During
the programming process, the programming LED is turned off.
Now the bus device is programmed and ready for use.
i

Application manual
KNX standard wall presence detector with movement function EK-SN2-TP-…
Rev. 1.0 –29/09/2022 MAEKSN2TP_EN
© Ekinex S.p.A. –All rights reserved Pag. 14
IMPORTANT:
After a download, it takes approximately 60 s for the sensor to stabilize before it enters
normal operation mode.
Both the light output channels and the red LED are steady ON during the warm-up
phase, and they are switched OFF at the end.
During this settling period, the sensor may not appear to reactor perform itsprogrammed
functions.
13 Operations
13.1 Slide switch setup
By using a screwdriver in the center groove (1), pull out the cover of slide switch slightly (2).
Turn it upwards to access the switch (3).
Once the setting is complete, turn the cover downwards in its original position.
Figure 13 - Slide switch access
13.2 Slide switch functions
The slide switch allows to set the following parameters.
AUTO: by placing the switch in the central position, the detector is in AUTO mode.
ON: In ON mode, the load remains ON for 8 hours and the LED flashes for 1 second every
5 seconds. After 8 hours, the detector automatically returns to AUTO mode.
OFF: in the OFF position, the load remains OFF for 8 hours and the LED flashes for 1 second
every 5 seconds. After 8 hours, the detector automatically returns to AUTO mode.
In the event of a power failure, the detector enters AUTO mode once the power is supplied again,
even the switch is set to ON or OFF.
i

Application manual
KNX standard wall presence detector with movement function EK-SN2-TP-…
Rev. 1.0 –29/09/2022 MAEKSN2TP_EN
© Ekinex S.p.A. –All rights reserved Pag. 15
Figure 14 - Slide switch function setup
13.3 Walk test
The purpose of the walk test is to select a proper location and verify the desired detection coverage.
Lux setting value is not regarded during this process.
First of all, make sure the tester is within the detection coverage and the sensor is connected to the
powered KNX bus and allow the 60 s warm-up time to pass. During this timeframe, the red LED
turns on, then turns off after warming up time is expired.
Set the operating mode to “Test” via ETS®, then refer to the following steps:
Walk from outside across to the detection pattern until red LED and load turn on for approx. 2s, then turn off again. The
2s, then turn off again. The next trigger should be after 2s (please refer to
Figure 15).
If required, adjust the sensitivity setting through ETS®.
Also if required, adjust the time setting through ETS®.
Repeat the procedure in other selected radial directions, particularly if a shield is applied on
the lens.
Repeat the above steps until desired performance is achieved.
Figure 15 - Walk Test

Application manual
KNX standard wall presence detector with movement function EK-SN2-TP-…
Rev. 1.0 –29/09/2022 MAEKSN2TP_EN
© Ekinex S.p.A. –All rights reserved Pag. 16
13.4 Auto / Semi-auto mode (absence detection function)
This function is enabled with ETS®setting and it is used to activate / deactivate Auto mode or Semi-
auto mode of Light control output C1.
The behaviour is as follows:
Under auto mode, the load will turn on automatically when a movement is detected and the
ambient light level is below the Lux setting value. When movement is no longer detected and
the delay time has expired, the load will turn off automatically.
Under semi-auto mode, the load can only be manually switched on by operating via a
connected external pushbutton. When the load is switched on, it will keep be on if the
movements are detected constantly. The load will turn off only when movement is no longer
detected and the delay time has expired.
Please refer to section 14.3 for further information.
13.5 Test mode
Parameters can be set via ETS®. Test mode switches to the RUN status after “storing”, or 10 min
after activating the test mode. Load and red LED are not controlled by Lux setting under the Test
mode. Once the detector is triggered, both load and red LED turn on for 2s, then turn off, and the
next triggering should be 2 sec interval.
IMPORTANT:
The settings of functions described in paragraphs 13.6, 13.7, 13.8, 13.9 and 13.10 are
intended for lighting control, therefore do not apply to HVAC control.
13.6 Manual ON / OFF and DIM switching function
This function is enabled with ETS®setting and operated either by the slide switch loacted under the
frontal cover, or through a connected KNX interface module on KNX bus system.
Please refer to section “Parameter setting“ - “Communication objects description“ for further
information.
13.7 Master / Slave selection
This function can only be set via ETS®software and it allows to set the device as a master or slave
device:
when detector is enabled as master device, all the functions are available and it also can
receive the triggering signal from one or more slave detectors;
if it is enabled as slave detector, then it works exclusively to extend the field of detection and
all its function are managed by a master detector.
Please refer to section “Parameter setting“ - “Communication objects description“ for further
information.
13.8 Ambient light appraisal
In case of changeable ambient light level, the detector can postpone delay time of turning on and off
loads, in order to avoid its unnecessary on or off switching.
This behaviour works in two ways:
The ambient light level changes from bright to dark: to avoid unnecessary switching on / off
of the load due to temporary variations in the ambient light value caused by events (e.g.
i

Application manual
KNX standard wall presence detector with movement function EK-SN2-TP-…
Rev. 1.0 –29/09/2022 MAEKSN2TP_EN
© Ekinex S.p.A. –All rights reserved Pag. 17
passing cloud), the detector has been designed with a delay of 10 s for light activation, i.e. it
will ignore any movement within the 10 s delay time. The red LED will be on steady as an
indication, but the detector will not react within this timeframe.
The ambient light level changes from dark to bright: if the ambient light level exceeds the
“Switch ON Lux value”for 5 min, there are different reactions according to the value of the
“Lighting delay time” parameter:
oIf Lighting delay time > 5 min: the light will be automatically switched off after 5 min.
oif Lighting delay time < 5 min:the light will be automaticallyswitched off when the set time
expires, if no movement is detected within the 5 min. timeframe. But if any movement is
detected within the 5 min timeframe, the time will be reset upon detection and the light is
switched off after 5 min.
13.9 2-level (Standby Lighting) function
In Auto mode and when Output type is set to “Dimming”, when the ambient light level falls below the
pre-set “Switch ON Lux value”, the detector will enter into 2-level mode function automatically.
if “StandbyTime” is set to “Infinity”,the detector will enter into 2-level mode when the “Lighting
delay time” is expired. In this situation, if a movement is detected, the load will turn on with
the setting illumination (100% or the dimmed value according to the setting of “Standby
brightness) and then turn off if movement is no longer detected and the “Lighting Delay time”
has expired. It will be cycled until the ambient light level is higher than the “Switch ON Lux
value”and it lasts for 5min, then turns off and the detector resumes to Auto mode function.
if “Standby Time” is set to other position except for “infinity”, the detector behaviour is
basically the same as above mentioned, but the duration is according to the selected
“Standby Time” value.
If “Lighting standby time” is set to “disable” (OFF), the load willbe off when the “Lighting delay
time”is expired.
13.10Constant light control
According to the changeable ambient light level, if “Constant light control” is set to Enabled, then the
load can dim to bright or dark automatically to match the “Preset setpoint” Lux value.
13.11Alarm
The alarm function can be set to behave in the same way in case of switching on or off, or in a
different way depending on the event.
The Alarm output (Communication Object 18) can be locked using CO 17 (Lock alarm).
Options for “Behaviour at switching ON (or OFF) lock by CO are “no reaction”, “switch OFF” and
“switch ON”.
The number of detected movements (“windows”) within a time frame (“Duration”) can be set.

Application manual
KNX standard wall presence detector with movement function EK-SN2-TP-…
Rev. 1.0 –29/09/2022 MAEKSN2TP_EN
© Ekinex S.p.A. –All rights reserved Pag. 18
14 List of ETS®parameters
The parameters available in ETS®are detailed in the next sections.
14.1 Menu: General
Figure 16 - General parameters window
Parameter name
Conditions
Values [Default]
Device type
-
Master
Slave
When the sensor is configured as master, all features are available; it can also receive the trigger signal
from one or more slave sensors for only one of the 4 output channels available.
When the sensor is configured as slave, it can only be used to extend the field of coverage for a master
sensor.
Input slave
Device type = Master
Light output C1
Light output C2
HVAC output C3
HVAC output C4
Assign the signal from the slave to one of the device channels.
Measured Lux value report
Disable
Enable
When enabled, the measured ambient brightness value in Lux is transmitted on the bus every 5 s.
Light control output C1
Device type = Master
Disable
Enable
Enable the control channel and show the respective group of parameters.
Light control output C2
Device type = Master
Disable
Enable
Enable the control channel and show the respective group of parameters.

Application manual
KNX standard wall presence detector with movement function EK-SN2-TP-…
Rev. 1.0 –29/09/2022 MAEKSN2TP_EN
© Ekinex S.p.A. –All rights reserved Pag. 19
Parameter name
Conditions
Values [Default]
HVAC control output C3
Device type = Master
Disable
Enable
Enable the control channel and show the respective group of parameters.
HVAC control output C4
Device type = Master
Disable
Enable
Enable the control channel and show the respective group of parameters.
Alarm function
Device type = Master
Disable
Enable
Enable the alarm function and show the respective group of parameters.
14.2 Menu: Motion sensors
Figure 17 - Motion sensors parameters window
Parameter name
Conditions
Values [Default]
External switch
as ON / OFF / Dim input
Device type = Master
No
Yes
If enabled, each channel can also be controlled from the KNX bus through communication objects #5-6-
7-8.
For Light control channels, the CO (which is of 1-bit Switch type) also controls the dimming function.
The Manual ON/OFF and DIM function is operated by the switch built-in/connected with KNX interface
module on KNX bus system.
Lux / Time /
Sensitivity(Meter)/
STBY selected by
Device type = Master
ETS
IR
It is used to set the parameter of Lux, Time, Sensitivity (Meter), STBY of detector is changed by ETS®
software or IR remote control (not available in this product version). When the control mode is set to
“ETS”, all the parameters on detector can only be changed by ETS®after completing the object build up.
Note: this setting is only relevant for the two Light Control channels (C1-C2).

Application manual
KNX standard wall presence detector with movement function EK-SN2-TP-…
Rev. 1.0 –29/09/2022 MAEKSN2TP_EN
© Ekinex S.p.A. –All rights reserved Pag. 20
Parameter name
Conditions
Values [Default]
Test mode
Device type = Master
Disable
Enable
If enabled, test mode is activated after the program download and exits automatically after 10 min. Then
enters into auto mode or semi-auto mode according to the setting item of “Auto-Semi-auto select”.
If test mode function is activated, once the movement is detected, both the load and LED will be 2 sec on
and 2 sec off.
Sensor sensitivity
Maximum
High
Medium
Low
OFF
It is used to increase or decrease the sensitivity of PIR in the device. The sensitivity can be adjusted
according to user’s requirement no matter the detector is master or slave.
Maximum: Highest sensitivity
High: Higher sensitivity
Medium: Medium sensitivity
Low: Lowest sensitivity
OFF: Detecting function of PIR is deactivated
LED turns on when PIR is
triggered
Disable
Enable
It is used to set the switch on of the indicator LED when PIR is triggered.
When enabled, the red LED will turn on for 1 s every time movement is detected. This indication can be
suppressed (disable); however, all other indication functions of the LED remain enabled.
14.3 Menus: Light control output C1 / C2
Following parameters are repeated for each of the two Light Control channels C1 and C2.
Although not specified below, these options are only listed if the corresponding channels are active.
Figure 18 - Light control output C1 / C2 –Switching parameters
This manual suits for next models
1
Table of contents
Other Ekinex Security Sensor manuals
Popular Security Sensor manuals by other brands

LST
LST 5351E Specification sheet

Kolibri
Kolibri Bishop user manual

Johnson Controls
Johnson Controls tyco Bentel Security BW-SHK installation instructions

ADA INSTRUMENTS
ADA INSTRUMENTS Wall Scanner 80 operating manual

PCB Piezotronics
PCB Piezotronics RH240M20 Installation and operating manual

ESYLUX
ESYLUX PD-C360i/24 DIMplus manual