Electrex EXA TR D6 User manual

INSTALLATION GUIDE
EXA TR D6 4-20mA
MECHANICAL CHARACTERISTICS
Case Self-extinguishing plastic material class V0
Protection degree IP40 on front panel. IP20 terminals side
Size 105 x 90 x 58 mm (6 moduli DIN)
CURRENT INPUT
Direct Up to 290 Vrms phase-neutral
or 502 Vrms phase to phase
With external PT(VT) Primary: programmable (max. 400 kV)
Secondary: programmable (max. 300 V)
Overload: 900 Vrms phase to phase for 1 sec
Power supply 230/240Vac +/- 10% 50/60Hz
Self consumption < 2,5VA
MODELLI
PFAE6T1-62 EXA TR D6 RS485 230-240V 2AO4-20mA
ENERGY ANALYZER
Exa TR D6
Energy analyzer Transducer
1000 imp/kvarh
1000 imp/kWh
00 i
000 i
m
00 i
00 i
m
E
x
E
x
1
2
3
LED
Description of the LEDs
LED (1) Under the sine wave symbol next to the Electrex logo a red LED indicates the
operation status
LED (2) Two red LEDs, for calibration checking, pulse with a frequency proportional to the
active and reactive energy imported.
LED (3) Two other LEDs, below the white band, indicate the communication activities of
the RS485 port (red LED TX, green LED RX)
ANALOGUE OUTPUTS CONNECTION
C
10
1
11
2
12
AUX
IN/OUT
!
Max 250 ohm
R max = (Vdc / 0.027) + 250
Vdc R max
5 435
9 583
12 694
24 1138
The voltage to be applied is given by the following formula:
V = (R-250) x 0.027
(Eg. with an impedance of 1 ohm, the voltage to be applied
is:
(1000-250) x 0.027= 20.25 Vdc
For loads with impedance less than or equal to 250 ohms follow the diagrams below.
For loads with higher impedance of 250 ohms it is necessary to include in series an
external power supply.
Exa TR D6
Energy analyzer Transducer
1000 imp/kvarh
1000 imp/kWh
S1 S2 S1 S2 S1 S2
19 2017 18V1 V2 V3
AUX
IN/OUT
VOLTAGE INPUTS POWER
SUPPLY
CURRENT INPUTS
N21
AB
T
10 11 12
RS-485 AUX
IN/OUT
I1 I2 I3
230 V~
24V =
N L
- +
Further documentation may be downloaded from our web site www.electrex.it.
This document is owned by company AKSE that reserves all rights.
DECLARATION OF CONFORMITY
Akse hereby declares that its range of products complies with the following directives EMC
89/336/EEC 73/23CE 93/68 CE and complies with the following product’s standard
CEI EN 61326 – IEC 61326 CEI EN 61010 – IEC 61010.
The product has been tested in the typical wiring confi guration and with peripherals
conforming to the EMC directive and the LV directive.
COPYRIGHT
Electrex is a trademark of Akse S.r.l. All rights reserved.
It is forbidden to duplicate, adapt, transcript this document without Akse written
authorization, except when regulated accordingly by the Copyright Laws.
WARRANTY
This product is covered by a warranty against material and manufacturing defects for a 24
months period from the manufacturing date.
The warranty does not cover the defects that are due to:
• Negligent and improper use
• Failures caused by atmospheric hazards
• Acts of vandalism
• Wear out of materials
• Firmware upgrades
Akse reserves the right, at its discretion, to repair or substitute the faulty products
The warranty is not applicable to the products that will result defective in consequence of
a negligent and improper use or an operating procedure not contemplated in this manual.
RETURN AND REPAIR FORMALITIES
Akse accepts the return of instruments for repair only when authorized in advance. The
transport costs are at customer charge.
RE-SHIPPING OF REPAIRED PRODUCT
The terms for re-shipment of repaired products are ex-works, i.e. the transport costs are
at customer charge.
Products returned as detective but found to be perfectly working by our laboratories, will
be charged a fl at fee to account for checking and testing time irrespective of the warranty
terms.
SAFETY
This instrument was manufactured and tested in compliance with IEC 61010-1 CAT III -
300V class 2 standards for operating voltages up to 300 VAC rms phase to neutral.
In order to maintain this condition and to ensure safe operation, the user must comply with
the indications and markings contained in the following instructions:
• When the instrument is received, before starting its installation, check that it is
intact and no damage occurred during transport.
• Before mounting, ensure that the instrument operating voltages and the mains
voltage are compatible then proceed with the installation.
• The instrument power supply needs no earth connection.
• The instrument is not equipped with a power supply fuse; a suitable external
protection fuse must be foreseen by the contractor.
• Maintenance and/or repair must be carried out only by qualifi ed, authorized
personnel
• If there is ever the suspicion that safe operation is no longer possible, the instrument
must be taken out of service and precautions taken against its accidental use.
• Operation is no longer safe when:
1) There is clearly visible damaged.
2) The instrument no longer functions.
3) After lengthy storage in unfavorable conditions.
4) After serious damage occurred during transport
The instruments must be installed in respect of all the local regulations.
OPERATOR SAFETY
Warning: Failure to observe the following instructions may lead to a serious danger of
death.
• During normal operation dangerous voltages can occur on instrument terminals and
on voltage and current transformers. Energized voltage and current transformers
may generate lethal voltages. Follow carefully the standard safety precautions while
carrying out any installation or service operation.
• The terminals of the instrument must not be accessible by the user after the installation.
The user should only be allowed to access the instrument front panel where the
display is located.
• Do not use the digital outputs for protection functions nor for power limitation functions.
The instrument is suitable only for secondary protection functions.
• The instrument must be protected by a breaking device capable of interrupting both
the power supply and the measurement terminals. It must be easily reachable by the
operator and well identifi ed as instrument cut-off device.
• The instrument and its connections must be carefully protected against short-circuit.
Precautions: Failure to respect the following instructions may irreversibly damage to the
instrument.
• The outputs and the options operate at low voltage level; they cannot be powered by
any unspecifi ed external voltage.
• The application of currents not compatible with the current inputs levels will damage
to the instrument.
ANALOGUE OUTPUT
C Common (negative)
1 Output 1 (positive)
2 Output 2 (positive)

The instrument is shipped with the following default values :
PAGE PARAMETERS VALUES AVAILABLE DEFAULT
PASSWORD REQUEST 0000 ... 9999 0000
RS485
RS485 Address 1 ... 247 27
Rate 2400, 4800, 9600, 19200, 38400 38400
Data Bit 7 o 8 8
Parity N = no parity, E = even, O = odd N
Stop Bit 1 or 2 2
NETWORK
Type (note n.1) 3PH-4W, 2PH-2W, 1PH-2W, 3PH-4W-BAL,
3PH-3W-2CT 3PH-4W
Export NO, YES NO
CT 10000/1 o 5 5/5
VT 400000/300 1/1
AVG-MD TIME (note n.2)
POWERS 1...60 (minutes) 15
CURRENTS 1...60 (minutes) 8
ALARM 1 / A (note n.8)
MODE (note n.3) Normal, 1-OF-3, 3-OF-3, DERIV, UNBAL NORMAL
TYPE (note n.4) MAX, MIN MIN
MEAS (note n.5) Controlled measure. See table n.1 for register
selection 200
THRE (note n.5) Threshold value 0
ALARM 1 / B
HYST 1...100 (%) 1
DELAY 1...99 (seconds) 1
AVG (note n.6) 1...99 (seconds) 1
OUT (note n.7) Normal, Hold, Pulse-L, Pulse-S NORMAL
ALARM 2 / A (note n.8)
MODE (note n.3) Normal, 1-OF-3, 3-OF-3, DERIV, UNBAL NORMAL
TYPE (note n.4) MAX, MIN MIN
MEAS (note n.5) Controlled measure. See table n.1 for register
selection 200
THRE (note n.5) Threshold value 0
ALARM 2 / B
HYST 1...100 (%) 1
DELAY 1...99 (seconds) 1
AVG (note n.6) 1...99 (seconds) 1
OUT (note n.7) Normal, Hold, Pulse-L, Pulse-S NORMAL
ALARM 3 / A (nota n.8)
MODE (note n.3) Normal, 1-OF-3, 3-OF-3, DERIV, UNBAL NORMAL
TYPE (note n.4) MAX, MIN MIN
MEAS (note n.5) Controlled measure. See table n.1 for register
selection 200
THRE (note n.5) Threshold value 0
ALARM 3 / B
HYST 1...100 (%) 1
DELAY 1...99 (seconds) 1
AVG (note n.6) 1...99 (seconds) 1
OUT (note n.7) Normal, Hold, Pulse-L, Pulse-S NORMAL
ALARM 4 / A (note n.8)
MODE (note n.3) Normale, 1-OF-3, 3-OF-3, DERIV, UNBAL NORMAL
TYPE (note n.4) MAX, MIN MIN
MEAS (note n.5) Misura controllata. Vedi tabella n.1 per la
selezione del registro 200
THRE (note n.5) Valore soglia 0
ALARM 4 / B
HYST 1...100 (%) 1
DELAY 1...99 (seconds) 1
AVG (note n.6) 1...99 (seconds) 1
OUT (note n.7) Normal, Hold, Pulse-L, Pulse-S NORMAL
ANALOG OUT 1
MEAS (note n.5) Controlled measure. See table n.1 for register
selection
200
MODE 4-20, 0-20 4-20
LOW (note n.9) 000.00
HIGH (note n.9) 000.00
ANALOG OUT 2
MEAS (note n.5) Controlled measure. See table n.1 for register
selection
200
MODE 4-20, 0-20 4-20
LOW (note n.9) 000.00
HIGH (note n.9) 000.00
NOTE n.1
3PH-4W 3 phases 4 wires, Star
2PH-2W 2 phases 2 wires, biphase
1PH-2W 1 phase 2 wires, monophase
3PH-4W-BAL 3 phases 4 wires, Star Balanced
3PH-3W-2CT 2 phases 3 wires, triangle
NOTE n.2
POWERS Integration time of the average value (AVG) and peak value (MD) for
power (from 1 to 60 minutes)
CURRENTS Integration time of the average value (AVG) and peak value (MD) for
current (from 1 to 60 minutes)
NOTE n.3
NORMALE Classic Alarm with reference to a fi xed threshold or to maximum and
minimum delay and applicable hysteresis. “AVG” parameter is not used.
1-OF-3 Consider also the 2 following registers of the selected one in “MEAS”.
Works on a fi xed max or min threshold with delay and applicable
hysteresis. If one of the three register exceed the threshold the alarm goes
on. “AVG” parameter is not used.
3-OF-3 Consider also the 2 following registers of the selected one in “MEAS”.
Works on a fi xed max or min threshold with delay and applicable hysteresis.
When all the three register exceed the threshold the alarm goes on. “AVG”
parameter is not used.
DERIV “THRE” parameter becomes a % value, “AVG” parameter is used. The
instant value applied to the alarm on “MEAS” is compared with its value
mediated obtained on the basis of the time set on “AVG”. When the
instantaneous value combined alarm differs in more (setting “Max”) or less
(setting “MIN”) from the average value (“ AVG “) of the percentage set on
“THRE” the alarm goes on. With delay and applicable hysteresis.
UNBAL Consider also the 2 following registers of the selected one in “MEAS”.
“THRE” parameter becomes a % value. Alarm goes on when one of the
three register is different from the percentage set on “THRE” comply with
the higher value of the three read register if “MAX” is set on “TYPE”, or
comply with the lower value of the three register if “MIN” is set on “TYPE”
With delay and applicable hysteresis.
NOTE n.4
MAX Alarm setting in excess compared with the established conditions.
With the exception of “UNBAL”.
MIN Alarm setting in decrease compared with the established conditions.
With the exception of “UNBAL”
NOTE n.5
MEAS Indicates which register (and thus measure) the alarm is related.
See table n.1 input register.
THRE Alarm threshold in absolute value, with the exception made for “DERIV”
and “UNBAL” in which the value inserted becomes a percentage.
NOTE n.6
AVG Parameter to be used only in “DERIV” mode. Is the duration of the refe-
rence (in seconds) used to create a reference value for the istantaneous
readings.
NOTE n.7
NORMAL Physical output of the alarm excited during the duration of the alarm. It
restores automatically
HOLD Output remains excited until manual reset made via Modbus
PULSE-L Output generate a 500ms impulse when the alarm goes on.
PULSE-S Output generate a 100ms impulse when the alarm goes on.
NOTE n.8
ALLARME 1 Only MODBUS alarm
ALLARME 2 Only MODBUS alarm
ALLARME 3 Only MODBUS alarm
ALLARME 4 Only MODBUS alarm
NOTE n.9
LOW Associated scale value starts at 0 and 4 mA
HIGH Full scale value associated with 20 mA
COMMUNICATION PROTOCOL
It is possible to obtain the communication protocol of the instrument by sending a request

akse srl Via Aldo Moro, 39 42124 Reggio Emilia Italy
P.I. 01544980350 R.E.A. 194296 Cap. Soc. Euro 85.800,00 i.v.
Subject to modifi cation without notice.
Edition 2015 04 24 ENG0031
STAR 4W (4 WIRES) 3PH-4W LV STAR 4W (4 WIRES) 3PH-4W-BAL
The instrument is fi tted with a separate power supply. The power supply terminals are
numbered (17 e 18). Use cables with max cross-section of 2,5 mm2 if stranded, 4 mm2 if
rigid.
POWER SUPPLY AND SERIAL LINE CONNECTION
Voltage connection: Use cables with max cross-section of 2,5 mm2 if stranded 4 mm2 if rigid and connect them to the clamps marked VOLTAGE INPUT on the instrument according to
the applicable diagrams that follow.
Current connection: It is necessary to use external CTs with a primary rating adequate to the load to be measured and with a 5A or 1A secondary rating. Connect the CT output(s) to
the terminals marked I1, I2, I3 (CURRENT INPUT) of the instrument according to the applicable diagrams that follow.Use cables with cross-section adequate to the VA rating of the CT
and to the distance to be covered. The max cross-section for the terminals is 2,5 mm2 if stranded and 4 mm2 if rigid.
N.B. The CT secondary must always be in short circuit when not connected to the instrument in order to avoid damages and risks for the operator.
Scrupulously respect the matching of phase between the voltage signals and current signals (RTD) and the direction of insertion of CT (P1-P2 and S1-S2). Failure to comply with this
correspondence and connection diagrams gives rise to measurement errors. (*) The grounding of S2 must be close to the CT and not near the instrument.
VOLTAGE AND CURRENT CONNECTION
STAR 4W (4 WIRES) 3PH-4W MV
MONOFASE (2 WIRES) 1PH-2WTRIANGLE 3W (3 WIRES) 3PH-3W TRIANGLE 2CT (3 WIRES) 3PH-3W
TRIANGLE 2CT (3 WIRES) 3PH-3WTRIANGLE 2CT(3 WIRES) 3PH-3W TRIANGLE 2CT (3 WIRES) 3PH-3W
BI-PHASE (2 WIRES) 2PH-2W
Made
in Italy
Pensato, progettato e prodotto in Italia
Engineered and manufactured in Italy
Exa TR D6
Energy analyzer Tran sduce r
1000 imp/kvarh
1000 imp/kWh
S1 S2 S1 S2 S1 S2
19 2017 18V1 V2 V3
AUX
IN/OUT
VOLTAGE INPUTS POWER
SUPPLY
CURRENT INPUTS
N21
AB
T
10 11 12
RS-485 AUX
IN/OUT
I1 I2 I3
S1 S2
P1 P2
L1
L2
L3
N
S1 S2
P1 P2
S1 S2
P1 P2
*
Exa TR D6
Energy analyzer Tran sduce r
1000 imp/kvarh
1000 imp/kWh
S1 S2 S1 S2 S1 S2
19 2017 18V1 V2 V3
AUX
IN/OUT
VOLTAGE INPUTS POWER
SUPPLY
CURRENT INPUTS
N21
AB
T
10 11 12
RS-485 AUX
IN/OUT
I1 I2 I3
S1 S2
P1 P2
L1
L2
L3
S1 S2
P1 P2
S1 S2
P1 P2
*Exa TR D6
Energy analyzer Transducer
1000 imp/kvarh
1000 imp/kWh
S1 S2 S1 S2 S1 S2
19 2017 18V1 V2 V3
AUX
IN/OUT
VOLTAGE INPUTS POWER
SUPPLY
CURRENT INPUTS
N21
AB
T
10 11 12
RS-485 AUX
IN/OUT
I1 I2 I3
S1 S2
P1 P2
L1
N
*
Exa TR D6
Energy analyzer Tran sduce r
1000 imp/kvarh
1000 imp/kWh
S1 S2 S1 S2 S1 S2
19 2017 18V1 V2 V3
AUX
IN/OUT
VOLTAGE INPUTS POWER
SUPPLY
CURRENT INPUTS
N21
AB
T
10 11 12
RS-485 AUX
IN/OUT
I1 I2 I3
S1 S2
P1 P2
L1
L2
L3
S1 S2
P1 P2
S1 S2
P1 P2
*
Exa TR D6
Energy analyzer Transducer
1000 imp/kvarh
1000 imp/kWh
S1 S2 S1 S2 S1 S2
19 2017 18V1 V2 V3
AUX
IN/OUT
VOLTAGE INPUTS POWER
SUPPLY
CURRENT INPUTS
N21
AB
T
10 11 12
RS-485 AUX
IN/OUT
I1 I2 I3
S1 S2
P1 P2
L1
L2
L3
N
*
Exa TR D6
Energy analyzer Tran sduce r
1000 imp/kvarh
1000 imp/kWh
S1 S2 S1 S2 S1 S2
19 2017 18V1 V2 V3
AUX
IN/OUT
VOLTAGE INPUTS POWER
SUPPLY
CURRENT INPUTS
N21
AB
T
10 11 12
RS-485 AUX
IN/OUT
I1 I2 I3
S1 S2
P1 P2
L1
L2
L3
S1 S2
P1 P2
*
Exa TR D6
Energy analyzer Tran sduce r
1000 imp/kvarh
1000 imp/kWh
S1 S2 S1 S2 S1 S2
19 2017 18V1 V2 V3
AUX
IN/OUT
VOLTAGE INPUTS POWER
SUPPLY
CURRENT INPUTS
N21
AB
T
10 11 12
RS-485 AUX
IN/OUT
I1 I2 I3
S1 S2
P1 P2
L1
L2
L3
S1 S2
P1 P2
*
Exa TR D6
Energy analyzer Tran sduce r
1000 imp/kvarh
1000 imp/kWh
S1 S2 S1 S2 S1 S2
19 2017 18V1 V2 V3
AUX
IN/OUT
VOLTAGE INPUTS POWER
SUPPLY
CURRENT INPUTS
N21
AB
T
10 11 12
RS-485 AUX
IN/OUT
I1 I2 I3
S1 S2
P1 P2
L1
L2
L3
S1 S2
P1 P2
*
Exa TR D6
Energy analyzer Transducer
1000 imp/kvarh
1000 imp/kWh
S1 S2 S1 S2 S1 S2
19 2017 18V1 V2 V3
AUX
IN/OUT
VOLTAGE INPUTS POWER
SUPPLY
CURRENT INPUTS
N21
AB
T
10 11 12
RS-485 AUX
IN/OUT
I1 I2 I3
S1 S2
P1 P2
L1
L2
L3
S1 S2
P1 P2
*
Exa TR D6
Energy analyzer Tran sduce r
1000 imp/kvarh
1000 imp/kWh
S1 S2 S1 S2 S1 S2
19 2017 18V1 V2 V3
AUX
IN/OUT
VOLTAGE INPUTS POWER
SUPPLY
CURRENT INPUTS
N21
AB
T
10 11 12
RS-485 AUX
IN/OUT
I1 I2 I3
S1 S2
P1 P2
L1
L2
*Exa TR D6
Energy analyzer Transducer
1000 imp/kvarh
1000 imp/kWh
S1 S2 S1 S2 S1 S2
19 2017 18V1 V2 V3
AUX
IN/OUT
VOLTAGE INPUTS POWER
SUPPLY
CURRENT INPUTS
N21
AB
T
10 11 12
RS-485 AUX
IN/OUT
I1 I2 I3
230-240VAC FUSE
T 500mA
Other Electrex Measuring Instrument manuals

Electrex
Electrex EXA 96 User manual

Electrex
Electrex FEMTO D4 User manual

Electrex
Electrex ZEPTO D6 User manual

Electrex
Electrex NET D6 User manual

Electrex
Electrex KILO User manual

Electrex
Electrex MICO DELTA User manual

Electrex
Electrex Zepto D6 User manual

Electrex
Electrex PLUS96 Y User manual

Electrex
Electrex FEMTO D4 DC User manual

Electrex
Electrex FEMTO 96 User manual