Electrex Zepto D6 User manual

akse srl Via Aldo Moro, 39 42100 Reggio Emilia Italy
VAT IT 01544980350 R.E.A. 194296 Cap. Soc. Euro 85.800,00 i.v.
COPYRIGHT
Electrex is a trademark of Akse S.r.l. All rights reserved.
It is forbidden to duplicate, adapt, transcript this document without Akse written
authorization, except when regulated accordingly by the Copyright Laws.
WARRANTY
This product is covered by a warranty against material and manufacturing defects for
a period of 24 months period from the manufacturing date.
The warranty does not cover the defects that are due to:
• Negligent and improper use
• Failures caused by atmospheric hazards
• Acts of vandalism
• Wear out of materials
• Firmware upgrades
Akse reserves the right, at its discretion, to repair or substitute the faulty products
The warranty is not applicable to the products that will result defective in consequence
of a negligent and improper use or an operating procedure not contemplated in this
manual.
RETURN AND REPAIR FORMALITIES
Akse accepts the return of instruments for repair only when authorized in advance.
The transport costs are at customer charge.
RE-SHIPPING OF REPAIRED PRODUCT
The terms for re-shipment of repaired products are ex-works, i.e. the transport costs
are at customer charge.
Products returned as detective but found to be perfectly working by our laboratories,
will be charged a flat fee to account for checking and testing time irrespective of the
warranty terms.
SAFETY
This instrument was manufactured and tested in compliance with IEC 61010 class 2
standards for operating voltages up to 250 VAC rms phase to neutral.
In order to maintain this condition and to ensure safe operation, the user must comply
with the indications and markings contained in the following instructions:
• When the instrument is received, before starting its installation, check that it
is intact and no damage occurred during transport.
• Before mounting, ensure that the instrument operating voltages and the
mains voltage are compatible then proceed with the installation.
• The instrument power supply needs no earth connection.
• The instrument is not equipped with a power supply fuse; a suitable external
protection fuse must be foreseen by the contractor.
• Maintenance and/or repair must be carried out only by qualified, authorized
personnel
• If there is ever the suspicion that safe operation is no longer possible, the
instrument must be taken out of service and precautions taken againstits
accidental use.
• Operation is no longer safe when:
1) There is clearly visible damage.
2) The instrument no longer functions.
3) After lengthy storage in unfavorable conditions.
4) After serious damage occurred during transport
The instruments must be installed in respect of all the local regulations.
OPERATOR SAFETY
Warning: Failure to observe the following instructions may lead to a serious danger
of death.
• During normal operation dangerous voltages can occur on instrument terminals
and on voltage and current transformers. Energized voltage and current
transformers may generate lethal voltages. Follow carefully the standard safety
precautions while carrying out any installation or service operation.
• The terminals of the instrument must not be accessible by the user after the
installation. The user should only be allowed to access the instrument front panel
where the display is located.
• Do not use the digital outputs for protection functions nor for power limitation
functions. The instrument is suitable only for secondary protection functions.
• The instrument must be protected by a breaking device capable of interrupting both
the power supply and the measurement terminals. It must be easily reachable by
the operator and well identified as instrument cut-off device.
• The instrument and its connections must be carefully protected against short-
circuit.
Precautions: Failure to respect the following instructions may irreversibly damage to
the instrument.
• The instrument is equipped with PTC current limiting device but a suitable external
protection fuse should be foreseen by the contractor.
• The outputs and the options operate at low voltage level; they cannot be powered
by any unspecified external voltage.
• The application of currents not compatible with the current inputs levels will
damage to the instrument.
READINGS
READINGS DISPLAYED
(The parameters available vary according to instrument configuration)
Uf I P QSPF
Press to scroll readings
L-N f I P Q S PF
L-L In P Avg Q L Avg S Avg
THD L-N THD P MD Q C Avg S MD
THD L-L I Avg Q L MD
I MD Q C MD
READINGS DISPLAYED
(The parameters available vary according to instrument configuration)
Press to change readings
Press for 2
seconds
Ea ∑Er L ∑Er C ∑Es ∑
Ea ∑E2 Er L ∑E2 Er C ∑E2 Es ∑E2
CNT ∑CNT E2
TIME ∑TIME E2
LEGEND OF PARAMETERS AND SYMBOLS
L-N Phase Neutral UVoltage
L-L Phase Phase ICurrent
THD Total Harmonic Distortion In Neutral current
Avg Average (rolling) value PActive Power
MD Maximum Demand QReactive Power
LInductive SApparent Power
CCapacitive PF Power Factor
TIME ∑Life Time (total) (hour/100) Ea Active Energy
TIME E2Life Time (partial) (hour/100) Er Reactive Energy
CNT ∑Pulse count (total) Es Apparent Energy
CNT E2Pulse count (partial) f Frequency
Further documentation may be downloaded from our web site www.electrex.it.
This document is owned by company AKSE that reserves all rights.
DECLARATION OF CONFORMITY
Akse hereby declares that its range of products complies with the following directives
EMC 89/336/EEC 73/23CE 93/68 CE and complies with the following product’s
standard CEI EN 61326 – IEC 61326 CEI EN 61010 – IEC 1010.
The product has been tested in the typical wiring configuration and with peripherals
conforming to the EMC directive and the LV directive.
Subject to modification without notice. Preliminary. Edition 18-02-2008.
!
ZEPTO D6
INSTALLATION INSTRUCTIONS
MECHANICAL CHARACTERISTICS
Enclosure Self-extinguishing plastic material class V0
Protection degree IP40 on front panel, IP20 terminals side
Dimensions 105 x 90 x 58 mm (6 DIN modules)
VOLTAGE INPUT
Direct Up to 300 Vrms phase-neutral
or 519 Vrms phase to phase
With external PT(VT) Primary: programmable (max. 400 kV)
Secondary: programmable (max. 300 V)
Overload: 900 Vrms phase to phase for 1 sec
Power supply 230/240Vac +/- 10% 50/60Hz
Self consumption < 3VA
MODELS
PFA8611-02 ZEPTO D6 RS485 230-240V
ENERGY ANALYSER
PFA8611-12 ZEPTO D6 RS485 230-240V 1DI 2DO
ENERGY ANALYSER

akse srl Via Aldo Moro, 39 42100 Reggio Emilia Italy
VAT IT 01544980350 R.E.A. 194296 Cap. Soc. Euro 85.800,00 i.v.
The instrument is fitted with a separate power supply. The power supply terminals are
numbered (17) and (18). Use cables with max cross-section of 2,5 mm2if flexible, 4
mm2if rigid.
Voltage connection
Use cables with max cross-section of 2,5 mm2if flexible 4 mm2if rigid and connect them to the terminals marked voltage input on the instrument according to the applicable
diagrams that follow.
Current connection
It is necessary to use external CTs with a primary rating adequate to the load to be metered and with a 5A or 1A secondary rating. The number of CTs to be used (1, 2 or 3)
depends upon the type of network. Connect the CT output(s) to the terminals marked I1, I2, I3 (current input) of the instrument according to the applicable diagrams that follow.
Use cables with cross-section adequate to the VA rating of the CT and to the distance to be covered. The max cross-section for the terminals is 4 mm2.
N.B. The CT secondary must always be in short circuit when not connected to the instrument in order to avoid damages and risks for the operator.
Warning: The phase relationship among voltage and current signals, the P1-P2 orientation and the S1-S2 connection of the CT(s) must be carefully respected.
All disregard of this rule or of the wiring diagram leads to severe measurement errors.
S1 S2 S1 S2 S1 S2 A B
T
10 11 12
I1 I2 I3 RS-485 AUX
17 18 19 20U1 U2 U3 N
AUXVOLTAGE INPUT POWER
S1 S2
P1 P2
L1
L2
L3
N
S1 S2
P1 P2
S1 S2
P1 P2
4W Star (4 wire) 3PH-4W
POWER SUPPLY and SERIAL LINE CONNECTION CONFIGURATION SETUP
C
10
1
11
2
12
AUX
IN/OUT
!
Common
12
11
10
DO2
DO1
DI (+)
20
19
DI (-)
3W Delta (3 wire) 3PH-3W-2CT SINGLE PHASE 1PH-2W
S1 S2 S1 S2 S1 S2 A B
T
10 11 12
I1 I2 I3 RS-485 AUX
17 18 19 20U1 U2 U3 N
AUXVOLTAGE INPUT POWER
S1 S2
P1 P2
L1
N
BI-PHASE 2PH-2W
S1 S2 S1 S2 S1 S2 A B
T
10 11 12
I1 I2 I3 RS-485 AUX
17 18 19 20U1 U2 U3 N
AUXVOLTAGE INPUT POWER
S1 S2
P1 P2
L1
L2
S1 S2 S1 S2 S1 S2 A B
T
10 11 12
I1 I2 I3 RS-485 AUX
17 18 19 20U1 U2 U3 N
AUXVOLTAGE INPUT POWER
S1 S2
P1 P2
L1
L2
L3 S1 S2
P1 P2
+
19
-
20
AUX
IN/OUT
!
VOLTAGE AND CURRENT CONNECTION
S1 S2 S1 S2 S1 S2 A B
T
10 11 12
I1 I2 I3 RS-485 AUX
17 18 19 20U1 U2 U3 N
AUXVOLTAGE INPUT POWER
LN FUSE
(50mAT)
230 ÷ 240 V ±10%
Serial RS485 port
AB
T
SETUP SEQUENCE
ENTERS INTO SET UP MODE
(Push together for 2 seconds)
REQUEST PASSWORD 0000 ... 9999
RS-485
RS485 address 1 ... 247
Speed 2400, 4800, 9600, 19200, 38400
Data Bit 7 or 8
Parity N = No parity, E = Even parity, O = Odd parity
Stop Bit 1 or 2
NETWORK
Type 3PH-3W-2CT, 3PH-4W, 2PH-2W, 1PH-2W
CT (Primary) 10000
CT (Secondary) 1 o 5
VT (Primary) 400000
VT (Secondary) 300
CLEAR TOTAL COUNTERS NO, YES
CLEAR PARTIAL COUNTERS NO, YES
CLEAR MAX DEMAND NO, YES
ENTER NEW PASSWORD 0000 ... 9999
EXIT SETUP (Push for 2 seconds)
OPERATING KEYS
Click Change selected field
value
Change selected field value Go to next field
Click
2 sec
Go to next window Back to initial entry field Exits setup
The instrument is programmed with the following default values:
RS485 address
Communication
27
9600, 8, N, 2
Type
CT
VT (PT)
3PH-4W
5/5
1/1
Initial Password 0000
DIGITAL INPUTS AND OUTPUTS CONNECTION
(Applicable only to type PFA8611-12)
Digital Inputs
Supply voltage (external): from 10 to 30
Vdc
Current consumption: from 2 to 10mA
Max. count frequency 10 or 100Hz
N.B. For gas meters a galvanic separation is
needed per ATEX standards
Digital outputs (optocoupled NPN
transistor type per DIN 43864)
Maximum applicable voltage: 27 Vdc
Maximum switchable current: 27 mA
Table of contents
Other Electrex Measuring Instrument manuals

Electrex
Electrex EXA TR D6 User manual

Electrex
Electrex EXA 96 User manual

Electrex
Electrex NET D6 User manual

Electrex
Electrex ETTO D2 User manual

Electrex
Electrex FEMTO D4 70A User manual

Electrex
Electrex FEMTO D4 User manual

Electrex
Electrex FEMTO 96 User manual

Electrex
Electrex KILO User manual

Electrex
Electrex EXA 96 User manual

Electrex
Electrex KILO F RJ45 User manual