3.5. Alarm Conf"gurat"on Page ( )ACNF
(0) :OFF Off
(1) :LO Low Alarm aIf the process value s below the alarm set pont, the alarm
becomes actve. The alarm deactvates when the process value rses above the alarm
set pont by the amount of hysteress.
(4) : It s the same as the . The alarm set pont s
calculated by addng the control set pont to the alarm set pont (Set = Control Set +
Alarm Set).
HID H"gh Dev"at"on H"gh Alarma
(6) : The alarm s actve when the PV s outsde the bandHIB Out Band Alarm a
(5) : The alarm s actve when the PV s nsde the bandLOB In Band Alarm a
(2) :HI H"gh Alarm aIf the process value s above the alarm set pont, the alarm
becomes actve. The alarm deactvates when the process value drops below the
alarm set pont by the amount of hysteress.
(3) : It s the same as the . The alarm set pont s
calculated by addng the control set pont to the alarm set pont (Set = Control Set +
Alarm Set).
LOD Low Dev"at"on Low Alarma
Alarm Types (x
( )
= 1..4)
A1TP, A2TP, A3TP, A4TP Always
Screen Def"n"t"on M"n Access
Max Un"t
Alarm Set Po"nts (x
( )
= 1..4)
A1SP, A2SP, A3SP, A4SP A TP OFFx≠
SPLL SPHL EU
Alarm Hysteres"ses (x
( )
= 1..4)
A1HY, A2HY, A3HY, A4HY A TP OFFx≠
0.0 999.9 EU
Alarm Locks (x
( )
= 1..4)
A1LT, A2LT, A3LT, A4LT A TP OFFx≠
DSB ENB
(0)
(1)
: Alarm lock s not actve.
: Alarm lock s actve.
DSB
ENB
If s selected, once an alarm s trggered, t wll contnue to be actve untl
manually acknowledged usng the front panel keys, even f the alarm condton s
not exsst. To unlock alarms that are n a locked state, you should press the
button whle n the process screen. If the alarm s no longer actve, pressng ths
button wll release the alarm.
ENB
4
Four alarms are defned n the devce. Alarm Type, Set Value, Hysteress and Alarm
Lock paremeters can be set for each alarms. The alarm sngnals can be assgned to
requred relays avalable on the devce.
LOB HIBve Alarm Band
Control Set Value + Alarm SetControl Set Value - Alarm Set
A TPx
LO
A SPx
100.0
A HYx
0.5
A LTx
DSB