Gira One 5023 00 User manual

Switching actuator / blind actuator 16 A Standard
Table of Contents
1 Safety instructions.............................................................................................................3
2 Device components...........................................................................................................3
3 Function ............................................................................................................................4
4 Operation ..........................................................................................................................5
5 Information for electrically skilled persons ........................................................................9
5.1 Mounting and electrical connection........................................................................ 9
5.2 Commissioning .................................................................................................... 11
6 Technical data.................................................................................................................12
7 Parameter list ..................................................................................................................13
8 Warranty..........................................................................................................................16
2 / 17
82402632 15.12.2022

1 Safety instructions
Electrical devices may only be mounted and connected by electrically skilled
persons.
Serious injuries, fire or property damage possible. Please read and follow manual
fully.
Danger of electric shock on the SELV/PELV installation. Do not connect loads for
mains voltage and SELV/PELV together to the device.
For parallel connection of several motors to an output it is essential to observe the
corresponding instructions of the manufacturers, and to use a cut-off relay if neces-
sary. The motors may be destroyed.
Use only Venetian blind motors with mechanical or electronic limit switches. Check
the limit switches for correct mastering. Observe the specifications of the motor man-
ufacturers. Device can be damaged.
Do not connect any three-phase motors. Device can be damaged.
This manual is an integral part of the product, and must remain with the end cus-
tomer.
2 Device components
Image1: Device components
(1) Button field for manual operation
(2) Programming button and LED
(3) Bus connection
(4) Status LEDs for outputs
(5) Load connections (relay outputs)
3 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard

3 Function
System information
This device is a product for the Gira One Smart Home system. The Gira One system
is commissioned easily and in a time-saving manner using the Gira Project Assistant.
The Gira One Smart Home system enables the control and automation of lighting,
heating and shading, as well as connection to various third-party systems and much
more. It can be operated via Gira One switches, by app from home or securely from a
remote location. Electrically skilled persons can maintain the Gira One project re-
motely free of charge.
Data transmission between the Gira One devices is encrypted. This provides protec-
tion against third-party access and manipulation.
Commissioning is carried out with the free Gira Project Assistant (GPA), version 5 or
higher. Free function and security updates are also transferred to the Gira One
devices with the GPA.
The Gira One system is based on the globally proven KNX smart home standard.
Intended use
– Switching of electrical loads with potential-free contacts
– Switching of electrically-driven Venetian blinds, roller shutters, awnings and
similar hangings
– Installation in sub-distribution unit on DIN rail according to DIN EN 60715
– Operation in Gira One system
Product characteristics
– Outputs can be operated manually, construction site mode
– Manual switching between Venetian blind operation and switching operation
without commissioning
– Programming and commissioning with the Gira Project Assistant (GPA), ver-
sion 5 or higher.
– Updating via the Gira Project Assistant (GPA).
– Encrypted data transmission between the Gira One devices.
Characteristics switch operation
– Operation as NO or NC contacts
– Setting of a switch-on or switch-off delay.
– Staircase function for which a pre-warning time can additionally be set.
– Configuration as a switching function, e.g. for a light or sockets, as a garage
door function or door opener function, and as a potential-free switching contact
for transmission of the heat requirement to a heat pump.
– Garage door function: The time for closing the relay can be configured.
4 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard

– Door opener function: The time for closing the relay can be configured.
Characteristics Venetian blinds operation
– Suitable for AC motors 110...230 V
– Control of blinds with slats, shutters, awnings, roof windows or roof domes.
– Travelling times can optionally be set.
– Sun protection function with blind or slat positions at the beginning and at the
end of the function can be set separately for each output.
– Setting of the delay time at the beginning or end of sunshine.
– Fabric stretching for awnings.
– If a wind alarm is active (e.g. as the result of an analogue wind sensor), the
Venetian blinds are raised and automatically locked. The status of the binary
input connected to the wind sensor is monitored cyclically.
– If a rain alarm is active (e.g. as the result of an analogue rain sensor), roof
windows or roof domes are closed and automatically locked. The status of the
binary input connected to the rain sensor is monitored cyclically.
– If a frost alarm is active (e.g. as the result of an analogue frost sensor), active
movements of shutters are stopped and disabled to protect the shutter motor.
The status of the binary input connected to the rain sensor is monitored cyclic-
ally.
– Door contact polling and visualisation in the Smart Home app: An open door
leads to the Venetian blind or shutters being raised and locked.
4 Operation
Image2: Operating elements
(4) Status LEDs for outputs
ON: Relay output closed
OFF: Relay output opened
Flashes slowly: Output in manual mode selected
Flashes quickly: Output disabled via continuous manual mode
(6) Button ǃ
Manual operation
5 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard

(7) LED ǃ
ON: Continuous manual mode active/Flashing: Temporary manual mode
active
(8) LED DŽ
ON: Relay outputs closed, manual mode active
(9) Button DŽ
Short: Switch on, adjust slats or stop
Long: Move hanging upwards
(10) Button Dž
Short: Switch off, adjust slats or stop
Long: Move hanging downwards
(11) LED Dž
ON: Relay outputs opened, manual mode active
(12) Button ALL OFF
Open all relay outputs, stop drives
In operation with the button field the device distinguishes between a short and a long
press.
– Short: Pressing for less than 1 s
– Long: Pressing for between 1 and 5 s
In switching operation, the device distinguishes between the "NO contact" and
"NC contact" operating modes. The buttons (9 + 10) switch the switching state
when actuated:
NO contact: Switch on = close relay, Switch off = open relay
NC contact: Switch on = open relay, Switch off = close relay
The LED (4 + 8 + 11) always indicate the relay state.
Operating modes
– Bus operation: operation via push-button sensors or other bus devices
– Temporary manual control: manual control locally with keypad, automatic re-
turn to bus control
– Continuous manual mode: exclusively manual operation on the device
No bus operation is possible in manual mode.
After a bus failure and restoration the device switches to bus operation.
Switching on temporary manual operation mode
Operation is not disabled.
■ Press button ǃ (6) briefly.
LED ǃ (7) flashes, LEDs A1... (4) of the first configured output or output pair
flash.
Short-time manual operation is switched on.
6 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard

After 5 s without a button actuation, the actuator returns automatically to bus
operation.
Switching off temporary manual operation mode
The device is in short-term manual mode.
■ No button-press for 5 s.
- or -
■ Press ǃ (6) button briefly as many time as necessary until the actuator
leaves the short-time manual mode.
Status LEDs A1... (4) no longer flash, but rather indicate the relay status.
Short-time manual operation is switched off.
Switching outputs: depending on the programming, the output relays switch to
the position that is active after the manual mode is switched off.
Venetian blind outputs: depending on the programming, the blind moves to the
position that is active after the manual mode is switched off, e.g. to safety or
sun protection position.
Switching on permanent manual operation mode
Operation is not disabled.
■ Press the ǃ (6) button for at least 5 s.
LED ǃ (7) lights up, LEDs A1... (4) of the first configured output or output
pair flash.
Continuous manual mode is switched on.
Switching off permanent manual operation mode
The device is in continuous manual mode.
■ Press the ǃ (6) button for at least 5 s.
LED ǃ (7) is off.
Continuous manual mode is switched off. Bus operation is switched on.
Switching outputs: depending on the programming, the output relays switch to
the position that is active after the manual mode is switched off.
Venetian blind outputs: depending on the programming, the blind moves to the
position that is active after the manual mode is switched off, e.g. to safety or
sun protection position.
Operating an output in manual mode
■ Activate short-term or permanent manual operation.
7 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard

■ Press button ǃ (6) repeatedly until LED A1... (4) of the desired output or
output pair flashes.
■ Press button DŽ (9) or Dž (10).
Short: Switch on/off, drive stop.
Long: Move blind/shutter upwards/downwards.
LED DŽ (8) ON: Relay output closed
LED Dž (7) OFF: Relay output opened
Short-term manual mode: After running through all of the outputs the device
exits manual mode after another brief actuation.
Switching off all outputs / Stopping all hangings
The device is in permanent manual operation mode.
■ Press the ALL OFF button (12).
Switching outputs: all outputs switch off (NO operating mode: relay output
opened/NC operating mode: relay output closed).
Venetian blind outputs: all blinds/shutters stop.
Disabling outputs
The device is in continuous manual mode.
■ Press button ǃ (6) repeatedly until LED A1... (4) of the desired output or
output pair flashes.
■ Press the DŽ (9) and Dž (10) buttons simultaneously for approx. 5 s.
Selected output is disabled.
The status LED A1... (4) of the selected output or output pair flashes quickly.
A disabled output can be operated in manual mode.
Re-enabling outputs
The device is in continuous manual mode. One or more outputs were disabled in
manual mode.
■ Press button ǃ (6) repeatedly until the output to be unlocked or the output
pair is selected.
■ Press the DŽ (9) and Dž (10) buttons simultaneously for approx. 5 s.
Disabling is deactivated.
The LED A1... (4) of the selected output or output pair flashes slowly.
Switching between Venetian blind and switching operation
Device is not in operation
■ Activate permanent manual operation.
8 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard

■ Press button ǃ (1) repeatedly until LED A1... (8) of the desired output or
output pair flashes.
■ Press the ǃ (1) and DŽ (4) and Dž (5) buttons simultaneously for
approx. 5 s.
Switching operation: Both status LEDs A1... (8) of the output pair light up.
Venetian blind operation: Both status LEDs A1... (8) of the output pair flash al-
ternately.
■ Press the DŽ (4) and Dž (5) buttons simultaneously.
Outputs switch between switching operation and Venetian blind operation.
Both status LEDs A1... (8) indicate the current operating mode.
■ Press the ǃ (1) and DŽ (4) and Dž (5) buttons simultaneously for
approx. 5 s.
Operating mode switchover is terminated, permanent manual operation mode
is activated.
■ Press the ǃ button (1) for approx. 5 s.
Operating mode switchover is terminated, permanent manual operation mode
is deactivated.
5 Information for electrically skilled persons
DANGER!
Mortal danger of electric shock.
Disconnect the device. Cover up live parts.
5.1 Mounting and electrical connection
Mounting the device
– Enter or scan the device certificate and add it to the project. A high resolution
camera should be used to scan the QR code.
– The device certificate should be removed from the device during mounting.
– Document all passwords and keep them safe.
Observe ambient temperature. Ensure adequate cooling.
■ Mount device on DIN rail.
9 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard

Connecting the device
Image3: Device connection (connection example)
■ Connect bus line with device connection terminal observing the correct polar-
ity.
■ Attach the cover cap to the bus connection as protection against hazardous
voltages.
■ Connect load as shown in the connection example. Two adjacent relay outputs
form a Venetian blind output.
The total current capacity of neighbouring outputs is a maximum of 20 A.
Image4: Total current capacity of neighbouring outputs
10 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard

5.2 Commissioning
Commissioning the device
NOTICE!
Incorrect load control due to undefined relay state at delivery.
Risk of destruction of connected drive motors.
During commissioning, before switching on the load, ensure that all relay contacts
are open by applying the bus voltage. Observe commissioning sequence!
■ Switch on the bus voltage.
■ Wait about 10 s.
■ Switch on load circuits.
Delivery state: The outputs can be operated with manual control. Outputs are
set as Venetian blind outputs.
The device is commissioned with the Gira Project Assistant (GPA) version 5 or
higher.
Safe-state mode
The safe-state mode stops the execution of the program.
Only the system software of the device is still functional. Diagnosis functions and pro-
gramming of the device are possible. Manual operation is not possible.
Activating safe-state mode
■ Switch off the bus voltage or remove the device connection terminal.
■ Wait about 15 s.
■ Press and hold down the programming button.
■ Switch on the bus voltage or attach the device connection terminal. Release
the programming button only after the programming LED starts flashing slowly.
The safe-state mode is activated.
Deactivating safe-state mode
■ Switch off the bus voltage (wait approx. 15 s) or carry out programming.
Master reset
The master reset restores the basic device settings (firmware remains in place). The
device must then be recommissioned with the GPA. Manual operation is possible.
Performing a master reset
Precondition: The safe-state mode is activated.
11 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard

■ Press and hold down the programming button for > 5 s.
The programming LED flashes quickly.
The device performs a master reset, restarts and is ready for operation again
after approx. 5 s.
6 Technical data
Rated voltage DC 21 ... 32 V SELV
Current consumption
Order no. 5023 00, 5028 00 5 ... 18 mA
Order no. 5030 00 5 ... 24 mA
Outputs
Switching voltage AC 250 V ~
Switching current AC1 16 A
Fluorescent lamps 16AX
Current carrying capacity
Neighbouring outputs Ʃ 20 A
Loads per output
Ohmic load 3000 W
Capacitive load max. 16 A (140 μF)
Motors 1380 VA
Switch-on current 200 μs max. 800 A
Switch-on current 20 ms max. 165 A
Lamp loads
Incandescent lamps 2300 W
HV halogen lamps 2300 W
HV-LED lamps max. 400 W
LV halogen lamps with electronic
transformers
1500 W
LV halogen lamps with inductive
transformer
1200 VA
Compact fluorescent lamps
uncompensated 1000 W
parallel compensated 1160 W (140 μF)
Installation width
Order no. 5023 00 72 mm / 4 HP
Order no. 5028 00 144 mm / 8 HP
Order no. 5030 00 216 mm / 12 HP
12 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard

Weight
Order no. 5023 00 approx. 230 g
Order no. 5028 00 approx. 500 g
Order no. 5030 00 approx. 740 g
Clampable conductor cross-section
Single stranded 0.5 ... 4 mm²
Finely stranded without conductor sleeve 0.5 ... 4 mm²
Finely stranded with conductor sleeve 0.5 ... 2.5 mm²
Ambient conditions
Ambient temperature -5 ... +45 °C
Storage/transport temperature -25 ... +70 °C
Connection torque, screw terminals max. 0.8 Nm
7 Parameter list
Parameters that can be set via the GPA:
Output - Switching functions
Function of the switching output NO contact
NC contact
NO contact
The relay works as an NO contact. The logical switching state of the switching out-
put is not forwarded to the relay in inverted form.
Switching state = OFF ("0") -> relay contact open,
Switching state = ON ("1") -> relay contact closed.
NC contact
The relay works as an NC contact. The logical switching state of the switching output
is forwarded to the relay in inverted form.
Switching state = OFF ("0") -> relay contact closed,
Switching state = ON ("1") -> relay contact open.
Switch-on delay 0 ... 3599 s (0 ... 59:59 min)
This parameter is used for setting the duration of the switch-on delay.
After receipt of an ON-telegram, the time that can be configured here is started. The
lamp is switched on after the set time has elapsed.
A further ON-telegram during the switch-on delay time re-triggers the time, i.e. the
time set here is started again.
An OFF-telegram received during the ON-delay will end the delay and sets the
switching status to "OFF".
13 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard

Switch-off delay 0 ... 3599 s (0 ... 59:59 min)
This parameter is used for setting the duration of the switch-off delay.
After receipt of an OFF-telegram, the time that can be configured here is started.
The lamp is switched off after the set time has elapsed.
A further OFF-telegram during the switch-off delay time re-triggers the time, i.e. the
time set here is started again.
An ON-telegram received during the OFF-delay will end the delay and sets the
switching status to "ON".
Staircase switch
Switch-off delay
0 ... 65535 s (0 ... 18:12:15 h)
The duration of the switch-on time for the staircase function is configured here.
Once the time set here has elapsed, the lighting is switched off or (if configured) the
pre-warning time is started.
The staircase function is only active if the function "Staircase" has been selected for
the push-button of this dimming channel.
Pre-warning time 0 ... 3599 s (0 ... 59:59 min)
In accordance with DIN 18015-2, the pre-warning is intended to warn persons still on
the staircase that the light will soon be switched off automatically.
The pre-warning time set here is added to the time set in the parameter "Staircase
switch switch-off delay".
Switching time 0 ... 65535 s (0 ... 18.20 h)
The switching time in seconds can be specified here.
Output - Blind functions
No travelling time
If this option is activated, no explicit travelling times can be set for the blind/shutter.
Preset travelling times are used instead.
This has the result that it is not possible to move this blind/shutter to defined posi-
tions (e.g. 60%).
Downwards travelling time 0 ... 1199 s (0 ... 19:59 min)
This parameter defines the travelling time for closing the blind/shutter. The time
needed for a complete travel from the upper into the lower end position must be de-
termined.
Upwards travelling time 0 ... 1199 s (0 ... 19:59 min)
This parameter defines the travelling time for opening the blind/shutter. The time
needed for a complete travel from the lower into the upper end position must be de-
termined.
14 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard

Slats travelling time
(for Venetian blinds only)
0 ... 1199 s (0 ... 19:59 min)
This parameter defines the travel time of the slats. The time needed for a complete
movement from the completely open slat position into the completely closed slat po-
sition (travel movement DOWN) must be determined.
This parameter is only visible in the Venetian blind operating mode.
Time for fabric stretching
(for awnings only)
0…59 s
The time for fabric stretching can be specified here. After the end of a downward
movement, the awning stops and – after the switchover time has elapsed – moves in
the opposite direction for a period corresponding to the fabric stretching time con-
figured here.
This parameter is only visible in the awning operating mode.
Delay at the beginning of sunshine 0 ... 3599 s (0 ... 59:59 min)
The telegram received via the object "Sunshine" for activation of the sun protection
can be evaluated with a time delay.
Venetian blind position at the beginning of
sunshine
0 ...100 %
The blind/shutter position to which the blind/shutter is to be moved if sun protection
has been activated can be defined here.
Slat position at the beginning of sunshine
(for Venetian blinds only)
0 ...100 %
The slat position to which the slats are to be set if sun protection has been activated
can be defined here.
This parameter is only visible in the Venetian blind operating mode.
Delay at the end of sunshine 0 ... 3599 s (0 ... 59:59 min)
The telegram received via the object "Sunshine" for deactivation of the sun protec-
tion can be evaluated with a time delay.
15 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard

At the end of sunshine no reaction
raising
lowering
stop
Last position before sunshine
This parameter defines the behaviour of the output at the end of shading – if applic-
able, after the end of the delay time.
no reaction
At the end of shading, the output quits the sun protection mode and the relays of the
output show no reaction. Any travel movements still in progress at this instant will
still be finished.
raising
At the end of shading, the actuator raises the blind/shutter or opens the venting
louvre/roof window.
lowering
At the end of shading, the actuator lowers the blind/shutter or closes the venting
louvre/roof window.
stop
At the end of shading, the actuator switches the relays of the output to the "stop" po-
sition. A travel movement, if any, will be interrupted.
Last position before sunshine
At the end of shading, the blind/shutter moves back to the position that was active at
the beginning of sunshine.
8 Warranty
The warranty is provided in accordance with statutory requirements via the specialist
trade. Please submit or send faulty devices postage paid together with an error de-
scription to your responsible salesperson (specialist trade/installation company/elec-
trical specialist trade). They will forward the devices to the Gira Service Center.
Gira
Giersiepen GmbH & Co. KG
Elektro-Installations-
Systeme
Industriegebiet Mermbach
Dahlienstraße
42477 Radevormwald
Postfach 12 20
42461 Radevormwald
Deutschland
Tel +49(0)21 95 - 602-0
16 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard

Fax +49(0)21 95 - 602-191
www.gira.de
17 / 17
82402632 15.12.2022
Switching actuator / blind actuator 16 A Standard
This manual suits for next models
2
Table of contents
Other Gira Controllers manuals

Gira
Gira 0309 00 User manual

Gira
Gira 2100 Series User manual

Gira
Gira 1289 00 User manual

Gira
Gira 5423 00 User manual

Gira
Gira 0425 00 User manual

Gira
Gira One 5065 00 User manual

Gira
Gira KNX 1039 00 User manual

Gira
Gira 1288 Series User manual

Gira
Gira 0399 00 User manual

Gira
Gira Powernet Single Switching Actuator User manual

Gira
Gira One 5062 00 User manual

Gira
Gira 2164 00 User manual

Gira
Gira KNX 5061 00 User manual

Gira
Gira 1039 00 User manual

Gira
Gira KNX 5062 00 User manual

Gira
Gira 5023 00 User manual

Gira
Gira 2114 00 User manual

Gira
Gira 0388 00 User manual

Gira
Gira One 5061 00 User manual

Gira
Gira 2101 Series User manual