Room Temperature Controller Cala KNX T 101 1
Room Temperature Controller Cala KNX T 101 • Version: 05.10.2022 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250
EN
Cala KNX T 101
Room Temperature Controller
Technical specifications and installation instructions
Item numbers 70980 (white), 70982 (black)
1. Description
The Room Temperature Controller Cala KNX T 101 measures the room tem-
perature and displays the current value in white illuminated figures. Via the bus the
device can receive an external measured value and process it with own data to ove-
rall temperature value (mixed value).
The Cala KNX T 101 has got an integrated PI controller for a heating and a cooling
system (one or two step). The room temperature is adjusted by means of the „+“
and „-“ touch buttons.
The device is supplemented with a frame of the switch series used in the building,
and thus fits seamlessly into the interior fittings.
Functions:
• Measurement of temperature. Mixed value from own measured value and
external values (proportions can be set in percentage), output of minimum
and maximum values
•Display of the actual value or the target value/basic setpoint shift
•2 touch buttons (+/-) for adjustment of the room temperature
•PI controller for heating (one or two step) and cooling (one or two step)
depending on temperature. Control according to separate target values or
basic target temperature
Configuration is made using the KNX software as of ETS 5. The product file can be
downloaded from the ETS online catalogue and the Elsner Elektronik website on
www.elsner-elektronik.de in the “Service” menu.
1.0.1. Scope of delivery
• Room temperature controller in casing
• Base plate
Additionally required (not included in the deliverables):
• Windproof device socket according to DIN EN IEC 60670-1 and DIN 49073
• Frame (for insert 55 x 55 mm), compatible to the switch scheme used in the
building
1.1. Technical data
The product is compliant with the provisions of EU Directives.
1.1.1. Accuracy of the measurement
Measurement variations from permanent sources of interference (see chapter Ins-
tallation position) can be corrected in the ETS in order to ensure the specified accu-
racy of the sensor (offset).
When measuring temperature, the self-heating of the device is compensated.
2. Installation and commissioning
Installation, testing, operational start-up and troubleshooting should
only be performed by an authorised electrician.
CAUTION!
Live voltage!
There are unprotected live components inside the device.
• Inspect the device for damage before installation. Only put undamaged
devices into operation.
• Comply with the locally applicable directives, regulations and provisions for
electrical installation.
• Immediately take the device or system out of service and secure it against
unintentional switch-on if risk-free operation is no longer guaranteed.
Use the device exclusively for building automation and observe the operating inst-
ructions. Improper use, modifications to the device or failure to observe the opera-
ting instructions will invalidate any warranty or guarantee claims.
Operate the device only as a fixed-site installation, i.e. only in assembled condition
and after conclusion of all installation and operational start-up tasks, and only in the
surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may
occur after publication of these operating instructions.
2.1. Installation position
The Room Temperature Controller Cala KNX T 101 is installed on a device so-
cket.
May be installed and operated in dry interior rooms only.
When selecting an installation location, ensure that the measurement results are af-
fected as little as possible by external influences. Possible sources of interference
include:
• Direct sunlight
• Drafts from windows and doors
• Draft from ducts which lead from other rooms or from the outside to the
junction box in which the sensor is mounted
• Warming or cooling of the building structure on which the sensor is mounted,
e.g. due to sunlight, heating or cold water pipes
• Connection lines and ducts which lead from warmer or colder areas to the
sensor
Measurement variations from permanent sources of interference can be corrected
in the ETS in order to ensure the specified accuracy of the sensor (offset).
2.2. Device structure
2.2.1. Casing
2.3. Installation of the sensor
First install the windproof socket with feed line. Seal the inlet tubes as well, in order
to prevent draughts.
Casing Genuine glass, plastic
Colours • similar to RAL 9010 pure white
• similar to RAL 9005 deep black
Installation on device socket according to
DIN EN IEC 60670-1 and DIN 49073
Degree of protection IP 20
Dimensions Housing approx. 55 x 55 (W x H, mm),
Installation depth approx. 10 mm,
Base plate approx. 71 x 71 (W x H, mm)
Total weight approx. 50 g
Ambient temperature Operating -5…+45°C, storage -30…+85°C
Ambient humidity 5...95% RH, avoid condensation
Operating voltage KNX bus voltage
Bus current max. 15 mA
Data output KNX +/- Bus plug-in terminal
Group addresses max. 183
Allocations max. 183
Communication
objects
41
Temperature measu-
rement range
-5…+60°C
Fig. 1: Sectional drawing.
The Room Temperature Controller
Cala KNX T 101 fits in a standard con-
nector socket (Ø 60 mm, depth 42 mm).
The frame is not included in the delive-
ry!
Installation depth
27 mm
Construction depth
10 mm
Fig. 2: Front
1 Ventilation slit (top and bottom)
2 Temperatur display
3 Touch area -
4 Touch area +
2
1
4
1
3
Fig. 3: Back
1 Base frame
2 KNX terminal BUS +/-
3 Programming button (reces-
sed) for teaching the device
4 Programming LED (recessed)
5 Catches
5
1
3
2
4
Room Temperature Controller Cala KNX T 101 2
Room Temperature Controller Cala KNX T 101 • Version: 05.10.2022 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250
Then screw the base plate to the socket and place the switch program frame. Con-
nect the bus cable +/- to the plug (black-red).
Insert the device firmly onto the metal frame using the catches so that the device
and the housing are fixed together.
3. Commissioning
Never expose the device to water (e.g. rain) or dust. This can damage the electro-
nics. You must not exceed a relative humidity of 95%. Avoid condensation.
After the bus voltage has been applied, the device will enter an initialisation phase
lasting a few seconds. During this phase no information can be received or sent via
the bus.
4. Addressing of the device at the bus
The device is supplied with the bus address 15.15.255. You can program another ad-
dress into the ETS by overwriting the 15.15.255 address or by teaching via the pro-
gramming button.
5. Display and operation at the device
5.1. Adjust room temperature
Depending on the setting of the "Display mode" parameter in the device application,
the Room Temperature Controller Cala KNX T 101 displays the current room
temperature value (or mixed value), the target value or the shift in relation to the
basic setpoint. The display can be dimmed and switched off via the bus so that no
value is displayed.
Option A: Display of actual temperature (room temperature)
The current room temperature is displayed. It is not possible to change the room
temperature manually using the +/- buttons.
Option B: Display of target temperature or basic setpoint shift
Depending on the setting, the current target value or the shift relative to the base
setpoint is displayed. The temperature can be changed by touching the +/- buttons.
Target value display (absolute value):
Display of the basic setpoint shift (change compared to the basic setpoint of the
control):
Option C: Display of actual temperature and target temperature/basic set-
point shift
During normal operation, the current room temperature is displayed. By touching
the buttons, the display jumps to the target temperature or to the basic setpoint
shift, depending on the presetting. Changes with + or - are visible. The display re-
turns to the room temperature if no button is touched for 7 seconds.
Touch the + or - button briefly: The current target temperature (or the basic set-
point shift) is displayed.
Tap +: Increase room temperature
(target temperature/basic setpoint shift is increased).
Tap -: Lower room temperature
(target temperature/basic setpoint shift is lowered).
General:
The step size for the change and the possible setting range are defined in the device
application (ETS). There you can also define whether the manually changed values
are retained after a mode change (e.g. Eco mode overnight) or reset to the stored
values.
The button functions can be locked due to operating mode with priority 1.
6. Maintenance
Ventilation slits must not be dirty of covered. As a rule, it is sufficient to wipe the
device with a soft, dry cloth as required.
7. Disposal
After use, the device must be disposed of in accordance with the legal regulations.
Do not dispose of it with the household waste!
Tap +:
Increase room temperatu-
re
(target temperature is in-
creased)
Tap -:
Lower room temperature
(target temperature is lo-
wered)
Tap +:
Increase room temperatu-
re
(Basic setpoint shift direc-
tion PLUS)
Tap -:
Lower room temperature
(Basic setpoint shift direc-
tion MINUS)
or

This manual suits for next models

2

Other elsner elektronik Temperature Controllers manuals

elsner elektronik Arexa 230V Window Control Guide

elsner elektronik

elsner elektronik Arexa 230V Window Control Guide

elsner elektronik 20552 User manual

elsner elektronik

elsner elektronik 20552 User manual

elsner elektronik KNX eTR 101 User manual

elsner elektronik

elsner elektronik KNX eTR 101 User manual

elsner elektronik KNX eTR 101-BA2 Guide

elsner elektronik

elsner elektronik KNX eTR 101-BA2 Guide

elsner elektronik KNX TH65-AP User manual

elsner elektronik

elsner elektronik KNX TH65-AP User manual

elsner elektronik KNX T-AP Guide

elsner elektronik

elsner elektronik KNX T-AP Guide

elsner elektronik Cala KNX T 101 User manual

elsner elektronik

elsner elektronik Cala KNX T 101 User manual

elsner elektronik KNX eTR 201 Sunblind User manual

elsner elektronik

elsner elektronik KNX eTR 201 Sunblind User manual

elsner elektronik KNX T-UN 130 Guide

elsner elektronik

elsner elektronik KNX T-UN 130 Guide

elsner elektronik KNX T-AP Guide

elsner elektronik

elsner elektronik KNX T-AP Guide

Popular Temperature Controllers manuals by other brands

Eurotherm controls 808 Handbook

Eurotherm controls

Eurotherm controls 808 Handbook

SMC Networks HRSH090 Series Technical data

SMC Networks

SMC Networks HRSH090 Series Technical data

TFA WIRELESS 868 MHz TEMPERATURE STATION instruction manual

TFA

TFA WIRELESS 868 MHz TEMPERATURE STATION instruction manual

TECSYSTEM T154 Series instruction manual

TECSYSTEM

TECSYSTEM T154 Series instruction manual

Kobold TTL Series operating instructions

Kobold

Kobold TTL Series operating instructions

BUSCH 6224/2.0-WL product manual

BUSCH

BUSCH 6224/2.0-WL product manual

Honeywell FIRE-LITE ALARMS W-H355 Installation and maintenance instructions

Honeywell

Honeywell FIRE-LITE ALARMS W-H355 Installation and maintenance instructions

Emerson E2 Quick reference guide

Emerson

Emerson E2 Quick reference guide

S+S Regeltechnik THERMASREG Frija I Series Operating Instructions, Mounting & Installation

S+S Regeltechnik

S+S Regeltechnik THERMASREG Frija I Series Operating Instructions, Mounting & Installation

Leister CSS operating instructions

Leister

Leister CSS operating instructions

Micatrone MDT-2000 OPERATING AND INSTALLATION Manual

Micatrone

Micatrone MDT-2000 OPERATING AND INSTALLATION Manual

Middleby Marshall 75729 instructions

Middleby Marshall

Middleby Marshall 75729 instructions

WIKA TC47 Series operating instructions

WIKA

WIKA TC47 Series operating instructions

Mitsubishi Electric PAC-TH011HT-E installation manual

Mitsubishi Electric

Mitsubishi Electric PAC-TH011HT-E installation manual

THERMOSALD UPSCR Series Maintenance & Operation Manual

THERMOSALD

THERMOSALD UPSCR Series Maintenance & Operation Manual

Danfoss ECL Comfort 210 installation guide

Danfoss

Danfoss ECL Comfort 210 installation guide

Chili Technology ChiliPad Setup guide

Chili Technology

Chili Technology ChiliPad Setup guide

Aube Technologies Temperature Sensor AC146-410 installation guide

Aube Technologies

Aube Technologies Temperature Sensor AC146-410 installation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.