manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Emerson
  6. •
  7. Control Unit
  8. •
  9. Emerson FISHER F180 Series User manual

Emerson FISHER F180 Series User manual

This manual suits for next models

3

Other Emerson Control Unit manuals

Emerson Fisher 8580 User manual

Emerson

Emerson Fisher 8580 User manual

Emerson E5 User manual

Emerson

Emerson E5 User manual

Emerson CASH VALVE C776 User manual

Emerson

Emerson CASH VALVE C776 User manual

Emerson Fisher ACE95 Series User manual

Emerson

Emerson Fisher ACE95 Series User manual

Emerson Fisher NPS 8 CHP User manual

Emerson

Emerson Fisher NPS 8 CHP User manual

Emerson Fisher GX User manual

Emerson

Emerson Fisher GX User manual

Emerson EIM 2000 Series User manual

Emerson

Emerson EIM 2000 Series User manual

Emerson Anderson Greenwood 500 Series User manual

Emerson

Emerson Anderson Greenwood 500 Series User manual

Emerson Sempell S Series User manual

Emerson

Emerson Sempell S Series User manual

Emerson YARWAY 9100 ARC Series Manual

Emerson

Emerson YARWAY 9100 ARC Series Manual

Emerson ANDERSON GREENWOOD MARVAC 121 Series User manual

Emerson

Emerson ANDERSON GREENWOOD MARVAC 121 Series User manual

Emerson PACSystems VersaMax IC200CMM020 User manual

Emerson

Emerson PACSystems VersaMax IC200CMM020 User manual

Emerson Neotecha Installation and operating instructions

Emerson

Emerson Neotecha Installation and operating instructions

Emerson KTM E0105 Series Manual

Emerson

Emerson KTM E0105 Series Manual

Emerson Keystone PED Quick guide

Emerson

Emerson Keystone PED Quick guide

Emerson Fisher Baumann Little Scotty 24000C User manual

Emerson

Emerson Fisher Baumann Little Scotty 24000C User manual

Emerson Keystone User manual

Emerson

Emerson Keystone User manual

Emerson KTM RICHARDS FIGURE R384 User manual

Emerson

Emerson KTM RICHARDS FIGURE R384 User manual

Emerson COM Express Carrier Guide

Emerson

Emerson COM Express Carrier Guide

Emerson ANDERSON GREENWOOD 96A Series Manual

Emerson

Emerson ANDERSON GREENWOOD 96A Series Manual

Emerson Clarkson series User manual

Emerson

Emerson Clarkson series User manual

Emerson SAPAG 7700 Guide

Emerson

Emerson SAPAG 7700 Guide

Emerson Fisher NPS 2 CCV-N User manual

Emerson

Emerson Fisher NPS 2 CCV-N User manual

Emerson ALCO Thermo TX6 User manual

Emerson

Emerson ALCO Thermo TX6 User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

F180 Series
D450016T012
Instruction Manual
MCK-1094
February 2008
R
www.emersonprocess.com/regulators/lp
F180 Series Excess Flow Valves for
Compressed Air Service
!
WARNING
Failure to follow these instructions or to
properly install and maintain this
equipment could result in property
damage and personal injury or death.
Fisher®equipment must be installed,
operated, and maintained in accordance
with federal, state, and local codes and
Fisher instructions.
Only personnel trained in the proper
procedures, codes, standards, and
regulations of the applicable industries
should install and service this equipment.
!
WARNING
A break or leak downstream of an
excess ow valve that does not allow a
ow equal to the valve ow rating will
not actuate the excess ow valve and
could result in property damage or
personal injury from a whipping hose or
high volume discharge of air. For this
reason the operator must be familiar
with the system shutoff valves and close
the system if an emergency occurs.
Introduction
Scope of Manual
This instruction manual covers installation and
maintenance for F180 Series excess ow valves used
on compressed air service.
Figure 1. F180 Series Excess Flow Valves
TYPE F186
TYPE F187
TYPE F188
F180 Series
2
Specications
Description
Excess ow check valves close when the ow rate
of air exceeds the valve’s rated ow capacity. They
are used to protect against the dangers of a whipping
hose. The valves are available in a variety of sizes
and body congurations.
When ow exceeds the valve’s setting, the valve
closes and remains closed until the system equalizes.
A built-in equalizing passage automatically opens the
valve once pressures on both sides of the poppet
are equal.
Specications
CAUTION
If the valve is to be used in service other
than compressed air, contact the factory
to determine if the valve materials are
suitable for the particular service.
Valves with brass materials must
not be used on anhydrous ammonia
(NH3) service.
Installation
CAUTION
Do not install the valve in any hose or
piping which tends to restrict the valve
inlet. This may prevent the excess ow
valve from closing.
Flow through the excess ow valve must
be in the same direction as the ow
arrow stamped on the valve.
1. A rule of thumb for sizing excess ow valves is
to choose a valve with a closing ow 1.5 times the
maximum operating ow. For surge conditions,
2 times maximum ow may be required.
However, the excess ow valve’s closing ow rate
must be less than the capacity of the compressed
air system in which the valve is being used. The ow
rating of the piping, ttings, pump, valves, and hose
on both the inlet and outlet of the excess ow valve
must be greater than the ow rating of the excess ow
valve. If branching, piping length, additional valves,
reduction in pipe size, elbows, or other necessary
TYPE
INLET
CONNECTION,
INCHES
OUTLET
CONNECTION,
INCHES
MATERIAL
CLOSING
FLOW,
AIR SCFM
(meters3/min) AT
100 PSIG
(6,9 bar) INLET
PRESSURE
CLOSING FLOW
DIFFERENTIAL
PRESSURE,
PSIG (bar)
BODY LENGTH,
INCHES (cm)
WRENCH HEX,
INCHES (cm)
F186-06-1 3/4 MNPT 3/4 FNPT Brass 171 (4,8) 11 (0,76) 1.85 (4,7) 1.31 (3,3)
F187-08-1 1 FNPT 1 FNPT Brass 189 (5,4) 3.3 (0,23) 3.47 (8,8) 1.75 (4,4)
F187-12-1 1-1/2 FNPT 1-1/2 FNPT Brass 416 (11,8) 4.7 (0,32) 4(10,2) 2.25 (5,7)
F187-16-1 2 FNPT 2 FNPT Brass 879 (24,9) 4.2 (0,29) 4.56 (11,6) 3(7,6)
F188-24-1 3 FNPT 3 MNPT x
2 FNPT Steel 1729 (49,0) 7.1 (0,49) 6.22 (15,8) 3.75 (9,5)
Maximum Operating Pressure: 250 psig (17,2 bar)
Maximum Differential Pressure: 15 psig (1,03 bar)
Closing Flow Tolerance: +10% to -20% of rated ow
F180 Series
3
components in the piping system create restrictions
which reduce the ow rating to less than that of the
excess ow valve rating, the valve will not give excess
ow protection, and additional excess ow valves must
be installed at these points.
2. Brass valves are not suitable for anhydrous
ammonia (NH3) applications.
3. Manually operate the excess ow valve’s poppet
before installation to assure parts were not
damaged in shipment or blocked with dirt or
foreign material.
4. Use pipe dope on the male threads of the valve or
the pipeline. Polytetrauoroethylene (PTFE) tape
or PTFE pipe dope compound is recommended for
the male threads of the larger valves such as the
2 and 3-inch sizes.
5. After the excess ow valve is installed, the system
should be tested for excess ow valve operation
by simulating a break downstream in the system
at the furthermost point being protected. To test
the unit, pressure the system and then open a
shutoff valve quickly at the farthest point in the
piping that the excess ow valve is intended to
protect. There should be a sudden decrease in
ow, indicating that the valve has closed and is
working properly. Because of the bleed that
permits the valve to equalize itself, a small amount
of leakage will continue after the excess ow
check closes.
6. To reopen a closed excess ow valve, close a
shutoff valve on either the upstream or
downstream piping. When pressure is equal on
both sides of the valve, it will “click” open and ow
can be resumed by opening the shutoff valve.
!
WARNING
Trained personnel should test the
excess ow valve in a safe location.
Excess ow closure should be checked
annually or on a regularly scheduled
basis to insure that the valve is
still functional.
Maintenance
Excess ow valves are non-repairable. Replace
non-functioning valves.
Troubleshooting
If the excess ow valve fails to close – check
the following:
1. Flow direction is the same direction as
arrow stamped on the valve.
2. Shut off valves on the inlet and outlet of the
piping are fully open.
3. Restrictions on the inlet or outlet of the excess
ow valve are restricting ow into or out of
the valve.
4. Flow capacity at point of test is not great enough
to close the excess ow valve.
5. Pipe scale, welding slag, or other debris is holding
the valve open.
Premature closing or valve chattering – check
the following:
1. Surge conditions – Increase ow slowly to
prevent surge. A larger excess closing ow may
be required.
2. Chattering – Normal ow conditions may be too
near to the closing ow rate, or ow direction is
wrong or back owing is occuring.
3. Restriction on inlet of valve.
!
WARNING
Back owing or owing too near to the
excess ow valve closing rate may cause
chattering which may result in excessive
wear on parts and valve failure.
F180 Series
Fisher and Fisher Regulators are marks owned by Fisher Controls International, LLC. The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the
property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, expressed
or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specications of such products at any time
without notice.
Fisher does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Fisher product remains solely with
the purchaser.
Emerson Process Management
Fisher Controls International, LLC.
P.O. Box 8004
McKinney, Texas 75070, USA
Telephone: 1 (800) 558-5853
Telephone: 1 (972) 548-3574
©Fisher Controls International, LLC., 2002, 2008; All Rights Reserved www.emersonprocess.com/regulators/lp