ENAPART EasyLine RM-208 CB.13.01 User manual


Operating and Installation Instructions
Filter control system
RM-208 CB.13.01
EasyLine
Supply voltage 110 V AC

RM-208 CB.13.01 Easy Line Documentation
RDN 10000795 220.03.2019
Table of Contents
1 Safety instructions .....................................................................................................................................3
2 Equipment specification.............................................................................................................................3
3 Assembly ...................................................................................................................................................4
4 “Step by step” installation...........................................................................................................................5
5 “Step by step” settings ...............................................................................................................................7
5.1 Function when shipped ...................................................................................................................7
5.2 Setting parameters..........................................................................................................................7
5.3 Parameter list..................................................................................................................................9
6 Operating modes .....................................................................................................................................10
6.1 Test mode .....................................................................................................................................10
6.2 Down time cleaning.......................................................................................................................10
6.3 Cleaning via start / stop input (external ∆p switch) .......................................................................10
7 Troubleshooting .......................................................................................................................................11
7.1 Instructions for the replacement of the device fuse ......................................................................11
7.2 Cleaning the controller ..................................................................................................................12
7.3 Manufacturing ...............................................................................................................................12
8 Text messages on the display .................................................................................................................13
9 Details on the equipment function ...........................................................................................................14
10 Glossary.................................................................................................................................................15
11 Technical specifications.........................................................................................................................16
Regulations
2014/30/EU
2014/35/EU
Legends
Warning against physical and health hazards or damages to the product and other properties.
Attention, make absolutely sure to observe the notes in the documentation!
Important note
Identification of safety class II (protective insulation).
Complete double insulation or reinforced insulation.
The symbol is affixed to the device.
Identification of direct current (DC).

RM-208 CB.13.01 Easy Line Documentation
RDN 10000795 320.03.2019
1 Safety instructions
The filter control system RM-208 CB when connected to the mains poses an electrical hazard.
Device failure, serious or even fatal injuries may occur as a result of improper installation of the
connected equipment. Consequently, follow in particular the points set out below in addition to
the general safety regulations for equipment in industrial electrical installations
:
Installation of the device may be carried out only by qualified experts, in accor
dance with the
provisions of IEC 364, DIN VDE 0105 for electrical equipment.
All applicable laws, conditions, orders and regulations governing the setting up of electrical
equipment must be observed with respect to the installation site.
Setting of equipme
nt with degree of protection IP00 without covers, may only be performed by
authorized expert staff, when disconnected, and whilst observing the local safety and accident
prevention regulations.
The RM-208 CB may only be operated in the permitted operating area.
Switch off the mains supply before replacing the filter control or any components connected to
it. Otherwise the equipment may be damaged.
2 Equipment specification
The RM-208 CB is used to control 24 V DC solenoid valves on filtering separators with compressed air
pulse cleaning. After connecting the supply voltage, the filter control system functions fully automatically
without further activation.

RM-208 CB.13.01 Easy Line Documentation
RDN 10000795 420.03.2019
3 Assembly
Wall-mounting of the filter controls is not permitted! The device may only be mounted to
machine parts.

RM-208 CB.13.01 Easy Line Documentation
RDN 10000795 520.03.2019
4 “Step by step” installation
Supply voltage connection
Solenoid valve connection
Connection of expansion modules RM-LV8 / RM-LV16

RM-208 CB.13.01 Easy Line Documentation
RDN 10000795 620.03.2019
Other connections
A device (switch, power circuit breaker) must be located in the proximity of the filter controller
RM-208 CB
, which enables the disconnection of all poles of the device from the mains
voltage / supply voltage. The device (switch, power circuit breaker) has to be easy accessible
for the user and to be marked as disconnecting device for the equipment.
The wires and cables used for the connection of the controls must be suitable for an ambient
temperature of up to 130 °C.
Use shielded cable for all bus lines! The shiel
ding must be connected unilaterally to the
protective earthing (PE).
Signal cables must not be laid parallel to power cables.
Tighten all cable glands in use so the cables are properly enclosed and water cannot
penetrate.
Cable glands that are not in use must be closed or replaced by blind plugs.

RM-208 CB.13.01 Easy Line Documentation
RDN 10000795 720.03.2019
5 “Step by step” settings
5.1 Function when shipped
The down time cleaning input 10, 11 is bridged at the factory. Once the supply voltage is at RM-208 CB,
the solenoid valves are controlled consecutively in sequence. The filter control system automatically
detects how many valves are connected.
For connecting an external ∆p switch, see section 6.3 “Cleaning via start / stop input (external ∆p switch)”.
To activate the down time cleaning, see section 6.2 “Down time cleaning”.
If another function is required or if additional functions are to be activated, the parameter setting of the
RM-208 CB must be changed. See also section 5.2.
5.2 Setting parameters
To set or check the parameters, proceed as follows:
Use the parameter list in section 5.3 to search for the parameters you want to change or check.
On the RM-208 CB, press buttons and
simultaneously, for at least 3 seconds. The
program then changes from operation mode to parameter selection mode. The parameter P01
“Pulse time” is displayed on the text display at its set value.
Press the button to call up all following parameters P02 ... P11 in sequence. The parameters
already displayed can be accessed by repeatedly pressing the button.
To change the value of a displayed parameter, press the ENTER button for at least one
second. The program then changes from parameter selection mode to parameter setting mode.
Press the
button to increase the parameter value displayed in increments. Press the
button to decrease the parameter value displayed.
Press the ENTER button for at least 3 seconds. The new parameter value is stored. The text
display will briefly display the message “Store
”. The program automatically returns to the
parameter selection mode. You can now call up other parameters and check or change their
values.
So that the program changes from parameter selection mode to operation mode, press buttons
and simultaneously for at least 3 seconds.
If the program is still in parameter setting mode, follow the instructions given under point .
The symbols shown on the right will be shown in the
lower left-
hand corner of the text display. They
indicate to the operator which mode the equipment is
currently in.
+ -Operation mode
+^-Parameter selection mode
+>-Parameter setting mode
If no buttons are pressed for 4 minutes, the RM-208 CB automatically returns from parameter
selection mode or parameter setting mode to operation mode with the last values stored.

RM-208 CB.13.01 Easy Line Documentation
RDN 10000795 820.03.2019

RM-208 CB.13.01 Easy Line Documentation
RDN 10000795 920.03.2019
5.3 Parameter list
Param. no.
Text on the display
Explanation
Factory settings
Setting range
P01
P01 Pulse time
Pulse time
60 ms
15 ... 2500 ms
P02
P02 Interval
Pause time
10 s
1 ... 500 s
P03
P03 DT interval
Down time interval time
6 s
1 ...100 s
P04
P04 tot Valve no
Total no. of valves*
0
0 ... 128
P05
P05 DT cycles
Down time cleaning cycles
6
0, 2 ... 32
P06
P06 Operating h
Operating hours
–
0 ... 250000 h
P07
P07 Language
Language for the display text
D
D, GB, F, I, NL,
DK, FIN, PL, E
P08
P08 Test Mode
0 = Test mode off
1 = Valve test
2 = Input test
3-5 = For manufacturer
purposes only
Off (0)
0 ... 5
P09
P09 Ser.run hour
Service operating hours
–
–
P10
P10 Ser.run h.AL
Service operating hours alarm
0 h**
0 ... 25000 h**
P11
P11 Ser.r.h.Code
Service operating hours code
0
0 ... 250
*Number of all valves connected to the RM-208 CB and to the expansion modules. The parameter is used by the equipment for
internal monitoring purposes and need only be set, if expansion modules are fitted. If the equipment detects that the total
number of valves set is different from the actual number of valves controlled, an alarm message is issued.
** If the parameter is set to the value 0 h, the alarm is switched off.
The parameters P09 and P10 are only displayed if the service operating hours code (parameter
P11) has been entered.

RM-208 CB.13.01 Easy Line Documentation
RDN 10000795 10 20.03.2019
6 Operating modes
6.1 Test mode
In test mode, the most important functions in the control sequence are checked and shown on the text
display. To start test mode, call up parameter no. P08 “Test mode” (see section 5.2 for more information)
and select one of the following test modes:
Test mode 1 (Valve test)
Each valve connected is activated in sequence and shown in the text display.
Test mode 2 (Input test)
The signal statuses of the inputs are displayed on the text display.
Test modes 3-5
For manufacturer purposes only
Test mode 0 (test mode off)
Test mode is switched off.
6.2 Down time cleaning
To activate down time cleaning, perform the following steps:
Remove the factory-fitted wire jumper on input 10, 11.
Connect a free auxiliary contact (make contact) of the fan contactor to terminals 10 and 11. The input
should be operated in isolation.
Set parameter P05 “Down time cleaning cycles” to the required number of cycles (see also section 5.2
“Setting parameters”).
If the fan is switched on, the contact on 10, 11 closes and switches on the cleaning. When switching off
the fan, the contact on 10, 11 opens and activates the down time cleaning. The down time cleaning cycles
set are carried out. The RM-208 CB then shuts down.
6.3 Cleaning via start / stop input (external ∆p switch)
If the cleaning is controlled via an external ∆p switch, the isolated contact on the ∆p switch must be
connected to the start / stop input 12, 13.
During down-time cleaning, the start / stop input 12, 13 is inactive.

RM-208 CB.13.01 Easy Line Documentation
RDN 10000795 11 20.03.2019
7 Troubleshooting
Error Possible causes Recommended action
The “ON” LED is not lit and input
10, 11 is bridged.
-
No mains voltage
-
Check power feed
-
Device fuse is defective
-
Replace fuse
- EMERGENCY STOP
activated
- Check EMERGENCY STOP
No valve activity
-
No control system release
-
Bridge input 10, 11
- Wiring to valves interrupted - Check cables and electrical
connections
-
Magnet coil faulty
-
Replace coil
No down time cleaning - Parameter P05 = 0
(down time cleaning cycles)
- Set parameter P05 “Down
time cleaning cycles” to a
different value
- There is no signal from the
fan control
- Activate signal to input 10, 11
Cleaning ineffective - Interval time too long - Set parameter P02 “Interval”
to a lower value
- Pressure too low - Set pressure to 6 ... 8 bar
(min. 5 bar)
- Set parameter P02 “Interval”
to a higher value
-
Valve faulty
-
Check / replace valves
- Pulse time too short - Set parameter P01 “Pulse
time” to a higher value
“Alarm” LED on - The number of valves is set
incorrectly
- Set parameter P04 “Total no.
of valves” correctly
7.1 Instructions for the replacement of the device fuse
Switch off the supply voltage of the device at the in-line fuse element of main switch and take
precautions against reactivation.
Check whether main supply line carries no voltage.
Unscrew the six screws of the RM-208 CB housing cover and remove the cover.
Pull off the transparent plastic cap of the fuse holder (see picture).

RM-208 CB.13.01 Easy Line Documentation
RDN 10000795 12 20.03.2019
Pull the fuse from the holder.
Insert the new fuse into the holder.
Use only the UL listed fuses that are mentioned in chapter 11 “Technical specifications“ on page
16
.
(Shut
-off after one hour at 135% of the nominal current.)
Place the transparent plastic cap of the fuse holder.
Position the housing cover on the bottom part of the housing and tighten the six screws evenly.
Switch on the supply voltage again.
7.2 Cleaning the controller
Wipe only with a damp cloth if outside of device is soiled.
7.3 Manufacturing
The filter control system RM-208 CB was manufactured by:
RECO Gesellschaft für Industriefilterregelung mbH
Junkersring 11
53844 Troisdorf
Germany
Fon +49 (0) 2241 39704-0
for:
Norbert Heinrich
Automatisierungtechnik
Feldstraße 16
32549 Bad Oeynhausen
Germany
Fon +49 (0) 5734 6002318
Fax +49 (0) 5734 6002319
E-mail: m[email protected]
Please contact
Norbert Heinrich to obtain technical support.

RM-208 CB.13.01 Easy Line Documentation
RDN 10000795 13 20.03.2019
8 Text messages on the display
Display Explanation
Reset status and text version
The text message is displayed for approx. 1 second after the voltage is
switched on.
Reset RM204VXX
Controller is not enabled through inputs 10 and 11.
Stand By
+ -Val.No
The control has been enabled via input 10, 11 and stopped via input 12,
13.
Cleaning Off
+ -Val.No
The control has been enabled via input 10, 11 and started via input 12,
13.
Cleaning On
+ -Val.No
Down time cleaning active
DTC Cleaning ON
+ -000 Pcs
The alarm switching point for the service hours counter has been
exceeded.
Call Service
+ -Val.No
A connected I/O module RM-LV8 or RM-LV16 is out of order
or
the total number of valves (parameter P04) is set incorrectly.
or
the valve outputs of a connected I/O module RM-LV8 or RM-LV16 are not
taken in sequence.
RM-LVX Alarm
+ -Val.No

RM-208 CB.13.01 Easy Line Documentation
RDN 10000795 14 20.03.2019
9 Details on the equipment function
Cleaning
Cleaning starts at the first valve. If the cleaning is interrupted via the start/stop input 12, 13, the control
sequence is continued at the next cleaning procedure. The cleaning then starts at the valve following the
last valve activated.
If the control is reactivated following a mains voltage failure, a restart is carried out.
Relay output 8, 9 to control extractor elements
If automatic components for dust removal (extractor elements) are fitted, these need to be in operation
during cleaning and during down time cleaning. Connect the cut-out for controlling these drive units to the
isolated output 8, 9.
“Alarm” relay output 5, 6, 7
As soon as the supply voltage is present on the RM-208 CB, relay contact 5, 6 closes and contact 6, 7
opens. In the following situations, relay contact 5, 6 opens and contact 6, 7 closes:
Supply voltage failure
Failure of a voltage internal to the equipment
Fault in a connected O module
Total number of valves is set incorrectly (parameter P04)

RM-208 CB.13.01 Easy Line Documentation
RDN 10000795 15 20.03.2019
10 Glossary
Term Explanation
Cleaning
Cleaning the filter elements using compressed air pulses.
Compressed air pulse
cleaning
Cleaning of the filter elements using compressed air pulses.
Differential pressure
Difference between the air pressures ∆p on the pure gas side (behind the
filter element) and the crude gas side (in front of the filter element) of the
filter.
Down time cleaning
Cleaning the filter elements after the system is shut down for a set
duration or number of cycles.
Down time cleaning cycles
The number of cleaning cycles performed in the down time cleaning.
Down time cleaning input
Input on the RM-208 CB for starting the down time cleaning.
Down time interval time
Pause time during the down time cleaning.
Expansion module
If the filter has more than 8 valves, expansion modules of type RM-LV8
(for 8 valves) or RM-LV16 (for 16 valves) are required. A maximum of 7
type RM-LV16 expansion modules can be connected to the main
RM-208 CB equipment. With the outputs on the main equipment, this
makes a maximum of 120 valve outputs available.
Extractor element
Device for extracting the filter casing from the dust deposited. E.g.
cellular wheel sluice, trough conveyor worm.
Extractor element contactor
Contactor which switches an extractor element drive unit on and off.
I / O module
Input / output module (module for the input and output of control signals)
Operation mode
Status of the RM-208 CB in which the equipment is ready for operation.
Parameter selection mode
Status of the RM-208 CB in which the equipment operator can select a
parameter.
Parameter setting mode
Status of the RM-208 CB in which the equipment operator can set a
parameter.
Pause time
(also Interval time)
Time period between two consecutive control pulses from the valve
outputs when the cleaning is running.
Pulse time
Duration of a control pulse on the valve outputs
Service operating hours
alarm
Alarm issued when the operating hours set for the maintenance interval
has elapsed.
Service operating hours
code
Code which needs to be entered to change the set value for the service
operating hours.
Solenoid valve
(also relay valve) electromagnetically operated valve for the pneumatic
triggering of the filter membrane valves. The membrane valves in turn
release the compressed air strokes for filter cleaning.
Start / stop input
Input on the RM-208 CB for starting and stopping the cleaning via an
external ∆p switch.
Total no. of valves
Number of all valves connected to the RM-208 CB and to the expansion
modules.
-Y1, -Y2, -Y3, ...
Designations of solenoid valves 1, 2, 3, …
∆p switch
Switch which is triggered by a differential pressure value set and which
activates the filter cleaning.

RM-208 CB.13.01 Easy Line Documentation
RDN 10000795 16 20.03.2019
11 Technical specifications
Application
Data
Supply voltages
110 V AC 50-60 Hz
Power consumption: max. 53 VA
Back-up fuse: max. 4 A
Signal inputs
24 V DC, operate ensuring isolation
Signal output
Relay outputs, max. 2 A, 250 V
or 1 A, 30 V DC
Control outputs for valves
For valves with a rated voltage of 24 V DC,
can be expanded to 120 outputs,
Output power in pulse mode 42 Watt
Outputs for expansion
modules
Supply voltage and pulse wires to the expansion modules
Device fuse
0.3 A / M, 5 x 20 mm, 250 V
Type Bell 5MT 300 mA
(ESKA UL 521.012)
Temperature range
-20°C to +50°C
Protection class
Housing IP-66 not evaluated by UL / Type 5
Installation torque of cover screws: 1,5 Nm
Weight
approx. 0.8 kg
Installation height
max. 2000 m above M.S.L.
Electrical connections
Tension spring terminals
Permissible wire gauge
single-wire: 22 ... 16 AWG / 0.5 ... 1.5 mm²
Flexible: 22 ... 16 AWG / 0.5 ... 1.5 mm²
Cable glands
Size Sealing range Cord diameter Installation
range torque
M16x1.5 5 … 10 mm 5.6 ... 10 mm 2.0 Nm
M20x1.5 8 … 13 mm 9 ... 13 mm 2.7 Nm
M25x1.5 11 … 17 mm 13 ... 17 mm 5.0 Nm
Disclaimer
The contents of this documentation has been verified for correctness and completeness. Nevertheless, errors can not be excluded
so that we cannot guarantee the correctness of this information. Subject to alterations at any time.
Table of contents
Popular Control System manuals by other brands

Thermon
Thermon TraceNet TCM2 Installation, Start-Up, Operating and Maintenance Guide

Evoqua
Evoqua WALLACE & TIERNAN SFC SC Original manual

viZaar
viZaar INVIZ MATRIX Short guide

WORKSWELL
WORKSWELL THERMOINSPECTOR user manual

AGCO
AGCO Glencoe DCS3000 Operator's manual & installation instructions

Elka
Elka EH 30 L Installation and operating instructions