4
b. Use the template (supplied with the boiler) to mark the required flue position, ensuring there is the correct slope
towards the boiler.
c. Determine the overall flue length as described in Section 3, paragraph (a) to determine the number of Alpha CD 750
or 1000 mm flue extensions required.
d. Assemble the flue extensions together by locating the inner duct into the seal joint and secure each extension
together with the clamps supplied (three screws). Ensure that the clamps are positioned centrally over the joints.
Note: If it is required to cut an extension, DO NOT cut the end of the inner duct that incorporates the seal joint.
Ensure the inner duct end without the seal joint is cut so that it is 20 mm longer than the outer duct.
e. Adjust the telescopic section of the Easy-Flue to the required length and secure the Easy-Flue with the sealing tape
supplied. Fit the Easy-Flue to the extensions by locating the inner duct into the seal joint and secure with the clamp
(three screws), ensuring it is located centrally over the joint.
f. Mark the end of the flue assembly 'TOP' where it is connected to the boiler, so that the 'TOP' of the flue terminal is
aligned with the 'TOP' at the boiler end of the flue assembly.
g. Pass the complete flue assembly through the wall.
h. Position the clamp (two screws) supplied, over the bend. Fit the bend to the boiler and rotate to the correct position
and secure in position using the sealing tape supplied and the clamp. Ensure the tape is located centrally over both the
bend and boiler adaptor.
i. Slide the clamp (three screws) over the outer duct and pull the flue assembly towards the bend, locating the inner
duct into the seal joint on the bend.
j. Secure the flue assembly to the bend with the clamp (three screws) ensuring it is positioned centrally over the joint,
ensuring the 'TOP' marked on the outer duct is positioned at the top.
Note: Check the flue terminal protrudes 90 mm out of the wall and that the inner duct of the terminal is positioned
correctly, i.e. the inner duct within the terminal is at the top. See Fig. 6.
k. Make good the outside wall by fitting a flue sealing collar onto the location provided immediately behind the flue
terminal grille. Make good the inside wall as required.
Note: If flue sealing collars are being used to make good the inside wall, then they will need to be fitted before
assembling the flue.
HE
CDR
CD50 LHS
CD50 RHS
CD C/S/X
225 mm
195 mm
180 mm
420 mm
220 mm
HE
CDR
CD50 LHS
CD50 RHS
CD C/S/X
130 mm
100 mm
85 mm
325 mm
125 mm
90
45 (25 for CD50)
Boiler front
Outer duct clamp
Inner seal joint
Inner seal joint
Flue length (L)
Clamp
and tape
90° bend
Seal joint
CD Easy-Flue
Note: Ensure outer flue duct of Easy-Flue is horizontal
Note: Ensure the flue extension slopes
downwards towards the boiler by a
minimum of 25 - 30 mm per metre
CD Flue extension
Flue sealing
collar
Flue
terminal
Ensure the inner duct within
the terminal is at the top.
The inner duct must
be positioned to slope towards
the boiler
Note:
20
Fig. 6 - Side flue