GENERAL INSTRUCTIONS
Adjustment of burner
The burner is from the factory pre-set
to an average value that must then be
inaccordancewithboilermanu-facturers
instructions. These must include the
average water temperature and CO2
or O2concentration.
General instructions
The installation of the gas burner
must be carried out in accordance
with current regulations and standards.
The installers of gas burners should
therefore be acquainted with all regu-
lations and ensure that the installation
complies with the requirements. The
should be made with the greatest
care and only the correct gas should
be used.
Operating instructions
The operating instructions accom-
panying the burner should be left
in a prominent position in the boiler
room.
Instructions
The user should be thoroughly
instructed in the function of the gas
burner and the whole installation.
The supplier must instruct the user.
Inspection and maintenance
Daily inspection is advisable.
Start up
the boiler and the electric connection,
the leakage control, the venting and
the electric function test have been
carried out, the burner will be ready
for start-up.
Howerer, study the sections dealing
-
bustion air and combustion head.
Open the ball valve and switch on the
main switch. If the burner starts the
Adjustment of burner head
-
ment device changing the position of
the brake plate in the burner head. This
drop over the combustion device in
order to obtain a good pulsation free
combustion.
Which position to use depends on
input and overpressure in the boiler.
172 305 28 07-01
A general rule is that the lower capacity
the smaller the opening between
brake plate and combustion device.
Commissioning of installation
Control of the combustion. The com-
bustion quality is checked by means
in accordance with the table. Check
gas volume on the gas meter so that
the correct input is achieved.
Service
Service should only be carried out
parts should be of the same make and
approved by the same authorities as
the original. If the burner is converted
re-commissioned. If town gas is to be
to suit (e.g.a larger gas armature or a
different spring in the governor may
be required).
Gas quality CO2
lambda 1,2
02max. CO2
Natural gas 10,0 3,5 11,9
LPG 11,5 3,5 13,9
ELECTRIC EQUIPMENT
Technical data
Reset after lock-out Immediately
Supervision of ionization current
Short circuit current max. 0,5 mA
Min. required ionization current 6 µ A
Recommended range of measuring device 0...50 µ A
a - b
Start-up sequence
b - b´
"idle steps" up to the self shut-down
of the sequence switch
b ( b´) - a
Post-purge sequence
172 405 27 07-01
a
b´
b
In the event of fault conditions the
fuel supply is always interrupted
immediately and, simultaneously,
the sequence switch stops and thus
the lockout indicator. The symbol
appearing above the reading mark
P Interruption of the start-up
sequence, because the OPEN
signal has not been supplied to
terminal 8 from damper motor
to switch «max.». Terminals 6,
7and 14 are under tension until
the fault has been remedied.
1 the fault has been remedied.
Lockout
signal has been received on
completion of the 1st safety
time.
time also causes the control
to go to lockout!
◄No start, because, e.g., the
CLOSE signal has not been
supplied to terminal 8 or a
contact has not been closed
between terminals 12 and 4
or 4 and 5.
▀ Lockout due to a fault in the
2 Lockout,
signal has been received on
completion of the 2nd safety
burners).
▲Interruption of the start-up
sequence, because the OPEN
signal has not been supplied to
terminal 8 from damper motor
to switch «max.». Terminals 6,
7and 14 are under tension until
the fault has been remedied.
▼ Interruption of the start-up
sequence, because the posi-
position has not been supplied
to terminal 8 by the damper
motor. Terminals 6, 7 and 14
are under tension until
▌ Lockout,
signal has been lost during
burner operation or air pressure
failure has occured.
◄ Lockout on completion
of control programme se-
quence due to extraneous light
leaking fuel valves) or due to
Control programme under fault conditions and lockout indication
gas burner control: LFL1....