ENSIM SENSORS DX-ELS Series User manual

OPERATING
MANUEL
LEVEL SWITCH
DX-ELS
Model :
Model: 02-2021-007
Information in this manual is reviewed and completely reliable. Responsibility is not assumed due to any typing error.
Products in this manual are available only for information purpose and they may be changed without notice.
1
Models :
DX-ELS 1783
Important Notes:
Used Symbols :
: Caution : Note : Disposal
Please read this manual carefully before installation of the level switch. User is responsible for accidents and losses arising
from failure to comply with the warnings in this manual.
In the event that level switch is broken, take measures in order to prevent accidents and losses which can occur in its system.
There is not any fuse and circuit breaker on the instrument; they should have been added to the system by the user.
This manual should be stored in an easily accessible place for subsequent use.
The manufacturer's liability cannot exceed the purchase price of the device according to the law.
Do not make any modification on the instrument and do not try to repair it. Reparation should be made by authorized service staff.
Do not operate the system before making assembly in compliance with the assembly chart related to the instrument.
Products which do not contain label and serial number are considered to be excluded from the warranty scope.
The instrument's useful life, determined and announced by the ministry, is 10 years.
Table of Contents :
General Information...........................................................................................................................................................................2
Installation .........................................................................................................................................................................................7
Failure Detection..............................................................................................................................................................................16
Disassembly of Instrument ............................................................................................................................................................16
Service .............................................................................................................................................................................................16
Recalibration....................................................................................................................................................................................16
Repair................................................................................................................................................................................................16
Disposal ...........................................................................................................................................................................................16
Terms of Warranty ..........................................................................................................................................................................16
Terms of Return ................................................16
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
2
1. General Information :
1.1. Material Acceptance
Check that there is no damage on the packages during the transportation immediately after the material acceptance. If packages are
damaged, open the packages immediately and check whether products are affected or not, if there is any damage, send your
complaint report to the transporter company and its photocopy to the address of our company.
1.2. Information about Areas of Use
Level Switch is designed for industrial plants. It should never be used in mines.
Otherwise, the responsibility of the manufacturer is eliminated.
Tank level measurement and control,boiler kontrol,store room control..
Yacht water level control, sewage level control.
Hydraulic oil tank level measurement and control
Ambient Conditions: Relative Humidity: 0-98 % RH Ambient temperature: 60 °C (It is not used under -20 °C)
1.3. Working Principle
In the float when the magnet magnetic area moves according to the liquid in the tube, then the reed swicthes the electrical circuit
on or off when it reaches the level of the sensor. The changes of the reed sensors with alarm or a level information can be assessable
with a relay circuit or a control device.The advantages of providing the analog output in the enclosure are preferred by the users.
1.4. Reed Relay and Operation Conditions
Advantages:
*A variety of materials according to the flow
*Different choices of ignition
*Quick delivery
*Different types of technics
Glass Tube Contact
Inert Gas Magnetic Reed
Wire
Magnet
Closed
Open
SPST-NO
Single Pole-Single Throw
Normally Open
SPST-NC
Single Pole-Single Throw
Normally Closed
SPDT-NO/NC
Single Pole-Double Throw
Open / Closed Contact
Inductive Load
Capacitive Load
When reed switch is used for loads such as electromagnetic relay ,contactor or solenoid, reed switch may be exposed to very high
voltage depending on value of inductive load. This causes either failure of switch or shortening its service life. Therefore, it is
recommended to be used as follows depending on used voltage, for the purpose of protection of switch.
When reed switch is used with capacitive load, it may cause that high current passes over reed switch, depending on value of
capacity during Charge '96 Discharge of capacity. So this may cause failure of switch. It is recommended to be used as follows
depending on used voltage, for the purpose of protection of switch.
Inductive Load Inductive Load Inductive Load
Diod
DC AC AC
C R Varistor
Neon Lamp
AC
R
AC
C
R
3
1.5. Technical Specifications and Material Knowledge
Example of application :
Light Solenoid
Valve
SSRPump
control
ll 1/2 G Ex d llC Tx*1 Ga/Gb For Gas
ll 1/2 D Ex (ta/tb)*3 lllC Tx*2 For Dust
Have a look at the temperature class chart.
Certification
*
Working Temperature
(Tp)
Ambient Humidity
Ambient Temperature (Ta)
Material Connection
Housing
Float
Pipe
Connection
Float Type
Number of Float
Stem Length
Electrical Connection
Cable and Plug Entry
Number of contacts
Contact Current
Max. Contact Current
Max. Supply Voltage
Protection Class
Certifications and Approvals
Max. 125 °C , 80 °C (Plastic Model)
0-98 % Rh (Non-condensing)
(-) 20 °C ... (+) 60 °C
304 St.St. (Std.) Opt. 316 St.St. , Aluminum
Aluminium Injection - AlSi12Fe (Std)
Black (RAL 9005)
316 St.St. (Std.) Opt. PU , PP
304 St.St. (Std.) Opt. 316 St.St. , Brass, PVC , PTFE
2" BSP (Std.) Opt.Selectable from Table.
S40A (Std.) , Selectable from Table.
1 ( Std.) A large number of available.
Max. 2500 mm (Thread Included)
Terminals
M20 x 1,5 (Std)
2 x SPST - NA (Std.) Opt. It can be added.
1,5 Amper (Std.)
50 W / VA veya 20 W / VA
200 VDC / 250 VAC , 30 VDC / 140VAC (Std.) Opt. Selectable.
IP 66 (EN60529)
CE Declaration , EMC , LVD , ATEX
DX-ELS
4
Type
Level Switch
S.N.
Quantity
DX-ELS 025-00-009-01-13-01-1000-113/2-1/200-2/800-08/0
IE18030050-0008
:
:
1 pc.:
Kullaným Kýlavuzu Montajdan Önce Okunmalýdýr.
Supply 24VDC ± %10:
IE18030050-0008
:
:
:
:
Type : DX-ELS 025-00-009-01-13-01-1000-113/2-1/200-2/800-08/0
Contact Output
Process Temp.
T (Ambient)
Serial Number
Level Switch
2xNO-NC (SPDT) Max.100mA/140VAC
Max. 125°C
-20...+60°C
IE18030050-0008
www.ensim.com.tr
MADE IN TURKIYE
1783
Std. Package
1.8. Target Group
This operating manual has been prepared for qualified technical personnel.
1.9. Certifications and Approvals
:It shows that, product meets required conditions of EU with CE stamp
and stipulate that product passed quality assessment stages
TS EN 60079 - 0 : 2013
TS EN 60079 - 1 : 2014
TS EN 60079 - 31 : 2014
ATEX (2014 / 34 / AB) :
LVD (2014 / 35 / AB) :TS EN 61010 - 1 : 2012
TS 3033 EN 60529 : 1997
TS EN 61326 - 1 : 2013EMC (2014 / 108 / AT) :
All the features and tests on this decument has manufactured with DX-ELS models at LONCA Inc.
Note:
1.6. Label Information :
1.7. Package and package contents :
Please check whether you have taken delivery
of below listed content completely or not and check
its conformity with criterions in your order:
*Float Level Switch
*This operating manual
Box
Label
Serial Number
Model
Piece Barcode
Supply Voltage
Model
Serial Number
Notified
Date Sign
Explosive ProtectionAreaProduct Name
Producer Website
Warning Symbols
Working Conditions
Manufacturer
Brand
Product
Label
If the ATEX certificate metal label is damaged, you can contact
the manufacturer with the serial number.
Note :
Metal
Label
Ground
Label
IE 18 03 0095 - 0014
Product
Number
System
Number
Month
Year
Work
Order
LONCA A.Þ. Ferhatpaþa Mah.Gazipaþa Cad. No:104A
34888 Ataþehir - ÝSTANBUL / TÜRKÝYE
TSE 18ATEX0099
ll 1/2 G Ex d llC Tx*1 Ga/Gb
ll 1/2 D Ex (ta/tb)*3 lllC Tx*2
Type B20x
www.ensim.com.tr
16A 240 VAC 50 / 60 Hz IE18030095-0014
S.No:
Manufacturer Name ManufacturerAddress
Model Serial
Number
Features
Explosive Protection
Area ATEX Classes
Explosive ProtectionAreaProduct Name
5
1.10. Safety Ýnstructions (ATEX)
Safety instructions should be read and applied to the end.
-The following notes must be taken into attention to protect the operator and the enviroment from possible hazards.
-The device setup and maintenance of this device must be done by knowledgeable persons who has read the instructions and is familiar with
the safety at work.
-Ýt should be checked by the users that the products are fitted suitable to the zone maps.
-Work safety,must be observe by accident prevention regulations and national installation standards.
-The product should be used within the specification presented guideline.
-You can only mount the device when there is no presure.
-These safety instructions are protected in terms of 1 / 2 D and 1 / 1 G category for DX-ELS coded series and is compatible with
TSE 18ATEX0099 and CE certificate.
-The Label should be used in appropriate environments.
-Because the enviroment is max. 60 °C you should choose a suitable cable for use.
-Do not over tighten the cable gland in order not to affect the IP protection class.
-Make sure the cable entry and plug is tightened right.
-Ground connection must be done properly and checked without energizing.
-Before starting use make sure the lid is fully closed and the set screw is tightened.
-DX-ELS models are metal protected.Ýt is Compatible with different supply voltages specified in the catalog.
- The metal enclosure must be in the 2D or 2G zone. The pipe and float section must be located in the 1D and 1G zone.
-Max. working temperature,max. Surface temperature can change depending on the model, Please read the document carefully before using.
-During the mounting it should be checked that there is no mechanical stress or deformation in the tank wall.When this happens, the sensor should
not be energized without the necessary correction measures.
-Check that the presure in the tank hasnt exceed the presure shown in the catalog.
-The mounting sensor must be mount properly in the tank filling system.In case it is not suitable, the sensor must be protected and the in-tank
apparatus must be protected.
- Flange surface smoothness must be maintained in flanged connection.
- Flange seating surface should not be scratched, and suitable liquid gasket should be used instead of sealing with gasket in counter flange mounting.
- Flanged connections are welded with the sensor part.
-The sensor is designed to withstand the chemical effects of the materials.Check the suitability of different materials.
-The Sensors are in suitable storage conditions and protected from dust and damp.
-Device repairs should only be done at the manufacturer Lonca Inc.
-Protect the device from friction and cleaning should be done without water.
-In case of improper circuit conditions, the main energy must be completely disconnected and safety measures should be taken without replacing
the temperature circuit breaker with its backup.Changes should be made in a safe area.
6
1.11. ATEX Marking Sample Description
II 1/2 D Ex ta/tb IIIC T4 IP66
II 1/2 G Ex d IIC T4 IP66
Dust
Explosive Protection
Area
Equipment Group
Equipment Category
Explosive Atmosphere
Explosive Protection
Protection Type
Dust Type
Temperature Class
(Max. Surface Temperature)
Housing Protection Class
Gas
Explosive Atmosphere
Protection Type
Temperature Class
(Max. Surface Temperature)
Housign Protection Class
Equipment Group
Equipment Category
Explosive Protection
Gass Type
Explosive Protection
Area
2. Installation :
2.1. General Notes :
The device installation is in 2014 / 34 / EU criteria to ensure the safety of atmosphere and people from explosions, must only be done by staff who
knows the safeguards.
Do not apply force to the instrument during the installation!
Do not use the Level switch with a greater pressure than recommended pressure.
Do not forget that instrument is precise, carry it carefully and prevent not to be damaged.
It should be guaranteed that there are not any magnetic particles.
The Max. working pesure should not be exceeded.
2.2. General Installation Stages
*Remove Level switch from the box carefully
*Check whether gasket is appropriate for fluid or not. If is not appropriate, contact with the producer.
*Then, apply below mentioned explanations according to structure of the design.
2.3. Special Notes
*Please ensure that there is no mechanical stress on the shaft following installation. Such case will cause slipping in thecharacteristic curve.
*Level switch must be placed upright or horizontal.
*Allocate valve certainly in the process connection while instrument is used.
*Allocate blowdown valve under bottom flange for blowdown.
*If instrument is mounted outside and if there is any danger of lightning or
excessive pressure, take preventive measures by taking necessary measures.
*In the operating conditions, Level switch may be hot according
to situation of fluid, in this case, do not touch the indicator, otherwise your skin is damaged.
*The grounding product must be done properly. (can be done outside or in housing)
2.4. Installation For Mechanical Connections
*Use appropriate O-Ring or gasket for tightness.
*Ensure that its surface is clean and smooth.
*Assemble the instrument manually.
*Connect the contacts as shown in the figure.
(For G1" max. 20 Nm, G 1 1/4, for G 1 1/2 max. 30Nm)
7
2.5. Mechanic Connections :
Order
Code
Dimension
B
Hex
[mm]
Stem Lenght
b [mm]
3/8BSP
1/2BSP
3/4BSP
1BSP
1 1/4BSP
1 1/2BSP
2BSP
50
50
50
50
50
60
70
20
14
14
23
23
23
23
(ISO228-1)
0003
0004
0005
0006
0008
0009
0012
PN 16 D (mm)
DN25
DN32
DN50
DN80
DN100
165
140
165
200
220
85
100
125
160
180
D1 (mm) b (mm)
16
16
18
20
20
(ISO1092-1)Order
Code
0502
0503
0505
0507
0508
PN 40 D (mm)
DN25
DN32
DN50
DN80
DN100
115
140
165
200
235
85
100
125
160
190
(ISO1092-1)
D1 (mm) b (mm)
18
20
20
20
24
Order
Code
0702
0703
0705
0707
0708
150 LBS D (mm)
DN50
DN65
DN80
DN100
152,4
177,8
190,5
228,6
121
139,7
152,4
157,2
(ANSI B16.5)
D1 (mm) b (mm)
19
22,2
23,8
23,8
Order
Code
1005
1006
1007
1008
Dimension Dia. b
(mm)
DN32
DN50
DN65
50,5
64
91
15
17
17
(ISO2852)
D (mm)
1501
1502
1503
Order
Code
D (mm)
DN40
DN50
DN100
56
68
121
48
61
114
d1 (mm) A (mm)
13
14
20
Dimension
DN40
DN50
DN100
Dimension
1600
1601
1602
Order
Code
b
D1
D
AA
B
b
b
D
D
d
d1
A
Thread (Connection has been welded with sensor)
Flanged (Connection has been welded with sensor)
Clamp (Connection has been welded with sensor)
Dairy
(Connection has been welded with sensor)
8
Not: RLY ledi pompa çalýþýrken
sönecek þekilde dizayn edilmiþtir.
1 2 3 4
EX-GNL
1
2 3
4
1 2 3 4
EX-GNL
1
2 3
4
Liquid level relay
(12 / 24 VDC)
Four contacts
NO or NC
Lower
Contact
Upper
Contact
Two independent contacts
NO or NC
Two double contacts
NO / NC (SPDT)
NC NO
NC NO
Com
Com
1 2 3 4
EX-GNL
1
2 3
4
1 2 3 4
EX-GNL
1
2 3
4
NONC
Com
4
3
2
1Supply
Pipe
Float
Ta
Factory Area
(Safe)
ZONE 21 / 1
or
ZONE 22 / 2
Cable Plug
(Suitable Cable Diameter
: Ø 6-12 mm)
Aluminium Housing
2.5. Example Mounting Types :
DO NOT OPEN WHEN ENERGIZED
KEEP TIGHT WHEN CIRCUIT ALIVE
M3
Cover
Body
Thread
O-Ring
Cover Chain Screw
Grounding Terminal
(Max.1,5 mm2)
Recommended Cable
(5x1,5 mm2)
Bund
Stops
Tp
Process Side
(Explosive Enviroment)
ZONE 20 / 0
or
ZONE 21 / 1
or
ZONE 22 / 2
2.6.Electrical Installation
Make the electrical connection of the instrument according to details on its label, table and cable figures in this manual
Note : It has been produced according to IPC A 600 class 2 conditions and tested with 100 % E-test. Moreover,
HASL (non-lead) surface test has been applied.
Lower
Contact
Upper
Contact
Housing MATERIAL PROTECTION
CLASS
TEMPERATURE
(°C)
TYPE
B21x Aluminium IP 66 (-) 40...(+) 200
SIZE
a x b (mm)
132 x 104
ORDER
CODE
704
Aluminium
B21x
b
a
Test Rod : 304 St.St. (Std.) Opt. 316 St.St.
304 St.St. (Std.) Opt. 316 St.St.
Rod Material
Shaft Material
It is produced as a spring.As an optional it can be inside housing.
2.7. Parts and Accessories :
9
Minimum
Distances
2.8. Float Types :
Type Material X Y Z A BC
S1Y
S1A
S10Y
S11A
S2A
S5A
S6A
S7A
S17A
S40A
S41A
S42A
S52A
S53A
S54A
304 St. St.
316 St. St.
304 St. St.
316L St. St.
316 St. St.
316 St. St.
316 St. St.
316 St. St.
316 St. St.
316 St. St.
316 St. St.
316 St. St.
316 St. St.
316L St. St.
316L St. St.
28
28
25,4
28,6
43
73
73
43
52
55
55
55
73
52,5
51
28
28
24,5
28
43
73
73
52
35
55
55
30
40
50,2
61,2
9.5
9.5
9.5
9.5
11
20
17
15
15
15
15
15
20
15,5
15,5
8
8
8
8
10
16
15
13
13
13
13
13
16
14
14
10
10
10
15
15
30
30
30
30
30
30
20
20
10
10
150
150
110
200
150
150
150
150
150
150
150
150
150
200
200
0.80
0.80
0,82
0,70
0.80
0.65
0.65
0.88
0.85
0.80
0,9
1,2
0,9
0,6
0,47
25
25
22
26
34
50
50
34
39
42
42
42
50
42
50
50
50
45
52
68
99
99
68
78
82
82
55
65
82
90
25
25
22
26
34
50
50
34
39
42
42
42
50
42
50
Z
X
Y
G
S2A / S5A / S6A
S40A / S41A / S53A
X
Y
Z
G
S42A / S52A
X
G
Y
Z
S1Y / S1A / S7A / S17A
S10Y / S11A / S54A
X
Y
Z
G
P3 / P6 / P7 P9
X
Y
P25
Type Material X Y Z A BC
P3
P6
P7
P9
P25-1
P13
PU
PU
PU
PP
PU
PU
30
35
44
46
25
30
45
42
50
44
150
32
12
15
18
17
-
12
10
13
15
15
-
10
1
1
1
5
1
1
80
80
80
80
80
80
0.76
0.65
0.40
0.65
0.80
0.90
28
35
38
38
-
28
60
65
70
76
-
75
40
40
50
38
-
40
001
101
006
110
102
104
105
106
111
113
114
115
118
119
120
201
203
204
213
206
207
ABC
Order
Code
Order
Code Pipe
Dia.
Max.
Press. Density
Max.
Temp.
Pipe
Dia.
Max.
Press. Density
Max.
Temp.
10
** Length -/+ 5 mm tolerance is available.
2.9. Sample Models
Housing - Thread
(Std.)
Close
Open
L1
L2
L
2 BSP
L1
L2
L
ØDN
L1
L2
L3
L
Housing
Double Float Housing - Thread
L1
L2
L
Sample Application :
Stop
Start
Max.
Min.
NC
NO
Start
Stop
EMPTYING
Max.
Min.
NC
NO
Close
Open
Close
Open
Close
Open
Housing - Flanged
Close
Open
Close
Open
Close
Open
2 BSP 2 BSP
Close
Open
Close
Open
FILLING
11
2.10.Maximum Surface Temperature
Temperature Class Table
DX-ELS Plastic
STD.
MODEL
DX-ELS
(Metal)
5 min.20 min.
(-) 20 °C...(+) 125 °C (-) 20 °C...(+) 80 °C
Plastic models
working temperature (-) 20 °C...(+) 60 °C
DX-ELS
(Plastic)
DX-ELS (Metal)
Thermal Protection Insurance is 105 °C
Thermal Protection Insurance is 92 °C
T Ambient
MAX. AMBIENT TEMPERATURE
ZONE 21 / 1
T Process
MAX. PROCESS TEMPERATURE
ZONE 20 / 0
T Surface
MAX. SURFACE TEMPERATURE TEMPERATURE CLASS
(-) 20 °C < T Ambient < (+) 30 °C...(+) 60 °C Working Temperature: (-) 20 °C...(+) 80 °C
Protection Case :
Material : 304 Stainless Steel
Welded manufacturing
Opens - Closes Hinged
To Protect Against external conditions.
Without opening the cover
standby time
Working temperature
(-) 20 °C < T Ambient < (+) 30 °C...(+) 60 °C Working Temperature: (-) 20 °C...(+) 125 °C
T Ambient
MAX. AMBIENT TEMPERATURE
ZONE 21 / 1
T Process
MAX. PROCESS TEMPERATURE
ZONE 20 / 0
T Surface
MAX. SURFACE TEMPERATURE TEMPERATURE CLASS
30 °C
40 °C
50 °C
60 °C
125 °C
125 °C
125 °C
125 °C
50 °C
60 °C
70 °C
84 °C
T6
T6
T6
T6
30 °C
40 °C
50 °C
60 °C
80 °C
80 °C
80 °C
80 °C
40 °C
53 °C
65 °C
82 °C
T6
T6
T6
T6
12
2.11. Part Names
Cover Seal
Chain
Cover Set screw
Cover
Electronic Cart
Body
Terminal
Switch
Reed Relay
Product Label
Grounding Label
Body Set screw
Grounding Screw
Grounding Internal Bracket
Stopper
Cable Record
Metal Label
Body Seal
Thread
Pipe
Thimbile
Float
O-Ring
Pipe Plug
Grounding Screw
Grounding Outer Bracket
Connection Thread
Thimbile
13
Aluminium
....................................................................03
Special........................................................................x
2.12.
Order Form : Please consider sample models when coding
2CERTIFICATE
No..........................................................................0 (EN10204-3-1) Material Certification............................1
ATEX..................................................................................2
4ELECTRICAL CONNECTION
With Terminals.....................................................00
Special..........................................................................x
6CONNECTION MATERIAL
304 Stainless Steel.........................................01
316 Stainless Steel........................................02
1MODEL
Standard Version .................................DX-ELS
3HOUSING
Aluminium Housing
B21x, IP66...................704 Special..........................................................................x
5CONNECTION
(Connection has been welded with sensor)
Thread 3/8 BSP.........................................003
Thread 1/2 BSP.........................................004
Thread 3/4 BSP .......................................005
Thread 1 BSP.............................................006
Thread 1 1/4 BSP.......................................007
Thread 1 1/2 BSP.......................................008
Thread 2 BSP............................................009
Thread 1/2 BSP (Adjustable).....................013
Thread 3/8 BSP With Elbow......................093
Thread 1/2 BSP With Elbow.....................094
1/8 NPT..................................................................051
1/4 NPT..................................................................052
3/8 NPT..................................................................053
1/2 NPT..................................................................054
3/4 NPT..................................................................055
1 NPT.....................................................................056
1 1/4 NPT...............................................................057
1 1/2 NPT...............................................................058
2 NPT.....................................................................059
DN 25 - PN16 Flanged............................................103
DN 32 - PN16 Flanged.............................................104
DN 50 - PN16 Flanged.............................................105
DN 80 - PN16 Flanged.............................................108
DN 100 - PN16 Flanged..........................................109
Special........................................................................x
Note: Refer to the table for others.
PIPE SIZE
Ø10 mm...........................................................10
Ø12 mm...........................................................11
Ø12.7 mm............................................................................12
Ø13 mm.............................................................................13
Ø15 mm............................................................................15
Special.........................................................................x
7
14
13 OPTIONAL
No................................................................. .0
Pt100 Sensor................................................/ P
Liquid Level Relay................................../ SSR
External Tank (Measurement must be specified) ... / H
Test Rod ............................................................................ / T
Float Housing... ................................................................ / M
Special................................................................................ / x
8PIPE MATERIAL
PVC..................................................................................08
PTFE...................................................................................66
Special..................................................................................x
12 CONTACT STRUCTURE
NO Reed Relay.........................................................06
NC Reed Relay.......................................................07
NO / NC Reed Relay...........................................................08
NO Hold Type Reed Relay................................................09
Special.................................................................... / x
10 FLOAT MODEL / FLOAT NUMBER
Select from Table......................Number....Piece Note: Should be selected according to the connection
and radius.
11 CONTACT NUMBER / DISTANCE (mm)
Piece / Lenght (mm)............................................ Note: From connection thread included
EXAMPLE
DX-ELS 025 - 00 - 005 - 01 - 13 - 01 - 1500 - 001 / 1 - 1 / 1400 - 08 / 0
DX-ELS Level Switch, Plastic Housing, 3/4 BSP Male Thread, Connection and Pipe Material 304 St.St.
L=1500 mm, S1Y Float , L1= NO / NC Reed Relay Output
STEM LENGHT
.... mm
9
Note: From connection thread included
304 Stainless Steel....................................................01
316 Stainless Steel....................................................02
15
2.13.
WARNING !!!
Please pay attention to following matters in order to operate your level switch properly.
Do not pull the cable strongly,
otherwise the characteristics
might be changed.
Please keep away from magnetic materials
like iron board ; otherwise the
characteristics might be affected
Please do not drop ,
otherwise the characteristics
might be changed.
Please do not dip cables
potting into liquids,otherwise
instulation problem may cause.
Do not fasten switch reversely ,
otherwise its characteristics
might be changed.
Do not connect the switch in reverse.
Their characteristics may vary.
Vibration might be
caused instability.
Do not remove the plastic parts
of the bottom of the switch body ,
do not loosen.
In case vapour splash cable
potting points,insulation
problem may cause.
Excess current , to be drawn as
a result of direct connection to motor,
may burn relay of switch
Please avoid using with liquids which
damage materials of parts ,otherwise
quality can not be maintained accurately.
Please do not mount
slant way, otherwise
switch do not work correctly.
iron board
16
If you find an error, try to eliminate it by using this table or send the instrument to our service address for repair.
The instrument should be repaired only by authorized service! Serial number shall be indicated to the authorized service center.
4. Disassembly of Instrument
Instrument should be disassembled while feeding and pressure is not available!
5. Service
6. Re-Calibration
During long period usage of level switch, there might be deviations on measurements. In those cases, recalibration is recomended. Re-calibration could be made by your
technical staff or you could send to manufacturer company. According to IEC 60017, ex proof devices must be go through detailed inspection every 3 year from purchase
date.Respobsibility of inspections are belong to the user ( IEC: International Electrotechnical Commission)
7. Repair  Manufacturer Address
If irreparable breakdowns occur, the instrument should be sent to us for repair purpose. Before this, the instrument should be cleaned carefully and packaged
so as not to be broken. Furthermore, you should also add a detailed explanation which describes the breakdown while instrument is sent. If your instrument
contacts with harmful substances, decontamination report should be also sent additionally. In the event that instrument does not have any decontamination
report or our service department has doubts about instrument, repair process will not start until an acceptable report is sent.
8. Disposal
The instrument should be disposed according to 2002/96/EC and 2003/108/EC European Directives (waste electrical and electronic instruments).
Waste electrical and electronic equipment should not be mixed with domestic wastes!
If the instrument has contacted with harmful substances, special attention should be paid for its disposal!
9. Terms of Warranty
The instrument has warranty legally for 24 months after delivery date. Warranty demands are not accepted in case of inappropriate operation, damage on the
instrument or any modification on the instrument.
10. Terms of Return
In the return of materials, user should send an open list related to damage or problem, malfunction of the material to be returned or its operation in the different
modification, with the instrument. If it is required to return the material, used in the dangerous, corrosive or toxic fluid, in this case, used part should be cleaned
very carefully. Security of personnel should be ensured. All products to be returned should be sent to our company address, which
we have stated.
The instrument does not require maintenance. If it is desired, residue accumulated inside should be blown according to kind of fluid and instrument can be cleaned
with soft cleaning solutions. Measures should be taken during the disassembly.
If the instrument contacts with hazardous substances, necessary measures should be taken for decontamination!
Service -Manufacturer Company Name and Address:
LONCA MAK. SAN. TÝC. A.Þ. Ferhatpaþa Mah. Gazipaþa Cad. No: 104A Ataþehir - ÝSTANBUL - TÜRKÝYE
Tel:+90 216 50 50 555 Faks:+90 216 515 45 84 E-Mail: [email protected] Web: www.ensim.com.tr
3. Failure Delection
Breakdown
Fluid is leaking
It does not contact
or it contacts
continuously
Body was broken
Unsteady operation
in the contact
Probable cause
There is a hole on the body.
-Socket connection is not touched.
-Product was exposed to the magnetic field
in the ambient.
-Connetion angle is not corrrect.
-Contact may have been burned.
-Tightening the screws more than adequate during
the assembly.
-Product falling or taking a blow from outside.
-Product was exposed to the magnetic field in the ambient.
-Product was exposed to vibration.
-Product was exposed to high temperature.
Failure detection\correction
-Check that is worked under appropriate condition
and then contact with producer company.
-Check for socket connections.
-The factor which constitutes the magnetic field
should be removed or insulated.
-Correct assembly angle.
-Inform authorized service.
-Inform authorized service.
-The factor which constitutes the magnetic fieldshould
be removed or insulated.
-Vibration which will effect the product should
be prevented or it should be attached to any place
without vibration.
-Use in the appropriate opearating temperature.

This manual suits for next models

3

Other ENSIM SENSORS Switch manuals

ENSIM SENSORS ELT User manual

ENSIM SENSORS

ENSIM SENSORS ELT User manual

ENSIM SENSORS DX-ELT User manual

ENSIM SENSORS

ENSIM SENSORS DX-ELT User manual

ENSIM SENSORS ECAS 101 User manual

ENSIM SENSORS

ENSIM SENSORS ECAS 101 User manual

ENSIM SENSORS DX-ELS User manual

ENSIM SENSORS

ENSIM SENSORS DX-ELS User manual

ENSIM SENSORS ELC 21d User manual

ENSIM SENSORS

ENSIM SENSORS ELC 21d User manual

ENSIM SENSORS ELP Series User manual

ENSIM SENSORS

ENSIM SENSORS ELP Series User manual

ENSIM SENSORS DX-ELF 101 User manual

ENSIM SENSORS

ENSIM SENSORS DX-ELF 101 User manual

ENSIM SENSORS EFS User manual

ENSIM SENSORS

ENSIM SENSORS EFS User manual

ENSIM SENSORS ELP User manual

ENSIM SENSORS

ENSIM SENSORS ELP User manual

ENSIM SENSORS ISS 04 User manual

ENSIM SENSORS

ENSIM SENSORS ISS 04 User manual

ENSIM SENSORS DX-ELB 11 User manual

ENSIM SENSORS

ENSIM SENSORS DX-ELB 11 User manual

ENSIM SENSORS ELS User manual

ENSIM SENSORS

ENSIM SENSORS ELS User manual

ENSIM SENSORS ELM Series User manual

ENSIM SENSORS

ENSIM SENSORS ELM Series User manual

ENSIM SENSORS DX-ECAS Series User manual

ENSIM SENSORS

ENSIM SENSORS DX-ECAS Series User manual

Popular Switch manuals by other brands

ORiNG TES-3080-M12 Series user manual

ORiNG

ORiNG TES-3080-M12 Series user manual

LevelOne GEU-0522 Quick installation guide

LevelOne

LevelOne GEU-0522 Quick installation guide

Cisco Nexus 5000 Series Operation guide

Cisco

Cisco Nexus 5000 Series Operation guide

Honeywell CENTRAL HUB Quick reference guide

Honeywell

Honeywell CENTRAL HUB Quick reference guide

Curtiss-Wright DuraNET 3300 user manual

Curtiss-Wright

Curtiss-Wright DuraNET 3300 user manual

Asco Series 300 Operator's manual

Asco

Asco Series 300 Operator's manual

GMW 5971-160 user manual

GMW

GMW 5971-160 user manual

ATEN MiniView CS-14 user manual

ATEN

ATEN MiniView CS-14 user manual

HP 3600 v2 Series Command reference

HP

HP 3600 v2 Series Command reference

Aruba AT-8400 SERIES user guide

Aruba

Aruba AT-8400 SERIES user guide

F&F AZH-LED manual

F&F

F&F AZH-LED manual

Allied Telesis AT-8000S/24POE datasheet

Allied Telesis

Allied Telesis AT-8000S/24POE datasheet

Siemens SCALANCE X-400 operating instructions

Siemens

Siemens SCALANCE X-400 operating instructions

FS.COM ELPS Configuration manual

FS.COM

FS.COM ELPS Configuration manual

Atop EHG75 series user manual

Atop

Atop EHG75 series user manual

Laser AO-USBMHV2P Specifications

Laser

Laser AO-USBMHV2P Specifications

Raritan PX3TS Quick setup guide

Raritan

Raritan PX3TS Quick setup guide

GST CAN100H quick start guide

GST

GST CAN100H quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.