HUIZHOU EPEVER TECHNOLOGY CO., LTD. Tel:+86-10-82894896/82894112/+86-752-3889706 Website:www.epever.com
3 4
Timer3
LED Rated Current Percentage
Timer4/5
LED Rated Current Percentage
Timer6
LED Rated Current Percentage
※The default value can be changed according to the user's requirement.
4)Time Control
Control the load on/off time by setting the real-time clock.
5) Intelligent Power Reduction Mode
When the battery voltage goes lower than the "Reduce Power Start Voltage (adjustable),"
the intelligent power reduction mode is enabled. The LED output current is automatically
reduced in linear with the battery's voltage drop. When the battery voltage goes lower than
the "Reduce Power End Voltage (adjustable)," the LED output current is 2% of the rated
load current. The minimum percentage can be set to 1%. Also, when the battery voltage is
higher than "Reduce Power Start Voltage," the controller exits the intelligent power
reduction mode.
In Light ON/OFF and Light ON/Timer mode, the load is turned on after a
1-minute delay,the delay time can be set.
The controller's real-time clock is an analog clock, valid at power-on and
invalid after power-off. When using the time mode, the clock needs to be
calibrated by handheld devices. Do not power off the controller after
calibration.
6. Setting Operation
7. Protection
When the battery is correctly connecting, the
PV can be reversed.
The controller is no
damage
When the PV is not connected, or the
connection reversed, the battery can be
reversed.
WARNING: Controller is damaged when
the PV connection is correct, and the
battery connection is reversed!
The battery voltage reaches the OVD
The battery voltage reaches the LVD
The temperature sensor is higher than 65℃
The temperature sensor is less than 55℃
Lithium battery
Low
Temperature★
The temperature sensor is less than the low-
temperature value
Stop charging or
discharge
The temperature sensor is higher than the
low- temperature value
Begin charging or
discharge
Load current ≥2.5 times rated current
In one short circuit, the output is OFF 5s;
Two short circuits, the output is OFF 10s;
Three short circuits, the output is OFF 15s;
Four short circuits, the output is OFF 20s;
Five short circuits, the output is OFF 25s;
Six short circuits, the output is OFF
Output is OFF
Clear the fault:
Restart the
controller or wait for
one night-day cycle
(night time>3
hours).
Load Open
Circuit(Load
over voltage)
Max. load voltage≥68V
One open circuit, the output is OFF 5s;
Two open t circuits, the output is OFF 10s;
Three open circuits, the output is OFF 15s;
Four open circuits, the output is OFF 20s;
Five open circuits, the output is OFF 25s;
Six open circuits, the output is OFF5s;
Seven open circuits, the output is OFF5s
Output is OFF
(Cycle to perform)
★If selecting a lithium battery, the low-temperature value(LTV) must be set according
to the specification; otherwise, the lithium battery is damaged.
8. Protection
Charging LED
indicator off during
the daytime when
sunshine falls on PV
modules properly
Confirm that PV and battery wire
connections are correct and tight
Min.9V can start up
the controller.
Measure the battery voltage with a
multi-meter. Min.9V can start up the
controller.
Battery LED
indicator green Fast
Flashing
①Disconnect the solar array and
measure the battery voltage; ②Change
the controller; ③Change the battery
Battery LED
indicator red
When the battery voltage is restored to
or above setpoint (low voltage reconnect
voltage), the load work
Battery Status LED
red indicator
flashing
The controller automatically stops
working. When the temperature is below
50 ºC, the controller resumes working.
All the LED indicator
flashing(battery red
indicator flashing)
Check whether the battery voltage
matches the controller's working voltage.
Please change to a suitable battery or
reset the working voltage
Power on normally,
the load is off
①Unreliable
wiring, the
connection fails.
②The loading
mode is wrong
③The controller
does not match
with the LED light.
④Output short
circuit
①Check the connecting cables
②Check the load mode and parameter
③The voltage of the LED-light source is
not in the output voltage range of the
controller
④Check the connecting cables and LED
light source
The dimming
function is invalid
The controller does
not match with the
LED light source.
This product is a
step-up current
control; if the input
voltage is lower
than the rated
voltage, it is not
working.
①Replace the LED light
②Reduce system rated voltage grade
and replaced the product model
For example, switch the 24V system to a
12V system, and replace the
corresponding controller.
①When the battery is over-discharged, the battery indicator is red. The load keeps off all the
time before the voltage is more than the Low Voltage Reconnect Voltage (LVRV). To judge
the system is normal or not, firstly measuring the battery voltage, whether it is more than
LVRV; if not, restarting the controller to detect the load.
The LVRV can be set, but it must be done carefully to avoid damaging the
battery if the LVRV is set too low.
9. Technical Specifications
◆When selecting a lithium battery, the controller cannot automatically recognize
the nominal system voltage and has no temperature compensation.
▼The parameters are the 12V system at 25 ºC, double the values in the 24V system.
10. Disclaimer
This warranty does not apply under the following conditions:
Damage from improper use or use in an unsuitable environment.
PV or load current, voltage, or power exceeds the rated value of the controller.
The controller's working temperature exceeds the limit working temperature.
User disassembly or attempted to repair the controller without permission.
The controller is damaged due to natural elements such as lighting.
The controller is damaged during transportation or shipment.
Any changes without prior notice! Version number:V2.2
Max. PV open circuit voltage
Battery input voltage range
(Max. Battery Voltage +2V)~60V
Load open circuit voltage
Maximum output efficiency
Output current
control accuracy
Lead-acid battery: Sealed(default)/Gel/Flooded/User
Lithium battery:LiFePO4/Li-NiCoMn/User
Sealed:14.6V; Flooded:14.8V;User:9-17V
Sealed:14.4V;Gel:14.2V;Flooded:14.6V;User:9-17V
Sealed/Gel/Flooded:13.8V;User:9-17V
Reduce Power Start
Voltage ▼
Sealed/Gel/Flooded:12.2V;User:9-17V
Reduce Power End
Voltage ▼
Sealed/Gel/Flooded:12.0V;User:9-17V
Low Voltage
Reconnect Voltage▼
Sealed/Gel/Flooded:12.6V:User:9-17V
Low Voltage Disconnect
Voltage▼
Sealed/Gel/Flooded:11.1V:User:9-17V
LiFePO4(4s):14.5V/Li-NiCoMn(3s):12.5V/User:9-17V
Reduce Power Start
Voltage ▼
LiFePO4(4s):12.8V/Li-NiCoMn(3s):12.2V/User:9-17V
Reduce Power End
Voltage ▼
LiFePO4(4s):12.0V/Li-NiCoMn(3s):10.5V/User:9-17V
Low Voltage
Reconnect Voltage▼
LiFePO4(4s):12.8V/Li-NiCoMn(3s):10.5V/User:9-17V
Low Voltage Disconnect
Voltage▼
LiFePO4(4s):11.1V/Li-NiCoMn(3s):9.3V/User:9-17V
Charge Circuit Voltage Drop
Working environment
temperature
PV/BAT:14/2.5
LOAD:18/1.0
PV/BAT:12/4.0
LOAD:18/1.0
There are two methods to check and set the controller’s
parameters:
1) 2.4G Remote Controller—RC11
This method can realize one-key setting operation which is
suitable for bulk quantity products setting or applied in the
projects.
2) Super Parameter Programmer—FC02
NOTE: Please refer to the user manual of handheld device.