5Configuration (parameter options)
Content of chapter
5.1 Parameter usage_________________________________________________________________________13
5.1.1 Parameter number, resolution and data format ______________________________________________13
5.1.2 Modbus access (TRA-F221-A only) ________________________________________________________14
5.2 Setting controller parameter with user interface_________________________________________________14
5.3 Modbus settings (TRA-F221-A only) __________________________________________________________14
5.3.1 Parameter P00x overview_______________________________________________________________14
5.4 Operating options ________________________________________________________________________15
5.4.1 Parameter P1xx overview _______________________________________________________________15
5.5 Quick system and output configuration (application specific) _______________________________________16
5.5.1 Parameter P000 overview_______________________________________________________________16
5.5.2 Application modes: Wiring diagrams of outputs ______________________________________________16
5.6 System and output configuration ____________________________________________________________17
5.6.1 Parameter P2xx overview _______________________________________________________________17
5.6.2 Application modes: Valve control diagrams _________________________________________________18
5.6.3 Application modes: Wiring diagrams of outputs ______________________________________________19
5.6.4 Manual vs. auto heat/cool change ________________________________________________________20
5.6.5 3-position valve control ________________________________________________________________21
5.6.6 Modulating valve control________________________________________________________________21
5.6.7 Fan extension time for electric heater _____________________________________________________21
5.6.8 Periodic fan kick ______________________________________________________________________21
5.6.9 Floor heating system with or without floor temperature limitation ________________________________21
5.7 Set points ______________________________________________________________________________22
5.7.1 Parameter 3xx overview________________________________________________________________22
5.7.2 Temperature set point types ____________________________________________________________22
5.8 Control settings _________________________________________________________________________24
5.8.1 Parameter 4xx overview________________________________________________________________24
5.8.2 Proportional control (proportional band or switching differential) _________________________________24
5.8.3 Integral control (integral time) ___________________________________________________________24
5.8.4 On/Off control________________________________________________________________________25
5.8.5 3-position control _____________________________________________________________________25
5.8.6 Modulating control ____________________________________________________________________25
5.8.7 Graphics for modulating and 3-position control ______________________________________________25
5.8.8 On/Off control for 4-pipe application heating and cooling mode__________________________________26
5.8.9 Modulating control for 4-pipe application heating and cooling mode ______________________________26
5.8.10 Analog fan control in automatic mode (on/off control) _________________________________________27
5.8.11 Analog fan control for modulating and 3-position valve ________________________________________27
5.8.12 3-stage fan control in automatic mode (Modulating valve)______________________________________27
5.9 Temperature and digital inputs ______________________________________________________________28
5.9.1 Parameter P5xx overview _______________________________________________________________28
5.9.2 P500/502: 2 = Heat/cool changeover or floor temperature sensor (NTC or DI)______________________28
5.9.3 P500/502: 3/4 = Occupation sensor_______________________________________________________29
5.9.4 P500: 5 = Door switch (DI) and P502: 3 or 4 = Occupation sensor (DI) ___________________________29
5.9.5 P500/502: 7 = Dew point sensor _________________________________________________________29
5.9.6 P500/502 digital input assignment ________________________________________________________29
5.10 Load and store default settings______________________________________________________________30
5.10.1 With user interface ____________________________________________________________________30
5.10.2 With Modbus_________________________________________________________________________30
5.1 Parameter usage
5.1.1 Parameter number, resolution and data format
Parameter number and Modbus data address are the same. They are listed in column “Par/Addr” as decimal number.
E.g. P001 is parameter 001 and has Modbus data address 1.
All temperature related parameters are given in °C for Modbus. Only in the user interface values can be shown in °F.
Parameters without multiplier have a resolution of 1. Parameters with multiplier 10 have a resolution of 0.1.
For example, the default value of the Comfort temperature set point (P300) is 20.0°C and the value read via Modbus is
200 (because multiplier 10 is used for P300).
The multiplier is only used for Modbus data access. On the user interface, the values are displayed in normal resolution.
Parameter with values below 0 (zero) are given as signed integer values.