TECHNICAL DATA
Air Velocity
Measurement range 0...5 m/s (0...1000 ft/min)
0...10 m/s (0...2000 ft/min)
0...15 m/s (0...3000 ft/min)
0...20 m/s (0...4000 ft/min)
Accuracy1) ±(0.2 m/s / 40 ft/min + 3 % of mv): 0.5...5 m/s (100...1000 ft/min)
at 20 °C (68 °F) / 45 % RH and 1013 hPa (14.7 psi) ±(0.3 m/s / 60 ft/min + 4 % of mv): 1... 10 m/s (200...2000 ft/min)
±(0.35 m/s / 70 ft/min + 5 % of mv): 1... 15 m/s (200...3000 ft/min)
mv = measured value ±(0.4 m/s / 80 ft/min + 6 % of mv): 1... 20 m/s (200...4000 ft/min)
Analogue output signal 0 - 1 / 5 / 10 V2),max. 1 mA
Digital interface RS485 with Modbus RTU protocol (EE671 = 1 unit load)
Response time τ90, typ. 4 s
General
Supply voltage (Class III) 10 - 29 V DC
Current consumption, max. 50 mA at 20 m/s (4000 ft/min)
Connection Cable 0.5 m (1.6 ft) / 2 m (6.6 ft) cable, PVC, 5x0.25 mm² (AWG 23) with ferrules
Plug M12 connector, 5-pin
Electromagnetic compatibility3) EN 61326-1 EN 61326-2-3 Industrial Enviroment
FCC Part15 Class A ICES-003 Class A
Material / protection rating Polycarbonate / IP50 (probe head); IP54 (enclosure)
Temperature range Operation -20...60 °C (-4...140 °F)
Storage -30...60 °C (-22...140 °F)
Humidity range 5...95 % RH (non-condensing)
1) The accuracy statement includes the uncertainty of the factory calibration with an enhancement factor k=2 (2-fold standard deviation). The tolerance was calculated in
accordance with EA-4/02 following the GUM (Guide to the Expression of Uncertainty in Measurement).
2) 0 - 10 V version only with supply voltage ≥ 15 V
3) The EE671 is not short-circuit-proof and not surge-proof (ESD-sensitive device).
SCOPE OF SUPPLY
• EE671 sensor according to ordering guide
• Protection cap
• Mounting flange
• Quick guide
MODBUS RTU
The EE671 air flow probe represents 1 unit load in a Modbus RTU network. For Modbus protocol settings see Modbus Application
Note AN0103 (www.epluse.com/ee671).
Factory settings: Modbus address 238, Baud rate 9 600, even parity, 1 stop bit. The Modbus address can be customised in the
register 0x00 (value margin 1 - 247 permitted). Selectable Baud rates are 9 600, 19 200 and 38 400, parity may be even, odd or none.
Device address, Baud rate and parity can be set via:
1. PCS10 Product Configuration Software and the appropriate configuration cable HA011018.
The PCS10 can be downloaded free of charge from www.epluse.com/pcs.
2. Modbus protocol in the register 60001 (0x00) and 60002 (0x01).
Measured value Unit Scaling Type Register [DEC] Protocol address [HEX]
Read registers (function code 0x03 / 0x04)
Serial number ASCII 0001 0x00
Software version Binary 0009 0x08
Sensor name ASCII 0010 0x09
Temperature °C 32 bit float 1003 0026 0x3EA 0x19
Temperature °F 32 bit float 1005 0028 0x3EC 0x1B
Temperature K 32 bit float 1009 0030 0x3F0 0x1D
Air velocity m/s 32 bit float 1041 0032 0x410 0x1F
Air velocity ft/min 32 bit float 1043 0034 0x412 0x21
Temperature °C x 100 x 100 16 bit integer 4002 0046 0xFA1 0x2D
Temperature °F x 50 x 100 16 bit integer 4003 0047 0xFA2 0x2E
Temperature K x 50 x 100 16 bit integer 4005 0048 0xFA4 0x2F
Air velocity m/s x 100 x 100 16 bit integer 4021 0049 0xFB4 0x30
Air velocity ft/min x 1 x 10 16 bit integer 4022 0050 0xFB5 0x31
Write registers (function code 0x06)
Modbus address 0001 0x00
Communication parameters 0002 0x01
1)
2) 3)
1) Please observe correct scaling for used registers
2) Measured values available in both registers
3) Registers in right column not intended for new design (0026...0050 / 0x19...0x31)
2) 3)
}
left column E+E standard registers, right column legacy registers
2
2) 3)