EUCHNER CE Series User manual

EN
Operating Instructions
MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...

Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
2(Translation of the original operating instructions) 2121341-06-11/20
Contents
1. About this document............................................................................................. 3
1.1. Scope............................................................................................................................................3
1.2. Target group ..................................................................................................................................3
1.3. Key to symbols...............................................................................................................................3
1.4. Supplementary documents ..............................................................................................................3
2. Introduction.......................................................................................................... 4
3. Electrical connections........................................................................................... 4
4. Layout of the protocol data packet........................................................................ 5
4.1. Input structure................................................................................................................................7
4.2. Output structure .............................................................................................................................8
4.3. Configuration of the input and output structure................................................................................11
4.4. Input status on the SPM modules ...................................................................................................12
5. Diagnostics ........................................................................................................ 13
5.1. “I/O index” field ............................................................................................................................13
5.2. “Diagnostic code” field ..................................................................................................................14
5.3. Signals and pin assignment ...........................................................................................................15
5.4. Module CANopen CE-CO................................................................................................................15
5.5. Module DeviceNet CE-DN ..............................................................................................................16
5.6. Module PROFIBUS CE-PR...............................................................................................................17
5.7. Module EtherCAT (CE-EC) ..............................................................................................................17
5.8. Module EtherNet/IP CE-EI ..............................................................................................................18
5.9. Module EtherNet/IP CE-EI2 ............................................................................................................18
5.10. Module PROFINET CE-PN...............................................................................................................19
5.11. Module Modbus TCP/IP CE-MT.......................................................................................................19
5.12. Module Modbus RTU CE-MR...........................................................................................................20
5.13. Module PROFINET CE-US...............................................................................................................20
6. Fault diagnostics ................................................................................................ 21
7. Example diagnostics........................................................................................... 22
7.1. Example 1....................................................................................................................................22
7.2. Example 2....................................................................................................................................22
7.3. Example 3....................................................................................................................................23
8. “Bus Congurator” user interface........................................................................ 24
8.1. Graphic user interface...................................................................................................................25
8.2. Example EUCHNER Safety Designer configuration ...........................................................................28

3
2121341-06-11/20 (Translation of the original operating instructions)
Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
EN
1. About this document
1.1. Scope
These operating instructions are valid for FIELDBUS MODULES CE-... MSC. These operating instructions and any brief
instructions enclosed form the complete user information for your device.
1.2. Target group
Design engineers and installation planners for safety devices on machines, as well as setup and servicing staff possessing
special expertise in handling safety components.
1.3. Key to symbols
Symbol/depiction Meaning
Printed document
Internet
www Document is available for download at www.euchner.com
DANGER
WARNING
CAUTION
Safety precautions
Danger of death or severe injuries
Warning about possible injuries
Caution slight injuries possible
NOTICE
Important!
Notice about possible device damage
Important information
Tip! Useful information
FW < 2.0
Fieldbus module firmware version < 2.0
FW ≥ 2.0
Fieldbus module firmware version ≥ 2.0
1.4. Supplementary documents
The overall documentation for this device consists of the following documents:
Document title
(document number)
Contents
Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
(2121341) This document
Internet
www
Possibly brief instructions enclosed Item-specific information about deviations or additions
Important!
Internet
www
Always read all documents to gain a complete overview of safe installation, setup and use of the
device. The documents can be downloaded from www.euchner.com. For this purpose enter the doc.
no. in the search box.

Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
4(Translation of the original operating instructions) 2121341-06-11/20
2. Introduction
The operation of the fieldbus modules in the series MSC is described in this technical data sheet:
CE-PR (PROFIBUS DP-V1), CE-DN (DeviceNet), CE-CO (CANOpen), CE-EC (ETHERCAT), CE-EI (ETHERNET/IP),
CE-EI2 (Ethernet I/O - 2 PORT), CE-PN (PROFINET), CE-MT (Modbus TCP), CE-MR (Modbus RTU), CE-US (USB).
3. Electrical connections
Each module has four connections (Figure 1):
1. MSCB plug connector, 5-pin to the MSC system
2. USB Mini-B plug connector to the PC
3. BUS plug connector to the fieldbus (not available on CE-US)
4. Front connection power supply
Terminal block (side A – top)
Terminal Signal
1 24 VDC ± 20%
2 -
3 -
4 GND
Table 1: Terminal assignment
WARNING
ÌInstall safety modules in a control cabinet that meets degree of protection IP54 as a minimum.
ÌThe power supply for the modules must be 24VDC ± 20% (PELV, as per EN 60204-1).
ÌMSC is not allowed to be used to supply external devices.
ÌThe same ground connection (0VDC) is to be used for all system components.
Seite A
Seite B
Etikett
Technische
Daten
Seite A
Seite B
Klemmen-
leiste
Seite B Seite A
Haken MSCB Steckverbinder 5-pol.
USB Mini-B-Steckverbinder BUS-Steckverbinder
Figure 1: Connection overview

5
2121341-06-11/20 (Translation of the original operating instructions)
Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
EN
4. Layout of the protocol data packet
The fieldbus module transmits the system status as well as the status and diagnostic elements for all inputs/outputs that
are configured in the MSC system, and makes it possible to read up to 32 separate fieldbus inputs.
The input and output structures are described in chapters 4.1 and 4.2.
The input structure consists of up to four bytes that represent the fieldbus inputs. The number of input bytes depends on
the firmware version of the fieldbus module, see Table 2.
Fieldbus module rmware version Size of input structure
< 2.0 1 byte (8 fieldbus inputs)
≥ 2.0 4 byte (32 fieldbus inputs)
Table 2: Fieldbus input structure
FW ≥ 2.0
The base unit MSC-CB can process only 8 fieldbus inputs, which is why only the first byte in the input
structure is used.
FW < 2.0 The base unit MSC-CB-S can process up to 32 fieldbus inputs, but only the first byte is transferred due
to the limitation of the input structure.
FW ≥ 2.0
The output structure comprises:
Ìone status byte,
Ìone reserved byte,
Ì16 bytes for the status of the inputs,
Ì4 bytes for the feedback of the fieldbus inputs,
Ì4 bytes for the status of the fieldbus outputs,
Ì4 bytes for the status of the safe outputs,
Ì64 bytes reserved for analog data that are not available in the current EUCHNER portfolio,
Ì64 bytes for diagnoses
FW < 2.0
The output structure comprises:
Ìone status byte,
Ìa variable number of bytes for the status of the inputs (max. 16 bytes),
Ìone byte for the feedback of the fieldbus inputs,
Ìtwo bytes for the status of the fieldbus outputs,
Ìa variable number of bytes for the status of the safe outputs (max. 2 bytes),
Ìtwo bytes for diagnoses
The system status is indicated by one byte:
ÌBit 0 indicates whether the MSC system is online or offline
ÌBit 1 indicates whether diagnostic information is available
ÌBit 2 indicates whether there is an error in the MSC system (only firmware version ≥ 2.0)
Each input and each output (OSSD) that is configured in the MSC system is linked to two information elements: Status and
Diagnostics.
Status is a binary value, 0 or 1, Diagnostics is a code for the indication of the IO state, which can be in correct working
order, or which can be indicative of a problem on the I/O.
Each module with inputs has a number of bits that corresponds to the number of inputs present. For this reason, the modules
MSC-CB, MSC-CB-S, FI8, FI8FO2 and FI8FO4S are linked to one byte (8 bits) and the modules FI16 and FM4 to two bytes
(16 bits) for the input status.
Depending on the type of the respectively installed modules, the position of the inputs varies in the following sequence: MSC-
CB/MSC-CB-S, FI8FO2, FI16, FI8, FM4, SPM2, SPM1, SPM0, FI8FO4S. If several modules of the same type are installed,
the order corresponds to the node number.

Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
6(Translation of the original operating instructions) 2121341-06-11/20
All safety outputs are combined in up to 4 bytes, depending on the firmware version of the fieldbus module, see Table 3.
The dual-channel safety outputs are transmitted as a bit via the fieldbus.
Fieldbus module rmware version Size of safety output structure
< 2.0 up to two bytes
≥ 2.0 4 bytes
Table 3: Safety output structure
FW ≥ 2.0 The base unit MSC-CB can process only 16 bits at the safety outputs, which is why only the first two
bytes of the safety output structure are used.
FW < 2.0
The base unit MSC-CB-S can process up to 32 bits at the safety outputs, but only the first 16 bits of
the safety output structure can be transferred due to the limitation of the fieldbus module.
Depending on the type of the respectively installed modules, the position of the safety outputs varies in the following se-
quence: MSC-CB/MSC-CB-S, FI8FO2, AC-FO2, AC-FO4, AZ-FO4, AZ-FO4O8, AH-FO4SO8, FI8FO4S. If several modules of the
same type are installed, the order corresponds to the node number.
A diagnostic element consists of an index of the I/O with a problem and a diagnostic code of the problem.
FW ≥ 2.0
The diagnostic area in the output structure comprises 64 bytes, and the first 23 diagnostic elements
are therefore sent via the fieldbus simultaneously.
FW < 2.0 The diagnostic area in the output structure comprises two bytes, which is why only one diagnostic
element can be sent. With several diagnostic elements, the relative values change every 500ms.
FW < 2.0 Each information set:
ÌInput status
ÌInput diagnostic
ÌFieldbus input status
ÌProbe State
ÌSafety output status
ÌSafety output diagnostic
can be activated/deactivated to control the information and therefore the number of bytes sent to
the fieldbus.
NOTICE
ÌThe input and output structures are represented from the viewpoint of the MSC system.
ÌOn fieldbuses in which the data frames are specified (e.g. PROFIBUS), the input bytes must pre-
cede the output bytes.

7
2121341-06-11/20 (Translation of the original operating instructions)
Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
EN
4.1. Input structure
FW ≥ 2.0
MSC-CB/MSC-CB-S
4 bytes
MSC-CB-S
…
MSC-CB-S
Figure 2: Input structure
FW < 2.0
The input structure size is one byte.

Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
8(Translation of the original operating instructions) 2121341-06-11/20
4.2. Output structure
FW ≥ 2.0
Figure 3: Output structure

9
2121341-06-11/20 (Translation of the original operating instructions)
Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
EN
Key for Figure 3: Output structure
System status (1 byte) B0 = 0: MSC offline
B0 = 1: MSC online
B1 = 1: Diagnostics available
B1 = 0: No diagnostics available
B2 = 1: Error present
B2 = 0: No error
Reserved area (1 byte)
Inputs State (16 bytes) Each module has a number of bits to suit the number of physical inputs.
The following applies:
ÌThe modules MSC-CB/MSC-CB-S, FI8, FI8FO2, FI8FO4S, SPM0, SPM1 and SPM2 occupy 1byte.
ÌThe modules FI16 and FM4 occupy 2 bytes.
ÌThe position of the bytes corresponds to the sequence: MSC-CB/MSC-CB-S, FI8FO2, FI16, FI8, FM4,
SPM2, SPM1, SPM0, FI8FO4S.
ÌIf there are 2 modules of the same type, the order is based on the node number.
Copy of the eldbus inputs
(4 byte)
Used for feedback to the PLC
Status of the eldbus outputs
(FIELDBUS PROBE) (4 bytes)
Each bit represents the status of a fieldbus output in the project plan. Max. 32 fieldbus output bits can be
used.
Status of OSSD/relay (4
bytes)
Each bit represents the status of an OSSD/relay. The position of the bits corresponds to the sequence:
MSC-CB/MSC-CB-S, FI8FO2, AC-FO2, AC-FO4, AZ-FO4, AZ-FO4O8, AH-FO4SO8, FI8FO4S.
Reserved for the status of
the analog inputs (64 bytes)
Diagnostics (64 bytes) Each input or safety output function block is linked to the diagnostic code. The system exports 2 bytes on
the fieldbus for every diagnosis:
ÌThe index for the related I/O
ÌThe diagnostic code
NOTICE
Refer to the “Diagnostics” chapter in this manual for more information about the indices of the I/Os
and the diagnostic codes. If I/O is “OK,” the system exports two bytes to the fieldbus with
Ì0 as index value
ÌDiagnostic code OK (0x80)
NOTICE
If a fieldbus module is used in the MSC system, the EUCHNER Safety Designer report contains a table
with the I/O index for all inputs, the fieldbus input, the fieldbus output (PROBE) and the safety outputs
in the circuit diagram.
The maximum number of inputs that can be administered in an MSC system is 128, which is why the size of the sub-section
“Inputs States” is 16 bytes (128/8).
The maximum number of safety outputs (OSSD/relay) that can be administered in an MSC system is 32, which is why the
size of the sub-section on the OSSD/relay status is 4 bytes (32/8).
FW < 2.0
The scope of the sub-sections “Inputs States” and the OSSD/relay status depends on the hardware
configuration in the MSC system. The sub-section on the OSSD/relay status is limited to 2 bytes here.
The reserved areas are not transmitted, and the Diagnostics sub-section comprises only 2 bytes.
The input and output structures can be graphically depicted in the Bus Configurator – User Interface, see Figure 4.

Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
10 (Translation of the original operating instructions) 2121341-06-11/20
Figure 4: Bus Configurator – User Interface, input and output structures
Key for Figure 4: Bus Congurator – User Interface, input and output structures see key for Figure 3: Output structure

11
2121341-06-11/20 (Translation of the original operating instructions)
Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
EN
4.3. Conguration of the input and output structure
FW < 2.0
The input and output structure can be configured using the software application Bus Configurator
– User Interface. Backward compatibility must be set under Settings -> Activation for this purpose.
Important!
The compatibility mode functions only in combination with a base unit MSC-CB or with a fieldbus module
with a firmware version < 2.0.
Figure 5: Bus Configurator – User Interface, compatibility mode
FW < 2.0
The “Backward Compatibility” tab appears after the compatibility mode is set, see Figure 5. The “I/O
Select” area can be used to define the sub-sections to be exported on the fieldbus. In this way, the
size of the structure and therefore the usage of the internal memory in the PLC can be defined.

Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
12 (Translation of the original operating instructions) 2121341-06-11/20
4.4. Input status on the SPM modules
All modules occupy 4 bits, i.e. bits 0 to 3 or bits 4 to 7 in the “Inputs State” area. The contents of the bits are given in the
tables below.
NOTICE
Check the information in this table in the operating instructions (in the “Function blocks for speed
control” chapter).
STANDSTILL CONTROL
Encoder / encoder + proximity switch Proximity switch
Code Meaning Code Meaning
0 > Standstill + counterclockwise (CCW) 0 > Standstill
2 > Standstill + clockwise (CW) 3 < Standstill
3 < Standstill + counterclockwise (CCW)
5 < Standstill + clockwise (CW)
Table 4: Standstill monitoring
WINDOW SPEED CONTROL
Encoder / encoder + proximity switch Proximity switch
Code Meaning Code Meaning
0 Out of range + counterclockwise (CCW) 0 Out of range
1 Within range + counterclockwise (CCW) 1 Within range
2 Out of range + clockwise (CW)
3 Within range + clockwise (CW)
Table 5: Speed range monitoring
SPEED CONTROL
Encoder / encoder + proximity switch Proximity switch
Code Meaning Code Meaning
0 > Speed limit + counterclockwise (CCW) 0 > Speed limit
1 < Speed limit + counterclockwise (CCW) 1 < Speed limit
2 > Speed limit + clockwise (CW)
3 < Speed limit + clockwise (CW)
Table 6: Speed monitoring
STANDSTILL AND SPEED CONTROL
Encoder / encoder + proximity switch Proximity switch
Code Meaning Code Meaning
0 > Standstill > speed limit + counterclockwise (CCW) 0 > Standstill > speed limit
1 > Standstill < speed limit + counterclockwise (CCW) 1 > Standstill < speed limit
2 > Standstill > speed limit + clockwise (CW) 4 < Standstill < speed limit
3 > Standstill < speed limit + clockwise (CW)
4 < Standstill < speed limit + counterclockwise (CCW)
6 < Standstill < speed limit + clockwise (CW)
Table 7: Standstill and speed monitoring

13
2121341-06-11/20 (Translation of the original operating instructions)
Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
EN
5. Diagnostics
Each input and each safety output is linked to a relative diagnostic code.
If the I/O is connected correctly, the system exports 2 bytes to the fieldbus:
Ì0 as index value
ÌDiagnostic code OK (0x80)
If there is a problem on the I/O, the system sends two bytes to the fieldbus with:
ÌThe index for the related I/O
ÌThe relative diagnostic code
5.1. “I/O index” eld
This field indicates the number of the I/O with the diagnostic code that is not OK. The area of the I/O index depends on the
base unit used. The possible values are shown in Table 8.
Signal type I/O index
MSC-CB MSC-CB-S
Input 1–128 1–128
Output 192–255 1–32
Table 8: “I/O index” field
I/O index
Figure 6: I/O index

Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
14 (Translation of the original operating instructions) 2121341-06-11/20
5.2. “Diagnostic code” eld
The diagnostics for the I/O are displayed in the “Diagnostic code” field. Possible values for this value are shown in Table 9
and Table 10.
Input diagnostic
128 (0x80) Input diagnostics OK -
1Not moved from zero Both contacts must switch to the de-energized state
2Simultaneity failed Both contacts must switch to the other state simultaneously
3Simultaneity failed hand1 Incorrect connection of switch 1 for two-hand operation
4Simultaneity failed hand2 Incorrect connection of switch 2 for two-hand operation
7Switch inconsistent Not more than one input is allowed to be set for the selector switch
8Switch disconnected At least one input must be set for the selector switch
10 OUT_TEST error OUT_TEST diagnostics present on this input
11 Second input KO Redundancy check on the input failed
12 OUT_TEST diagnostics OK
13 Output connected to other inputs Test output connected to wrong input
14 Output OK but input connected to 24VDC Input short-circuited
15 Short circuit between photocell test and photocell input Response time of the light barrier too short
16 No response from photocell The test signal on the transmitter for the light barrier is not visible at the receiver
17 Short circuit between photocells The test signal is present on two different light barriers
18 MAT disconnected Mat connected incorrectly
19 Output inconsistent with feedback The test signal on the input is present on more than one OUT_TEST
20 Connection incorrect The test signal is present on more than one input
21 Output stuck The test signal on the input is not present on the OUT_TEST
22 Second OUT_TEST KO Redundancy check on the OUT_TEST failed
23 SPM proximity missing Proximity switch not fitted / proximity switch does not work
24 SPM encoder missing Encoder not fitted / encoder not supplied
25 SPM encoder proximity missing Device connected not correct
26 SPM proximity1 proximity2 missing Both proximity switches must be connected
27 SPM encoder1 encoder2 missing Both encoders must be connected
28 SPM error congruence frequencies Redundancy check on measurement failed
29 SPM encoder supply missing Encoder not supplied correctly
30 SPM encoder fault Encoder error
133 (0x85) 1) TWO-HAND simultaneity failed Two-hand control simultaneity infringed
134 (0x86) 1) Not started Start check failed
137 (0x89) 1) Waiting for restart The input has been reset manually and not restarted
1) The diagnostic codes 133, 134 and 137 do not cause a visual error message on the LED on the MSC system.
Table 9: “Input diagnostic” field
OSSD diagnostics
0OSSD DIAGNOSTICS OK OSSD diagnostics OK
1ENABLE MISSING No enable
2WAITING FOR RESTART OSSD Waiting for restart OSSD
3FEEDBACK K1/K2 MISSING No feedback K1/K2
4WAITING FOR OTHER MICRO Redundancy check on OSSD failed
5OSSD power supply missing No OSSD supply
6Exceeded maximum time restart Time for restart exceeded
7External feedback K1 K2 not congruent CAT 2 Feedback error on using AZ-FO4/AZ-FO4O8 in CAT2 configuration
8Waiting for external feedback K1 K2 Waiting for feedback
9OSSD output overload Overload at OSSD output
10 OSSD with load set to 24V OSSD with set load of 24 V
Table 10: “OSSD diagnostics” field

15
2121341-06-11/20 (Translation of the original operating instructions)
Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
EN
5.3. Signals and pin assignment
MEANING
LED
ON
GREEN
RUN
GREEN
IN FAIL
RED
EXT FAIL
RED
LED1
RED/GREEN
LED2
RED/GREEN
Switching on – booting ON ON ON ON ON ON
Waiting for configuration from MSC-CB ON OFF OFF OFF OFF OFF
Configuration received from MSC-CB ON ON OFF OFF See tables for the individual modules
Table 11: Initial/dynamic view
5.4. Module CANopen CE-CO
DB9 male plug
(view on front)
PIN SIGNAL
1 -
2 CAN_L
3 CAN_GND
4 -
5 CAN_SHIELD
6 -
7 CAN_H
8 -
9 -
Housing CAN_SHIELD
OPR LED
STATUS INDICATION DESCRIPTION
GREEN OPERATIONAL OPERATIONAL state
GREEN flashing slowly PRE-OPERATIONAL PRE-OPERATIONAL state
GREEN 1 flashing STOPPED STOPPED state
GREEN flashing quickly Autobaud Baud rate detection
RED EXCEPTION EXCEPTION state
ERR LED
STATUS INDICATION DESCRIPTION
OFF - Normal operation
RED 1 flashing Warning level A bus error counter has reached the
warning level
RED flashing quickly LSS LSS operation ready
RED 2 flashing Event Control Node guarding (NMT master or slave) or
heartbeat (user) detected
RED Lack of BUS BUS is not working

Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
16 (Translation of the original operating instructions) 2121341-06-11/20
5.5. Module DeviceNet CE-DN
(view on front)
PIN SIGNAL DESCRIPTION
1 V– Power supply
2 CAN_L CAN bus cable (LOW)
3 SHIELD Shielding
4 CAN_H CAN bus cable (HIGH)
5 V+ Power supply
NET LED
STATUS INDICATION DESCRIPTION
GREEN On-line connected One or more connections made
GREEN flashing (1 Hz) On-line not connected No connections made
RED Critical connection error CE-DN communication not possible
RED flashing (1 Hz) Timeout of 1 or more
connection
One or more I/O devices have timed out
GREEN/RED alternately TEST CE-DN check in progress
STS LED
STATUS INDICATION DESCRIPTION
GREEN - Normal operation
GREEN flashing (1 Hz) Pending Configuration incomplete, CE-DN waiting
for activation
RED Fatal error One or more unrecoverable errors
detected
RED flashing (1 Hz) Error One or more recoverable errors de-
tected
GREEN/RED alternately TEST CE-DN check in progress

17
2121341-06-11/20 (Translation of the original operating instructions)
Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
EN
5.6. Module PROFIBUS CE-PR
DB9 female plug
(view on front)
PIN SIGNAL DESCRIPTION
1 -
2 -
3 B-line Positive RS485 RxD/TxD
4 RTS Request to send
5 GND bus 0VDC (isolated)
6 5V +5VDC (insulated/short circuit-proof)
7 - -
8 A-line Negative RS485 RxD/TxD
9 - -
Housing Shielding Connected internally to protective earth
(acc. to PROFIBUS standard)
MODE LED
STATUS INDICATION DESCRIPTION
GREEN On-line Data exchange
GREEN flashing On-line AVAILABLE
RED flashing
(1 flash)
Parameterization error See IEC 61158-6
RED flashing
(2 flashes)
PROFIBUS
configuration error
Configuration data for MASTER or CE-PR
incorrect
STS LED
STATUS INDICATION DESCRIPTION
OFF CE-PR not initialized SETUP STATE or NW_INIT
GREEN Initialized End of initialization NW_INIT
GREEN flashing Initialized with diagnostic
active
EXTENDED DIAGNOSTIC bit set
RED Exception error EXCEPTION STATE
5.7. Module EtherCAT (CE-EC)
STS LED
STATUS INDICATION DESCRIPTION
OFF INIT INITIALIZATION or no voltage
GREEN OPERATIONAL OPERATIONAL status
GREEN flashing PRE-OPERATIONAL PRE-OPERATIONAL status
GREEN one flash SAFE-OPERATIONAL SAFE-OPERATIONAL status
RED (Fatal Event) System inhibited
ERR LED
STATUS INDICATION DESCRIPTION
OFF No error No error or no voltage
RED flashing Configuration not valid Status change requested by master not
possible
RED one flash Unsolicited state change Use of the slave changed the module
status
RED two flashes Watchdog timeout Watchdog timeout in the Sync Manager
RED Controller fault Bus module in EXCEPTION state

Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
18 (Translation of the original operating instructions) 2121341-06-11/20
5.8. Module EtherNet/IP CE-EI
NET LED
STATUS INDICATION/ DESCRIPTION
OFF No voltage or no IP address
GREEN Online, connected
GREEN flashing Online, not connected
RED Duplicate IP address
RED flashing Connection timeout
STS LED
STATUS INDICATION DESCRIPTION
OFF No power -
Green RUN state -
GREEN flashing Not configured -
RED Fatal error One or more unrecoverable errors
detected
RED flashing Error One or more recoverable errors
detected
5.9. Module EtherNet/IP CE-EI2
NET LED
STATUS INDICATION/ DESCRIPTION
OFF No voltage or no IP address
GREEN Online, connected
GREEN flashing Online, not connected
RED Duplicate IP address
RED flashing Connection timeout
STS LED
STATUS INDICATION DESCRIPTION
OFF No power -
Green RUN state -
GREEN flashing Not configured -
RED Fatal error One or more unrecoverable errors
detected
RED flashing Error One or more recoverable errors
detected

19
2121341-06-11/20 (Translation of the original operating instructions)
Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
EN
5.10. Module PROFINET CE-PN
NET LED
STATUS INDICATION DESCRIPTION
OFF Offline No voltage
No connection to I/O control system
GREEN Online (Run) Connection to
I/O control system established
I/O control system RUN state
GREEN one flash Online (Stop) Connection to
I/O control system established
I/O control system STOP state
GREEN flashing Blink Identification of the network node
RED Fatal event Severe internal error
(in combination with RED STS)
RED one flash Station name error Station name not configured
RED two flashes IP address error IP address not configured
RED three flashes Configuration error Error during identification
STS LED
STATUS INDICATION DESCRIPTION
OFF Not initialized -
GREEN Normal operation -
GREEN one flash Diagnostic event -
RED Exception /Fatal event Module in the EXCEPTION/
severe internal error state
(in combination with RED NET)
5.11. Module Modbus TCP/IP CE-MT
NET LED
STATUS INDICATION/ DESCRIPTION
OFF No voltage or no IP address
GREEN Module in the active process or on standby
GREEN flashing Waiting for connection
RED Duplicate IP address or unrecoverable error
RED flashing Timeout for active process
STS LED
STATUS INDICATION DESCRIPTION
OFF No power -
Green RUN state Normal operation
RED Fatal error ÌSerious error;
Ìmodule in the EXCEPTION state (or
serious exception error)
RED flashing Error ÌMinor errors in the diagnostic object
ÌIP conflict

Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
20 (Translation of the original operating instructions) 2121341-06-11/20
5.12. Module Modbus RTU CE-MR
DB9 female plug
(view on front)
PIN DIRECTION SIGNAL DESCRIPTION
1 - GND Power supply 0V DC
2 OUT 5V Power supply 5V DC
3 IN PMC For RS-232 connect to pin 2.
Not connected for RS-485.
4 - -
5 Bidirectional B-line RS-485 B-line
6 - - -
7 IN Rx Receive RS-232 data
8 OUT Tx Send RS-232 data
9 Bidirectional A-line RS-485 A-line
Housing - PE Earth conductor
COM LED
STATUS INDICATION DESCRIPTION
OFF No power or no data exchange
YELLOW Frame reception or transmission Data exchange
RED Fatal Error One or more unrecoverable errors
detected
STS LED
STATUS INDICATION DESCRIPTION
OFF Initializing or no power
GREEN Module initialized
RED Fatal Error One or more unrecoverable errors
detected
RED one flash Communication fault or configura-
tion error
ÌInvalid setting in network configura-
tion or
ÌSetting in the network configuration
has been changed during operation
RED two flashes Application diagnostics available
5.13. Module PROFINET CE-US
CONNECT LED
STATUS INDICATION DESCRIPTION
GREEN USB connected Module connected to PC via USB
OFF USB not connected Module not connected
This manual suits for next models
10
Table of contents
Other EUCHNER Control System manuals