Ever SPECLINE PRO 700 User manual


Instruction manual for SPECLINE PRO 700 series power supply units
2016-01-18 03:29
Technical Service, tel.: +48 61 6500 400
www.ever.eu
2
TABLE OF CONTENTS
TABLE OF CONTENTS...................................................................................................................................... 2
INTRODUCTION................................................................................................................................................. 3
GENERAL FEATURES OF THE UPS UNIT ................................................................................................... 4
SAFETY INSTRUCTIONS AND RECOMMENDATIONS ............................................................................ 5
UPS DESCRIPTION AND INSTALLATION ................................................................................................. 10
FRONT PANEL............................................................................................................................................... 10
CONNECTION PANEL –POWER SUPPLY UNIT...................................................................................... 11
CONNECTION PANEL –BATTERY MODULE.......................................................................................... 11
UNPACKING .................................................................................................................................................. 11
SELECTING THE POINT OF INSTALLATION........................................................................................... 11
FIRST START-UP........................................................................................................................................... 12
SWITCHING THE POWER SUPPLY UNIT ON WITHOUT
A MAINS CONNECTION –“COLD START” .............................................................................................. 13
CONNECTING BATTERY MODULE........................................................................................................... 14
DESCRIPTION OF OPERATION OF THE UPS........................................................................................... 15
GENERAL INFORMATION .......................................................................................................................... 15
PROTECTION DEVICES INCORPORATED IN THE POWER SUPPLY UNIT......................................... 16
COMMENTS REGARDING OPERATION.................................................................................................... 17
TECHNICAL PARAMETERS.......................................................................................................................... 19
INFORMATION ON LEGAL PROVISIONS AND THE GUARANTEE.................................................... 21
DECLARATION OF CONFORMITY ............................................................................................................ 21
GUARANTEE ................................................................................................................................................. 21

Instruction manual for SPECLINE PRO 700 series power supply units
3
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-01-18 03:29
INTRODUCTION
Thank you for purchasing the EVER SPECLINE UPS power supply unit. It
belongs to our most modern, state-of-the-art series of technologically advanced
power supply units, which is primarily intended for securing the uninterrupted
operation of central heating boilers, fireplaces with water jackets, pumps, and solar
systems. The installation of a unit from this series guarantees correct operation for
many hours in the event of a power outage, thanks to the series connection of battery
module modules. In battery operation mode, the Clear Digital Sinus (CDS) system
enables the equipment to generate a sinusoidal waveform at output.
Specline series UPS units have been designed in such a way as to best meet all of
your expectations regarding protection against the consequences of power outages.
The power supply units are manufactured in Poland, in full compliance with the
requirements introduced for the CE mark.

Instruction manual for SPECLINE PRO 700 series power supply units
2016-01-18 03:29
Technical Service, tel.: +48 61 6500 400
www.ever.eu
4
GENERAL FEATURES OF THE UPS UNIT
The SPECLINE UPS units are designed to work with equipment supplied from ~ 230
VAC single-phase electric power mains. When in back-up mode, they output sine
wave voltage. This greatly enhances the list of tolerated voltages when compared to
UPS units with approximated sine wave. This series can provide energy for
practically any device whose power rating is not greater than the UPS unit’s power
rating. SPECLINE 700 units will not switch off automatically, even if no devices are
connected to their output sockets, which means they can be used with any low
power devices. Only the max power is limited and if the UPS is overloaded, it will
generate a visual and sound alarm.
Apart from excellent performance and reliability, SPECLINE 700 UPS units feature
these great advantages:
the CLEAR DIGITAL SINUS system generates an input voltage with a perfect
sinusoidal shape. This solution offers more opportunities to connect devices that
are sensitive to the supply voltage waveform, e.g.: laboratory equipment,
telecommunication devices;
synchronisation with the mains;
“cold start” –the unit can be started without being connected to the mains;
discharged battery sound indication;
intelligent charging method Cool Battery Charging (CBC), which extends
battery life - a novel charging method using the components of the internal
inverter;
microprocessor control of all parameters;
overload resistance;
short circuit protection;
system of passive mains filters;
enclosed batteries with a combined capacity of 14 Ah;
possibility of connecting up to three battery module or a car battery;
convenient and universal method of cable connection;
24 month guarantee

Instruction manual for SPECLINE PRO 700 series power supply units
5
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-01-18 03:29
SAFETY INSTRUCTIONS AND RECOMMENDATIONS
A) General remarks
CAUTION! Before starting the execution of procedures described herein,
please read the general safety instructions (and also instructions in this
document), OHS information, environmental protection information and
legal regulations; please observe information and recommendations
found in these documents.
CAUTION! It is strictly forbidden for the user to perform any repair
works, as this would constitute a threat to health and/or life. Any repairs
and replacement of batteries should be conducted only by qualified
service technicians properly authorized pursuant to the valid legal
regulations.
CAUTION! The appliance should be operated and stored in conditions
concordant with those set in the specification (technical documentation).
CAUTION! The device is completely disconnected from the mains only
when the power lead is removed from the mains socket (the plug is
removed from the mains socket).
CAUTION! The appliance is equipped with an internal power source
(battery) or can operate with a fixed, external source of power (battery
modules). Dangerous voltage may be present at the output terminal,
even if the device is disconnected from the mains.
CAUTION! The user should place warning labels on all primary switch
disconnectors installed far from the UPS, to warn electrical service
technicians that the circuit is powered by a UPS. The following (or
equivalent) text should be placed on such warning labels:
DISCONNECT THE UPS BEFORE STARTING WORK ON THIS CIRCUIT.

Instruction manual for SPECLINE PRO 700 series power supply units
2016-01-18 03:29
Technical Service, tel.: +48 61 6500 400
www.ever.eu
6
CAUTION! Opening the housing may result in electric shock.
CAUTION! Do not touch any electrical connectors and internal metal
elements before disconnecting power.
CAUTION! All openings and spaces facilitating access to the UPS's
electrical connectors must be covered (with relevant covers). Failure to
observe this requirement may result in danger to health or life of people
attempting to touch such connectors or in the damage of the device.
CAUTION! In the event of a short-circuit, serious burns may be caused
by high current.
CAUTION! There are no end-user serviceable parts inside the UPS.
CAUTION! SPECLINE PRO 700 UPS units are not intended for use
directly with medical equipment, life support systems or equipment that
may affect health.
B) Installation notes
CAUTION! SPECLINE PRO 700 UPS units may only be installed and
maintained by qualified personnel.
CAUTION! Before installation of the UPS, OHS regulations for working
with electrical equipment with voltage up to 1 kV must be read.
CAUTION! Before connecting cables or making connections in the UPS
or in electrical installations, make sure there is no dangerous voltage on
electrical terminals and cables in the system.
CAUTION! The UPS may only be connected to a ~230 V mains socket
with a grounding connection (a bolt). The building's electrical installation
to which the UPS is connected must feature overload and short-circuit
protection.

Instruction manual for SPECLINE PRO 700 series power supply units
7
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-01-18 03:29
CAUTION! Only TN-S or TN-C-S configuration is allowed on the UPS's
input, and only TN-S configuration is allowed on the UPS's output.
CAUTION! No extension cords should be connected to the UPS.
CAUTION! The device must not be installed near flammable materials!
Never perform works alone in conditions dangerous to health and/or life.
Shortly after moving the UPS from cold environment to warm environment,
moisture can condensate. The UPS must be completely dry before installation
and operation. The acclimatization time should be at least 2 hours.
UPS units and battery modules must not be installed in humid environment.
UPS units and battery modules must not be installed in places where they would
be subject to direct sunlight or near sources of heat.
Ventilation openings in the UPS housing must not be blocked - observe distances
to ventilation openings specified in the manual.
Before connecting the device, the technical condition of the connectors, sockets
and cables, and of the appliance itself, must be checked.
The device must be connected to a power circuit (mains socket) with three
terminals (phase, neutral and grounding), including a PE grounding conductor.
Failure to observe this requirement may result in electric shock.
To reduce the risk of electric shock (in case the grounding cannot be checked),
the device must be disconnected from the mains before installation or connecting
to other equipment - the power lead may only be connected again after making all
required connections.
A device powered through a lead with a plug has a grounding conductor that
carries away the leakage current from the receivers. The leakage currents of all
receivers connected to the UPS's output are summed in the UPS's power lead.
The summary leakage current may trigger protective devices (RCD) and result in
disconnecting power from the receivers.
When connecting and disconnecting signal cables, all activities should be
performed with one hand only (if feasible), in order to avoid electric shock from
touching two surfaces with various electrical potentials.

Instruction manual for SPECLINE PRO 700 series power supply units
2016-01-18 03:29
Technical Service, tel.: +48 61 6500 400
www.ever.eu
8
Leads connected to the UPS's output should not be longer than 10 m, in order to
maintain conformance with the EMC directive for products sold in Europe.
Connecting leads should be placed so that people walking over them will not step
or trip on them.
To limit the risk of fire, connections should only be made to circuits (electrical
systems) whose rating is adequate for the connected loads, with properly selected
overcurrent protection. Additionally, the breaker should feature at least 3 mm
insulating air gap.
C) UPS operation remarks
OHS regulations and guidelines specified in the device's manual must be
observed when handling and operating the UPS.
The instructions must be executed step by step. If any problems emerge when
executing the instructions given in this document, please contact EVER service
support (www.ever.eu).
Do not disconnect the grounding at the UPS or in the building's electrical system
terminals, as this will remove the UPS's protective grounding.
There may be voltage on the UPS's output terminals, even if the UPS is
disconnected from the building's electrical system (due to presence of power in
the device's internal batteries).
Liquids and foreign bodies must not penetrate the UPS's housing.
WARNING: This is a C2 category UPS. If installed in residential environment, this
product may interfere with radio signals, which may require additional precautions
to be employed by the user.
D) Maintenance, repair and defects related remarks
Dangerous voltages are present in the UPS. Only qualified service technicians
may perform maintenance works.
CAUTION - risk of electric shock. Even if the device is disconnected from the
mains (terminals of the electrical system), the elements inside the UPS are
connected to the battery, which may lead to danger. Disconnect the battery before
carrying out any service and/or maintenance works. Make sure there is no
dangerous voltage on the DC circuit internal elements.
WARNING: Only properly authorized and qualified service technicians who have
legally required protection gear may replace batteries.

Instruction manual for SPECLINE PRO 700 series power supply units
9
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-01-18 03:29
CAUTION - risk of electric shock. Dangerous voltage may be present between the
battery circuit and the grounding point!
Batteries have high short-circuit current and pose a risk of electric shock. The
following precautions should be taken when working with batteries:
-remove jewelry, watches, rings and other metal items,
-only use tools with insulated handles.
The same number and type of batteries should be used. Using batteries of
improper type may result in explosion.
Dispose of used batteries according to the manual.
WARNING: Disposing of batteries in a fire may result in explosion.
WARNING: Opening or damaging batteries may cause electrolyte to leak;
electrolyte is harmful to skin and eyes, and may also be toxic.
To avoid the danger of fire and damage to the power system, replace broken
fuses with fuses of the same type and parameters.
Disconnect the device from the mains before cleaning. Do not use liquid or
sprayed cleaning agents.
Only qualified service technicians may disassemble UPS units.
E) Transport and packaging remarks
Exercise particular care when transporting the device.
Heavy equipment must be moved by at least two or more persons.
UPS units may be transported only in their original packaging boxes (to protect
the device from shocks and bumps).
The device should be operated and stored in conditions concordant with those set
in the specifications. UPS units must be stored in dry and well ventilated rooms.
If a UPS is to be stored for a longer time, its batteries must be recharged at least
every 6 months. The recharging procedure must be documented.
Check the recharging date. Do not use the UPS if the deadline passed and the
batteries were not recharged. If this occurs, contact service support.

Instruction manual for SPECLINE PRO 700 series power supply units
2016-01-18 03:29
Technical Service, tel.: +48 61 6500 400
www.ever.eu
10
UPS DESCRIPTION AND INSTALLATION
UPS
Battery Module
Fig. 1: View of the front panel
FRONT PANEL
1. The red signalling diode depicts various operating modes of the power supply
unit, symbolically expressed by means of graphical symbols:
a) red diode continuously on: mains power mode.
b) red diode flashing every 2.5 sec.: battery charging mode.
c) red diode flashing and an intermittent sound signal: battery operation
mode; if the signal becomes continuous, this means that the UPS will shut
down in max. 30 sec.
d) red diode flashes rapidly and the sound signal reaches a high pitch: an
overload or short-circuit condition.
2. Main switch –in the event of a power outage or when the power supply unit is
not connected to the mains, it starts the power supply unit in battery operation
mode –cf. also “cold start

Instruction manual for SPECLINE PRO 700 series power supply units
11
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-01-18 03:29
Fig. 2: Connection panel
CONNECTION PANEL –POWER SUPPLY UNIT
AC input fuse socket (mains)1.
DC input fuse socket (battery module)2.
Screw connection terminals of the power supply unit3.
(INPUT, OUTPUT, BATTERY)
CONNECTION PANEL –BATTERY MODULE
DC output fuse socket4.
Screw connection terminals of the battery module5.
Mechanical elements for fastening leads in casing's lead ducts.6.
UNPACKING
Carry out a visual inspection of the power supply unit immediately upon delivery.
Although the product is solidly packaged, the appliance could have been damaged
due to shocks experienced during transport. If any damage is determined, inform the
carrier or seller.
SELECTING THE POINT OF INSTALLATION
When selecting the place and method of installation, you should take into
consideration the high weight of the appliance. The UPS should only be used in
rooms where the dust, temperature, and humidity levels are within the device's
specifications. Appropriate cooling conditions must be ensured for the UPS to work
properly. For this reason, ventilation openings of the UPS must be uncovered at all
times, and the distance between the UPS and other objects should not be less than
15 cm.

Instruction manual for SPECLINE PRO 700 series power supply units
2016-01-18 03:29
Technical Service, tel.: +48 61 6500 400
www.ever.eu
12
The distance between the power supply unit and the battery modules or battery
should be as small as possible. This makes it possible to use shorter connection
cables, thereby helping to limit cable losses.
NOTE! It is forbidden to install the appliance near flammable materials!
Due to the type and placement of fuses in the power supply unit, it is recommended
that the protection systems in the building's electric system be used as one of the
protection levels. This is necessary to ensure the short circuit protection of the
power supply unit. The parameters of the building's electric wiring system
protection should be selected in accordance with the type and magnitude of the load
connected to the wiring system. In extreme cases, different protection parameters of
the building and power supply unit’s systems may cause the former to be activated
more rapidly.
FIRST START-UP
NOTE! Once unpacked, the appliance should be placed in its working location and
connected to the mains. Next, switch the power supply unit on by means of a switch
on the front panel in order to charge the batteries. The batteries will be fully charged
after approx. 10-48 h (depending on their capacity and existing charge); this fact will
be duly signalled by the diode. Now, you can proceed with the remaining installation
steps.
The batteries gain full efficiency after more or less one month of mains
operation and after three cycles of complete discharge and charging.
In order to verify whether the power supply unit is operating correctly, please perform
the following steps:
1. Install the power supply unit in the selected location (e.g. on a wall)
2. Connect the cables to the unit’s connectors and the module
3. Install fuses in the sockets
4. Switch the power supply unit on by pressing the switch on the front panel.
A correctly operating power supply unit, which is connected to a network with the
requisite supply parameters, will signal that it has been switched on by emitting
three sound signals, while the diode will flash three times. Now, you should switch
the protected device on.

Instruction manual for SPECLINE PRO 700 series power supply units
13
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-01-18 03:29
In order to perform a test, switch the mains supply of the UPS off (e.g. on the
building’s switchboard) – the UPS should commence operation in battery mode,
while the protected device should function normally. This operating mode is signalled
by the simultaneous flashing of the red diode and an intermittent sound signal. If after
switching the mains supply on the diode starts to flash rapidly and an intermittent
sound signal is emitted, this means that the load connected to the unit is too great
(the power supply unit will operate for approx. 5 sec. and turn itself off). It will be
necessary to disconnect the excessive load.
5. Reconnect the mains supply –after approx. 3 sec., the diode will return to the
“continuous on” state. Once the unit resumes mains operation, the charging
circuit will top up the batteries; this will be signalled by the diode switching off
briefly, approx. every 2.5 seconds.
Please keep in mind that when the power supply unit is working in battery mode and
the red diode starts to flash and the sound signal becomes continuous, the device
will shut down in no more than 30 sec.
SWITCHING THE POWER SUPPLY UNIT ON WITHOUT A MAINS CONNECTION
–“COLD START”
If the mains voltage parameters are incorrect, the unit can be powered on in battery
operating mode and supply devices until normal voltage resumes, or until the battery
is discharged.
In order to use this function, press the “power on” switch on the front panel. The
powered appliance should be switched on. The power supply unit will emit three
short signals, informing that it is ready for operation, and will then switch to the
battery mode. In the case of EVER SPECLINE PRO 700 units, this is signalled by the
flashing of the red diode on the front panel and an intermittent sound signal.
NOTE! Since boiler control systems have varying start-up power input
requirements, problems may be encountered when attempting to start
the UPS and connected devices. If this is the case, you should try to
"cold start" the unit again.

Instruction manual for SPECLINE PRO 700 series power supply units
2016-01-18 03:29
Technical Service, tel.: +48 61 6500 400
www.ever.eu
14
CONNECTING BATTERY MODULE
You may connect 1-3 42 Ah battery modules to the power supply unit. Connections
should be made with conductors with a minimum section of 2.5 mm2(recommended
4 mm2). Both the module and power supply unit are delivered with fuses.
For transport and connection, the fuses should be removed from their sockets.
They should be installed only after all the connections are made!
Fig 3: Connection system
CAUTION! Connecting excessively high voltage or wrong polarity may
result in the necessity to return the UPS to the service.
CAUTION! A special attention should be paid to the polarity of
connections (plus and minus of the battery with plus and minus of the
UPS, respectively) as the opposite connection may result in damage of
the UPS and a loss of the warranty.

Instruction manual for SPECLINE PRO 700 series power supply units
15
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-01-18 03:29
DESCRIPTION OF OPERATION OF THE UPS
GENERAL INFORMATION
The fundamental role of the power supply unit is to supply connected devices with
electricity from the attached battery modules or an external battery in the event of
irregularities in the mains supply. The time over which electricity is provided by the
unit depends on the capacity of the battery and on the currently connected load. The
power supply unit utilises circuits that detect extreme operating conditions, i.e. an
overload of the converter and a short-circuit at the input. These circuits are active in
the battery operating mode.
When the mains voltage parameters are correct, the power supply unit switches to
mains operation. In this case, prior to reaching the UPS output, the mains voltage is
filtered in the anti-interference circuitry, where additional radio-electric impulses that
degrade the mains power quality are filtered out. If the upper or lower input voltage
limit is exceeded, or if no input voltage is detected, the unit immediately switches to
battery operation. The level of discharge of the battery during battery operation is
indicated by a sound signal. In the final phase of battery discharge, the signal
becomes continuous, thereby indicating that the UPS will switch off shortly (at full
power, this is approx. 30 seconds, while at lower power levels –a somewhat longer
period). Once mains voltage is restored, the power supply unit switches to mains
operation and commences the charging process, which is signalled by the diode.
When the battery is fully charged, the diode is continuously on. However, in order to
ensure permanent readiness, the UPS continues to charge the batteries.
In order to increase the life of the batteries, cyclic charging is used in the UPS.
The UPS employs an innovative charging method, typically reserved for high-end
power supply units (CBC –COOL BATTERY CHARGING), which utilises elements
of the internal converter. In the mains operating mode, this function charges the
batteries, while in battery operation mode it converts the internal energy of the
battery to an alternating voltage that supplies the protected devices.
If you want to turn the power supply unit on without it being connected to the mains,
you can switch it on in battery mode (cf. “cold start”).

Instruction manual for SPECLINE PRO 700 series power supply units
2016-01-18 03:29
Technical Service, tel.: +48 61 6500 400
www.ever.eu
16
PROTECTION DEVICES INCORPORATED IN THE POWER SUPPLY UNIT
Overload protection
The UPS indicates an overload for a load in excess of 110% of the UPS rated power.
This is signalled only in battery mode. The UPS:
switches off after 30 seconds in the range 200-400 W
switches off within 5 seconds above 400 W
The diode on the front panel starts to flash rapidly, while the sound signal becomes
intermittent.
Short circuit protection
The power supply unit is equipped with a fusible cut-out on the mains input and an
electronic fuse on the output. The electronic fuse operates only in battery mode.
Activation of the electronic fuse is indicated by the rapid flashing of the diode. A short
circuit is also signalled by a very quick, intermittent sound. Because the battery is
connected externally (it is not built-in), additional protection devices have been
utilised:
a. Battery overvoltage protection
The power supply unit is protected against the connection of a battery with a voltage
greater than nominal. In this case, the car fusible cut-out will burn out.
b. Protection against an incorrect battery connection
The power supply unit is protected against reverse battery connection.
NOTE! In the event of activation of the overvoltage protection or reverse
battery polarisation, the burn-out of the UNIVAL fuse will be
accompanied by damage to the protective diode. In this case, please
contact the manufacturer’s service department for replacement.
Battery overcurrent protection
The power supply unit is protected against exceeding the maximum battery current
by two protection devices:
- electronic
- car fuse, UNIVAL type, 19 mm, 40 A.

Instruction manual for SPECLINE PRO 700 series power supply units
17
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-01-18 03:29
COMMENTS REGARDING OPERATION
WARNING! EVER SPECLINE PRO 700 power supply units are C2
category appliances. In residential environments, the product may
interfere with radio signals, which may require additional precautions to
be employed by the user.
FUSE REPLACEMENT
In the event of the connection of a device with a power consumption level that
considerably exceeds the nominal value, or a short circuit in the mains socket, the
fuses may burn out (the fuses are located in a holder –cf. connection panel). In order
to replace a fuse, turn the unit off with the switch, disconnect mains power (e.g. at the
building’s switchboard), remove the fuse holder, and install a new fuse with
parameters that are concordant with the specification of the power supply unit. The
set contains one spare mains fuse and one spare battery fuse.
INTERACTION WITH ELECTRICAL GENERATORS
EVER SPECLINE PRO 700 power supply units are VFD-class devices that
synchronise themselves with the mains voltage. The unit has been designed to
tolerate voltage fluctuations in the range of 184-264 V and changes in the frequency
of ±5 Hz in relation to the model frequency of 50 Hz. The generator frequency value
may be variable over time and depends on changes in the load values. If the
generator voltage frequency changes were to exceed this tolerance, the power
supply unit may consider such a frequency value as incorrect and switch to battery
operation.
OUTPUTS
The connectors used in the power supply unit have a maximum current of 40 A.
STORAGE, MAINTENANCE, AND TRANSPORT
The power supply unit should be stored in a cool and dry place, and in its working
position. It is recommended to store battery modules with fully charged batteries:
at a temperature between 0°C ÷ +30°C, the battery should be charged every 6
months;

Instruction manual for SPECLINE PRO 700 series power supply units
2016-01-18 03:29
Technical Service, tel.: +48 61 6500 400
www.ever.eu
18
at a temperature between +30°C ÷ +45°C, the battery should be charged every 3
months.
The appliance should be transported in its original packaging, under conditions
concordant with those set in the product specification. EVER Sp. z o.o. shall not be
liable for mechanical damage arising during the transport of the appliance without its
original packaging.
UTILISATION
The appropriate utilisation of used electric and electronic equipment helps protect
human health and the natural environment against the negative effects brought about
by the presence of hazardous materials and components, and the improper storage
and processing of such equipment.
Act of 29 July 2005, on Waste Electric and Electronic Equipment, Article 22.1, Point
1.2.
The crossed out waste container symbol means that, in the
European Union, a used product should be handed over to a
special waste handling outlet. This concerns both the
appliance itself, and all accessories marked with this symbol.
Such products should not be disposed of together with
unsorted municipal waste.
Method of safe removal of the batteries from the appliance:
The batteries should be removed from the appliance by an authorised service outlet
or by a duly authorised electrician.

Instruction manual for SPECLINE PRO 700 series power supply units
19
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-01-18 03:29
TECHNICAL PARAMETERS
PARAMETERS \ TYPE
SPECLINE PRO 700
Part number
W/SPPRTO-000K70/00
Rated output power (Apparent / Active) 1)
350 VA / 200 W
The maximum output power of 30 s (Apparent /
Active)
700 VA / 400 W
GENERAL DATA AND ENVIRONMENTAL
Topology
VFD (offline)
Number of phases (in/out)
1 / 1
Housing Type
Tower
Operating temperature 2)
0 ÷ +40 °C
Storage temperature
0 ÷ +45 °C
Relative humidity during operation
20 ÷ 80 % (non-condensing)
Relative humidity during storage
20 ÷ 95 % (non-condensing)
Operating elevation 3)
< 1000 m
Protection level
IP20
Environment of installation
Technical rooms / industrial rooms with low level of pollution
Cooling
Gravity
INPUT
Rated input voltage
230 V AC
Input voltage range and tolerance
~ 184 ÷ 264 V ± 2 %
Input voltage rated frequency
50 Hz
Input voltage frequency range and tolerance
45 ÷ 55 Hz ± 1 Hz
Transfer thresholds: Mains –UPS
~ 184 ÷ 264 V ± 2 %
OUTPUT
Rated output voltage
230 V AC
Output voltage range and tolerance - normal
mode
~ 184 ÷ 264 V ± 2 %
Output voltage range and tolerance - battery
mode
~230 V ± 5 %
Shape of output voltage (battery mode /
normal mode)
Sine wave / same as input
Output voltage rated frequency
50 Hz
Output frequency range and tolerance - mains
operation mode
Synchronously
Output frequency range and tolerance - battery
mode
50 Hz ± 1Hz
Output voltage filtering
LC, RFI/EMI filter, varistor TVSS
Transfer thresholds: UPS–Mains
~ 189 V / 259 V ± 2 %
Transfer time to battery mode
< 3 ms
Transfer time to normal mode
0 ms
BATTERIES AND TYPICAL RUNTIME
Internal Batteries
12 V / 7 Ah VRLA
Number of internal batteries
2
Maximum overall internal batteries capacity
14 Ah
External Batteries
6 x 12 V / 7 Ah VRLA
Maximum number of EBMs 42 Ah
3
Backup time - internal batteries
( 100 % / 50 % Pzn)
24 / 55 min
Backup time - internal batteries + 1 EBM
( 100 % / 50 % Pzn)
120 / 290 min
Backup time - internal batteries + 2 EBM
( 100 % / 50 % Pzn)
250 / 560 min
Backup time - internal batteries + 3 EBM
( 100 % / 50 % Pzn)
370 / 800 min
Rated voltage DC circuit
12 V DC
EBM (42 Ah) Maximum charging time - after
discharging at 80 % Pmax*
10 h

Instruction manual for SPECLINE PRO 700 series power supply units
2016-01-18 03:29
Technical Service, tel.: +48 61 6500 400
www.ever.eu
20
PARAMETERS \ TYPE
SPECLINE PRO 700
Part number
W/SPPRTO-000K70/00
Rated output power (Apparent / Active) 1)
350 VA / 200 W
The maximum output power of 30 s (Apparent /
Active)
700 VA / 400 W
MECHANICAL SPECIFICATIONS
Dimensions (H x W x D)
367 x 209 x 125 mm
Net Weight
10,75 kg
Gross Weight
11,15 kg
Transport Dimensions (H x W x D)
150 x 220 x 390 mm
Operating position
Vertical or horizontal
Position in which devices transported
Horizontal
PROTECT
Input over current protection
Short circuit protection - Fuse 5 x 20 mm 5 A / 250 V AC
Surge Protection
Output over current protection
Electronic short-circuit and overload protection
DC over current (external battery input)
Overvoltage Protection and against reverse battery module connection
Battery overcurrent - Automotive Fuse type UNIVAL 19 mm 40 A
ACCESSORY AND EXTRA FUNCTIONS
Power supply connection
screw terminals; max. 4 mm2 (cable)
Output connection (number and type of
sockets )
screw terminals; max. 4 mm2 (cable)
Signalling
Acoustic and optical
CERTIFICATION
Declarations
CE
Standards
PN-EN 62040-1:2009, PN-EN 62040-2:2008
Note: The manufacturer reserves the right to modify the above parameters without prior notification.
* Charging time to 90% battery capacity, following a prior discharge with a load of 80% Pmax (to shut down the UPS).
Notes:
1) For standard operation, the load applied to the output must not exceed 80% of the value in the table. The power margin
is necessary to ensure continuous work of the connected devices in the case of instantaneous surges of the load
2) For UPS with internal batteries 5 ÷ 35 °C. Constant exposure of the battery module to temperatures of +25°C reduces the
battery life.
3) The permitted maximum load of the power supply unit decreases with the height above the sea level above the limit
specified above
Table of contents
Other Ever UPS manuals

Ever
Ever POWERLINE GREEN 33 LITE Instruction sheet

Ever
Ever SPECLINE Pro series User manual

Ever
Ever SINLINE User manual

Ever
Ever POWERLINE RT 1000 User manual

Ever
Ever SPECLINE AVR 700 User manual

Ever
Ever SINLINE XL User manual

Ever
Ever Duo II 350 User manual

Ever
Ever POWERLINE 31 series User manual

Ever
Ever POWERLINE 60-33 User manual

Ever
Ever W/PGRLTO-3310K0/00 User manual
Popular UPS manuals by other brands

Jovyatlas
Jovyatlas Powermaster ? Series operating manual

socomec
socomec Masterys Green Power 10 operating manual

Tescom
Tescom DS300SHA Series user manual

CyberPower
CyberPower Paragon OL2000RMXL2U Specification sheet

Power Solid
Power Solid PS-P0U3KD 8B9K Series user manual

Energenie
Energenie EG-UPS-031 user manual