CONV1-G rev 2.0
Ewimar Sp. z o.o.
www.ewimar.pl
Power sup.
Power sup.
RS485 - A+
RS485 - B-
RS485 - A +
RS485 - B -
GND
GND
Input
110
Term1
Term2
9~24V
RR
B
B
Inside
connection
Link
4. Dip-switch
Dip-switch description:
Baud rate
for RS-485 output
2400baud 4800baud 9600baud 19200baud
DIP 1 OFF ON OFF ON
DIP 2 OFF OFF ON ON
Baud rate
for RS-485 input
2400baud 4800baud 9600baud 19200baud
DIP 3 OFF ON OFF ON
DIP 4 OFF OFF ON ZAŁ
Address change Not active Active
DIP 4 OFF ON
The change of address (increment/decrement) function allows us to keep better compatibility because Pelco-D protocol start
addressing cameras from number 1, but the Pelco-P protocol starts from 0. When converting from Pelco-D to Pelco-P,
address is decreased by 1 and from Pelco-P to Pelco-D address is increased by 1.
Producer: Ewimar Sp. z o.o., ul. Konarskiego 84, 01-355 Warsaw, Poland,
Power: Connect power supply 9~24V DC / AC
Input A, B: Connect PTZ control device
Term1: Termination resistor 120Ωfor RS485 input
Wyjście A, B: Connect to PTZ camera
Term2: Termination resistor 120Ωfor RS485 output
GND: Cable shield
The RS-485 terminals, must be correctly connected to other devices
Ato A and Bto B.
For longer cables of bus, both RS-485 interfaces, should be
included to terminating resistors. This will prevent wave
reflections in cables, which are cause of transmission errors.
Terminating resistors should be connected only in devices, which
are of ends of the bus. Larger number of resistors will cause an
excessive burden of transmission.
Termination resistors are placed in converter. To active it please
make wire connections TERM terminal to A+ terminal – details
on drawing
OFF (up)
ON (down)