Facility Explorer FX Series User manual

Installation Instructions
Issue Date April 9, 2014
© 2014 Johnson Controls, Inc. 1
Part No. 24-10174-34, Rev. C www.johnsoncontrols.com
FX Supervisory Controller LON Card
Installation Instructions
Application
The FX Supervisory Controller LON Option Card
provides LONWORKS® Free Topology Transceiver
(FTT)-10A communications capability to the FX
Supervisory Controllers (FX20, FX30E, FX60, FX60E,
and FX70). See Figure 1.
Up to two LON Option Cards may be installed. If one
LON Option Card is installed, it operates as LON1,
regardless of the slot used. If two LON Option Cards
are installed, LON1 is Option Slot 1 and LON2 is
Option Slot 2 (see Figure 3 for locations of option
slots).
For related information on FX Supervisory Controllers
mounting and wiring, refer to the FX Supervisory
Controllers Installation Instructions
(Part No. 24-10174-77).
FIG:LONOpt
Figure 1: FX20/FX30E/FX60/FX60E LON Card
Figure 2: FX70 LON Card
IMPORTANT: For the FX70, carefully pry up the
shield tab to install the option card under the tab. Do
not install the Option Card in slot 2 with the card
resting on top of the shield tab. Otherwise, an
electrical short or some other issue from misaligned
card header pins may result.
North American Emissions Compliance
United States
This equipment has been tested and found to
comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection
against harmful interference when this equipment is
operated in a commercial environment. This
equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications.
Operation of this equipment in a residential area is
likely to cause harmful interference, in which case
the user will be required to correct the interference
at his/her own expense.
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel
brouilleur du Canada.

2FX Supervisory Controllers LON Card Installation Instructions
Installation
Parts Included
Unpack the LON Option Card and inspect the contents
of the package for damaged or missing components. If
any components are damaged, notify the appropriate
carrier and return them for repair or replacement.
Included in this package are the following items:
•one LON Option Card, along with connector end
plate
•one 2-position terminal plug for wiring to a
LONWORKS Twisted Pair/Free Topology
(TP/FT)-10 network
•FX Supervisory Controller LON Card Installation
Instructions (Part No. 24-10174-34)
Special Tools Needed
The following supplies and tools are required for
installation:
•#2 Phillips screwdriver: used to install the LON
card
•small flat-blade screwdriver: used for making
wiring connections to the LONWORKS network
Safety Precautions
The following information relates to the installation and
startup of the LON Option Card.
!
WARNING:Risk of Electric Shock.
Disconnect power supply before making electrical
connections. Contact with components carrying
hazardous voltage can cause electric shock and
may result in severe personal injury or death.
AVERTISSEMENT: Risque de décharge
électrique Débrancher l'alimentation avant de
réaliser tout branchement électrique. Tout contact
avec des composants conducteurs de tensions
dangereuses risque d'entraîner une décharge
électrique et de provoquer des blessures graves,
voire mortelles
IMPORTANT: Be careful to plug any option card
into its connector properly (pins aligned).
IMPORTANT: Avoid hot plug-in or removal of any
option card from the FX Supervisory Controllers; that
is, do not remove any card with power applied. If the
unit switches to battery operation, wait for all Light
Emitting Diodes (LEDs) to go out.
Mounting
Mount the LON Option Card in either of the option
slots on the FX Supervisory Controller, as available.
Follow these instructions:
1. If a station is running, stop the station using the
platform Application Director view.
2. Remove power from the FX Supervisory
Controller.
3. Remove the FX Supervisory Controller cover or
covers. Press in the four tabs on both ends of the
controller and lift off the cover.
Note: If accessory modules are plugged into
the FX Supervisory Controller, you may need to
slide them away from the unit to access the cover
tabs.
4. If the battery assembly is installed, remove it by
taking out the four screws holding it in place. Set
the screws aside for later.
5. Unplug the battery from the connector on the FX
Supervisory Controller (see Figure 3).
Battery Assembly
(includes cable and
bracket)
Blanking
End Plate Option Slot 1
Area
Option Slot 2
Area
Screws (4)
FX Supervisory
Controller
Figure 3: Removing Battery Assembly
6. Remove the blanking end plate for the slot into
which you are installing the Option Card. Retain
the blanking end plate in case you need to
remove the Option Card at a later date.

FX Supervisory Controllers LON Card Installation Instructions 3
7. Carefully insert the pins of the LON card into the
socket of the appropriate option slot. The
mounting holes on the LON card should line up
with the standoffs on the FX Supervisory
Controller. If they do not, the connector is not
properly aligned. Press until the LON card is
completely seated.
8. Place the custom end plate that came with the
LON card over its connector (see Figure 4).
Insert LON card
into option card slot
carefully with pins aligned.
Fully seat c ard.
Place LON card custom
end plate overend.
FX Supervisory Controller
Battery Connector
Figure 4: Inserting LON Card
9. If installing/replacing the battery and bracket, plug
the battery cable into the battery connector on the
FX Supervisory Controller (see Figure 4 for
location).
10. Set the battery and bracket assembly back over
the option slots, with the mounting holes aligned
with the standoffs.
11. Place the four screws through the battery bracket,
through the end plates, and into the standoffs on
the FX Supervisory Controller (Figure 5). Lightly
tighten these screws with a screwdriver.
FIG:FasnScrws
Lightly tighten the
four screws intothe
standoffs by going
through the battery
bracket and end plates.
Figure 5: Refastening Screws
12. Replace the FX Supervisory Controller cover. If
accessory modules were unplugged, plug them
back into the FX Supervisory Controller as before,
and secure.
13. Restore power to the controller and verify normal
operation.
Wiring
Connect the LONWORKS network communications
wiring to the 2-position connector of the LON Option
Card. Polarity is not a factor with LONWORKS TP/FT
wiring.
Refer to the LONWORKS FTT-10A Free Topology
Transceiver User’s Guide (078-0156-01) for technical
guidelines associated with free topology restrictions.
Refer to the Junction Box and Wiring Guidelines for
Twisted Pair LONWORKS Networks (005-0023-01) for
more detailed information on wiring specifications.
These documents are available on the Echelon® Web
site (www.echelon.com).

4FX Supervisory Controllers LON Card Installation Instructions
Operation
LEDs
Two LEDs are visible on the top of the LON Option
Card. To see them, remove the cover from the FX
Supervisory Controller. The LEDs operate as follows:
•RX (green): Receive—indicates that another
LONWORKS device is transmitting a message.
•TX (yellow): Transmit—indicates that the FX
Supervisory Controller is transmitting a message
on the LONWORKS network.
These LEDs are labeled on the top of the LON card
(see Figure 1).
Repair Information
If the LON Option Card fails to operate within its
specifications, replace the unit. For a replacement
Option Card, contact the nearest Johnson Controls®
representative.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Johnson Controls® is a registered trademark of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2014 Johnson Controls, Inc.
This manual suits for next models
4
Other Facility Explorer Controllers manuals
Popular Controllers manuals by other brands

Mircom
Mircom OpenBAS-HV-NX10 Series installation manual

LSIS
LSIS S100 Series troubleshooting manual

Distech Controls
Distech Controls VA-024ZS Series Hardware installation guide

HP
HP 9000 Series 700 owner's guide

Paradise Datacom
Paradise Datacom ROLA-CHEM Pool Sentry M-3000 Assembly instructions

INSTEON
INSTEON 2475F quick start guide