fafnir VISY-Output 8 Guide

FAFNIR GmbH • Schnackenburgallee 149 c • 22525 Hamburg • Germany • Tel.: +49 / 40 / 39 82 07–0 • Fax: +49 / 40 / 390 63 39
Technical Documentation
VISY-Output 8
8-Channel relay output module
Version: 3
Edition:
2016-09
Art
.no.: 350072

I Table of contents
© Copyright:
Reproduction and translation is only permitted with the written consent of the FAFNIR GmbH.
The FAFNIR GmbH
reserves the right to carry out product alterations without prior notice.

Table of contents II
Table of contents
1. Overview ................................................................................................ 1
2. Installation.............................................................................................. 1
2.1. Safety information..............................................................................................1
2.2. Requirements .....................................................................................................2
2.3. Installation .........................................................................................................2
2.4. Design and construction.....................................................................................2
2.4.1. Device information .............................................................................................2
2.4.2. Connections.......................................................................................................2
2.4.3. Controls.............................................................................................................3
2.4.4. LEDs...................................................................................................................3
2.5. Connection of the power supply.........................................................................3
2.6. Connection of the relay contacts ........................................................................4
2.7. Connection to VISY-Command...........................................................................4
3. Configuration ......................................................................................... 5
3.1. Hold time after communication loss....................................................................5
3.2. Output action after hold time .............................................................................6
3.3. Relay mode ........................................................................................................6
3.4. Relay delay .........................................................................................................7
3.5. Maintenance Mode ............................................................................................7
4. Fault diagnosis ....................................................................................... 7
4.1. Transmit LED (7) / Receive LED (8) .......................................................................7
4.2. Output LEDs (9)..................................................................................................8
4.3. Status LED (10)...................................................................................................8
4.4. Relay LEDs (11)...................................................................................................9
4.5. Operating voltage LED (12).................................................................................9
5. Technical data....................................................................................... 10
6. List of figures........................................................................................ 10
7. List of tables ......................................................................................... 10
8. Annex.................................................................................................... 11
8.1. EU Declaration of Conformity ...........................................................................11

Page 1/11 Overview
1. Overview
VISY-Output 8 is an 8-channel relay output module, installed in a case with the protection
IP66. It connects the VISY-X high-precision tank gauging system to external safety devices
or alarm indicators.
With VISY-Output 8, different alarm conditions detected by the VISY-X system will be
transferred to external devices. As VISY-Input 8 has its own housing it can be installed at
any position where the simplest wiring can be made. To connect to the VISY-X tank
gauging system only a low-cost communication cable has to be laid. Up to eight modules
VISY-Output 8 can be operated simultaneously with the VISY-Command.
2. Installation
2.1. Safety information
When installing VISY-Output 8 following safety instructions should be observed:
•VISY-Output 8 is designed for operation within the VISY-X system only.
•Modifications to the VISY-Output 8 are prohibited without the prior consent of
the manufacturer.
•All installation and maintenance work, with the exception of function testing,
must be carried out with the power disconnected.
•The installation and configuration of the VISY-Output 8 may be carried out only
by expert personnel. Specialised knowledge must be obtained by regular training.
•Operators, installers and service technicians must observe all applicable safety
regulations. This also applies to any local safety and accident prevention regula-
tions which are not stated in this technical documentation.
The safety instructions in this manual are marked as follows:
Failure to observe these safety instructions runs the risk of potential acci-
dents and damage to the VISY-X system.
Useful tips and information in this manual that should be observed are writ-
ten in italics and identified by this symbol.

Installation Page 2/11
2.2. Requirements
To connect the VISY-Output 8 to the VISY-X system an interface card of version VI 4 or
higher must be installed and connected to the communication adapter VISY-ICI 485.
2.3. Installation
The VISY-Output 8 is designed for wall mounting inside a building.
For mounting the casing cover must be removed.
2.4. Design and construction
The following figure shows the position of the connectors, LEDs and controls on the
board of the VISY-Output 8.
Figure 1: VISY-Output 8 Design
2.4.1. Device information
(1) Label with the serial number which uniquely identifies the device.
When configuring with the VISY-Setup software this serial number has to be en-
tered to address the device.
2.4.2. Connections
(2) 24-pin screw terminal for connection to the relay contacts
(3) 3-pin screw terminal for connecting the power supply
(4) 3-pin screw terminal for connecting the communication
1
3
2
7
8
Ser. no.
5
4
6
9
10
11
12

Page 3/11 Installation
2.4.3. Controls
(5) 2-pin plug connector to activate a terminating impedance for the RS-485 inter-
face. Normally, the communication on the RS-485 network should be trouble-
free without activation of the terminating impedance (jumper not plugged in),
because the data rate is comparatively low.
(6) 4-way DIL switch, currently without function.
2.4.4. LEDs
(7) Transmit LED (red)
(8) Receive LED (red)
(9) Output LEDs (red) - one per output
(10) Status LED (yellow)
(11) Relay LEDs (red) - one per relay
(12) Operating voltage LED (green)
2.5. Connection of the power supply
The power supply (230 VAC) has to be a permanent installation. The wires for the power
supply are to be connected to the screw terminals marked with PE, N and L.
Figure 2: Power supply screw terminal
PE
N
L

Installation Page 4/11
2.6. Connection of the relay contacts
The VISY-Output 8 has eight output relays, each with a potential-free changeover con-
tact.
External safety devices or alarm indicators can be connected to the clamps marked with
relay 1 to 8 of the 24-pin screw terminal (see following figure). The VISY-Command alarm
signals can freely be assigned to the relays. Whether the contact shall be used as normally
open (NO) or normally closed (NC) depends on the particular application and the relay
mode (see chapter 3.3).
Figure 3: Relay screw terminal
2.7. Connection to VISY-Command
Up to eight VISY-Output 8 can be operated simultaneously with the VISY-X tank gauging
system. For the connection of VISY-Input 8 a communication adapter VISY-ICI 485 is
required which must be installed inside VISY-Command. The communication between
VISY-ICI 485 and VISY-Output 8 is performed via a galvanically isolated RS485 interface.
The communication line is to be connected to the terminals A, B and GND of the 3-pin
screw terminal.
For the wiring of VISY-Output 8 with VISY-ICI 485 it is recommended using a 3-core cable
with signal ground (GND connection terminal) to increase the noise immunity.
Figure 4: Communication screw terminal
Additional information about the connection of the communication line can be found in
the documentation of VISY-ICI 485, see:
•Technical Documentation VISY-ICI 485, art. no. 207150
NO C NC NO C NC NO C NC NO C NC
Relay 2 Relay 4 Relay 6 Relay 8
Relay 1 Relay 3 Relay 5 Relay 7
GND
A
B

Page 5/11 Configuration
3. Configuration
Further configuration of VISY-Output 8 is done - as usual for the VISY-X system - with the
VISY-Setup configuration software.
If a VISY-Output 8 will be connected to the VISY-X system, the data proto-
col for communication with the VISY-Stick must always be set to “Multi
Probe”
using the VISY-Setup. Due to the shorter communication times, “Multi
Probe 4800 bps” should preferably be used.
Please follow the appropriate instructions in the VISY-Setup instructions.
•Technical Documentation VISY-Setup V4, art. no. 207158
Changing the configuration means to adopt VISY-Output 8 to the requirements of the
special application. The following settings are possible:
(1) Hold time after communication loss
(2) Output action after hold time
(3) Relay mode
(4) Relay delay
After the configuration it should be tested whether the alarm signalling
works as expected.
3.1. Hold time after communication loss
With the hold time it is configured if and when the outputs react after a communication
loss. The hold time can be configured in the range of 0 to 240 minutes.
Hold time = 0 (minutes)
The hold time is deactivated. The outputs keep their current states.
Hold time = 1 - 240 (minutes)
The hold time is set to 1 - 240 minutes. After the hold time is exceeded, the outputs react
as described in the following chapter.

Configuration Page 6/11
3.2. Output action after hold time
This configuration defines how the outputs react after the hold time is exceeded. After
the hold time the outputs can either be activated or deactivated.
If a hold time of "0" is configured, the outputs keep their current states.
The relays act according to the configured relay mode.
3.3. Relay mode
The following relay modes are possible:
Standard mode
In the standard mode, the relay is normally de-energized (passive) and it will be energized
(active) when the corresponding output is activated.
Fail-safe mode
In the fail-safe mode, the relay is normally energized (active) and will be de-energized
(passive), when the corresponding output is activated.
The fail-safe mode provides the advantage that even in case of a failure
in the power supply of the VISY-Output 8 an alarm can be signalled via
de-energized (passive) relays.
The following table shows the state of a relay depending on the configured relay mode
and the state of the associated output.
Relay mode
Output
Relay status
standard
deactivated
de-energized
standard
activated
energized
fail-safe
deactivated
energized
fail-safe
activated
de-energized
Table 1: Relay mode

Page 7/11 Fault diagnosis
3.4. Relay delay
If the relay delay is on, the relay state (de-energized/energized) changes when the event
for the output activation is present for at least 1 minute. The relay delay occurs only upon
activation of an output. Upon deactivation of an output the relay state changes without
delay.
If an output is activated and the relay delay is on, the corresponding output
LED blinks slowly to show the delayed reaction of the relay.
3.5. Maintenance Mode
The maintenance mode is used to deactivate the outputs of the VISY-Output 8 temporari-
ly. This function can for example be used during the configuration to prevent alarms via
the relay contacts caused by incomplete configuration. The maintenance mode is turned
on or off using the VISY-Setup configuration software, as far this function is supported by
the used version. During the maintenance mode, the output LEDs flash rapidly.
The maintenance mode is terminated automatically when VISY-Setup is
closed or the connection between VISY-Setup and the VI interface card is
interrupted.
Before activating the maintenance mode you should be sure about possible
consequences, as active safety devices might be turned off.
4. Fault diagnosis
VISY-Output 8 has several LEDs which help in diagnosing problems. The positions of the
LEDs can be found in the Figure 1.
4.1. Transmit LED (7) / Receive LED (8)
The two red communication LEDs indicate, whether data are received or transmitted from
VISY-Output 8.
Under normal conditions, the communication LEDs should light up
regularly.

Fault diagnosis Page 8/11
4.2. Output LEDs (9)
The eight red output LEDs indicate, whether an output is activated or deactivated. Addi-
tionally these LEDs indicate the active relay delays and the maintenance mode. The fol-
lowing table lists possible states of the output LEDs and explains their meanings.
Output LED
Description
on
output is activated
off
output is deactivated
slow blinking
relay delay
fast flashing
Maintenance Mode
Table 2: Output LEDs
4.3. Status LED (10)
The yellow status LED indicates the state of the communication between the VI interface
card in the VISY-Command and the VISY-Output 8.
The following table lists the possible states of the status LED and explains their meanings.
Status LED Error Description
on
no error
correct data are regularly received
continuous blinking
no communication
no correct data were received since the last
power up
1 x short flashing
interruption of the com-
munication
no correct data were received for more than
1 minute
2 x short flashing
hold time exceeded
no correct data were received for more than
the configured hold time
Table 3: Status LED
Under normal conditions, the status LED should remain illuminated.

Page 9/11 Fault diagnosis
4.4. Relay LEDs (11)
The eight red relay LEDs indicate, whether a relay is energized or de-energized.
In the standard mode the output LEDs and the relay LEDs have the same
state. In the fail-safe mode the output LEDs and the relay LEDs have the
opposite state.
4.5. Operating voltage LED (12)
The green operating voltage LED indicates whether VISY-Output 8 is supplied with volt-
age. After switching on the power supply, the operating voltage LED illuminates continu-
ously. If the LED flickers or is unlit, this indicates a problem with the power supply or the
mains adapter.

Technical data Page 10/11
5. Technical data
Dimensions: H 60 x W 180 x D 130 [mm] (without cable glands)
Casing protection class: IP66
Ambient temperature: 0 °C ... +40 °C
Power supply: 230 VAC ±10 %, 50 - 60 Hz, ≤4 VA
Communication: 1 x RS-485, galvanically isolated, 3-pin. screw terminal
with ground (GND) to connect to VISY-ICI 485
Outputs: Eight relays each with potential-free changeover contact
load rating of the contacts: AC: U ≤250 VAC, I ≤3 A, P ≤300 VA, cos ϕ≥0,7
DC: U ≤24 VDC, I ≤2 A, P ≤50 VA
Table 4: Technical data
6. List of figures
Figure 1: VISY-Output 8 Design...................................................................................... 2
Figure 2: Power supply screw terminal............................................................................ 3
Figure 3: Relay screw terminal ........................................................................................ 4
Figure 4: Communication screw terminal........................................................................ 4
7. List of tables
Table 1: Relay mode....................................................................................................... 6
Table 2: Output LEDs ..................................................................................................... 8
Table 3: Status LED ........................................................................................................ 8
Table 4: Technical data.................................................................................................10


Blank page

FAFNIR GmbH
Schnackenburgallee 149 c
22525 Hamburg
Germany
Tel.: +49 / 40 / 39 82 07–0
Fax: +49 / 40 / 390 63 39
E-mail: info@fafnir.de
Web: www.fafnir.com
Table of contents
Other fafnir Control Unit manuals
Popular Control Unit manuals by other brands

Alpha IP
Alpha IP RTA 61001-N1 Quick install guide

Honeywell
Honeywell NOTIFIER 020-772 Fitting instructions

Pilz
Pilz PNOZ mo4p operating manual

XOXO Modular
XOXO Modular IXO Operation manual and installation guide

M-system
M-system R7HL-DAC15E instruction manual

Lutron Electronics
Lutron Electronics LMM-16R-DV-B Installation

Hiltron
Hiltron PCM2 quick start guide

PERSTA
PERSTA HD91 operating instructions

Pfeiffer Vacuum
Pfeiffer Vacuum EVN 116 operating instructions

Danfoss
Danfoss WVFX 32 installation guide

Endress+Hauser
Endress+Hauser Prosonic S FMU90 operating instructions

V-Chip Microsystems
V-Chip Microsystems VT-SX1278-433M user guide