Fancom IMS User manual

IMS
MANUAL
GB

IMS
A5911573 - GB030409
Note: The original, authoritative version of this manual is the English version
produced by Fancom B.V. or any of its subsidiaries, (hereafter collectively referred
to as "Fancom"). Subsequent changes to any manual made by any third party
have not been reviewed nor authenticated by Fancom. Such changes may
include, but are not limited to, translation into languages other than English, and
additions to or deletions from the original content. Fancom disclaims
responsibility for any and all damages, injuries, warranty claims and/or any other
claims associated with such changes, inasmuch as such changes result in content
that is different from the authoritative Fancom-published English version of the
manual. For current product installation and operation information, please contact
the customer service and/or technical service departments of the appropriate
Fancom subsidiary or division. Should you observe any questionable content in
any manual, please notify Fancom immediately in writing to: Fancom B.V., P.O.
Box 7131, 5980 AC Panningen, The Netherlands.
All rights reserved. Reproduction of any part of this manual in any form
whatsoever without Fancom’s express written permission is forbidden. The
contents of this manual are subject to change without notice. All efforts have been
made to assure the accuracy of the contents of this manual. However, should any
errors be detected, Fancom would greatly appreciate being informed of them. The
above notwithstanding, Fancom can assume no responsibility for any errors in this
manual or their consequence.
Copyright 2009 Fancom B.V.
Panningen, the Netherlands
Always keep this manual by your network module

A5911573 - GB030409
IMS
EC Declaration of compliance
EC Declaration of compliance
Manufacturer Fancom B.V.
Address Industrieterrein 34
City Panningen (the Netherlands)
hereby declares that the IMS
Satisfies the conditions set out in:
1. The Low Voltage directive 2006/95/EC
According to EN-61010
2. The EMC directive 2004/108/EC
Emission according to NEN-EN 61000-6-3:2001
Immunity according to NEN-EN 61000-6-2:2001
Place: Panningen Date: 03-04-2009
Chris van Erp
Manager Innovation
Wout Hoolboom
Projectmanager

A5911573 - GB030409
IMS
Table of contents
Table of contents
About this manual 1
1. Introduction 2
IMS in I/O-Network 2
2. Technical specifications 3
3. Safety instructions and warnings 5
3.1 General 5
3.2 During installation 5
3.3 During use 6
4. Mounting and installation 7
5. Possibilities IMS 8
5.1 Pre-defined position / independent control 8
6. Switch 9
7. DIP-switches 10
8. 7-segment display 10
9. Control 11
9.1 The IMS as I/O-network module 11
9.2 The IMS as a traditional end station 13
10. Adjustment procedure 14
10.1 General 14
10.2 Air inlet minimum / maximum 15
10.2.1 Adjusting air inlet minimum 15
10.2.2 Adjusting air inlet maximum 16
10.2.3 End of adjustment procedure minimum and/or
maximum 16
10.3 Predefined position 17
Connection diagram IMS 1-Phase 18
Connection diagram IMS 3-Phase 19
Connection I/O-Network 20

ITM Manual
About this manual
A5911573 - GB030409 1
About this manual
This manual has been written for the network module installer and user
and contains information about the installation and working of the
network module. This manual also contains information concerning
network module service.
For the installer
Read this manual carefully and follow all the safety instructions. The
installer settings can then be made and the network module prepared for
further use.
For the user
This manual also contains a section for the user. It contains information
about the daily use of the network module.
If you have any questions, please do not hesitate to contact Fancom. The
subjects discussed in this manual are listed in the table of contents.
The following symbols are used in this manual:
Suggestions, advice and notes with additional information.
Caution
The product could be damaged, if the procedures are not followed
carefully.
Caution
Life threatening situation, if the procedures are not followed carefully.

IMS
Introduction
A5911573 - GB030409 2
1. Introduction
The Fancom IMS is an Intelligent Actuator Module to be used in
combination with a Fancom climate controller in the agricultural sector.
This IMS controls a Fancom actuator. Control is based on the
potentiometer feedback (4K7) of the actuator.
IMS in I/O-Network
An IMS in an I/O-Network has more possibilities. In addition to the
control mentioned above, temperature measurement is also possible.
The Fancom climate controller can use this input.
If I/O-network communication fails, the IMS controls the air inlet position
to the last received setting, based on the IMS temperature
measurement. The Fancom climate controller must communicate this
setting to the IMS. Refer to the description of the Fancom climate
controller concerned.

IMS
Technical specifications
A5911573 - GB030409 3
2. Technical specifications
Power supply
Mains voltage 1-phase: 230Vac (-10%, +6%)
3-phase: 400Vac (-10%, +6%)
Mains frequency 50/60Hz
Fuse electronics (5 x 20mm.) slow blown, 250V T50mA
Max. power consumption electronics 5VA
Inputs
Analog In Voltage- or temperature measuring
Voltage 0-10V, temperature sensor type S7 ( -50 t/m 110"C)
I/O-net I/O-net
PF (PowerFail) Make-contact
Position feedback motor Potentiometer 4k7Ω(+/- 20%)
Outputs
Relay (2×) 1-phase: 230Vac, max. 4A
3-phase: 400Vac, max. 4A
Limit switches Contact (voltage free) 30Vac / 60Vdc – min. 1A
Manual control
Rotary switch ‘close-0-aut.-0-open’ control
Housing
Plastic housing with screw on lid IP54
Dimensions (lxbxh) 1-phase: 180×240×140mm
3-phase: 300×240×140mm
Weight (unpacked) 1-phase: 1,72 kg.
3-phase: 2,35 kg.
Ambient climate

IMS
Technical specifications
A5911573 - GB030409 4
Operating temperature range 0 to 40°C
Storage temperature range -10 to +50°C
Relative humidity <95%, uncondensed
I/O-netwerk
Possibility of communication via the I/O-Network. One control computer
and a maximum of 31 network modules may be connected to the I/O-
Network. Each connected network module has a unique address. After an
address has been changed, the network module should always be
restarted (power off-on).
Table 1: I/O-Addresses for the control computer
In-/output type ITM address . sequence number
Analog measurement (temp.) “ITM address” . 1
Air inlet position “ITM address” . 2

IMS
Safety instructions and
warnings
A5911573 - GB030409 5
3. Safety instructions and warnings
3.1 General
Read the safety instructions carefully before installing and/or using the
network module. The installation of the network module and trouble
shooting must be carried out by an authorized technician/installer,
according to the prevailing standards.
Fancom takes no responsibility for any possible damage as a result of
incorrect settings and a non- or partially functioning installation.
3.2 During installation
Caution
1. Take precautions to prevent electrostatic discharge (ESD).
2. Provide a clean and dry place to work.
Disconnect power before installation
3. Use correct cables as shown on the connection diagrams (see
appendix) and follow all instructions.
4. Make all wiring connections and check them before applying
power.
Incorrect connections can cause permanent damage

IMS
Safety instructions and
warnings
A5911573 - GB030409 6
3.3 During use
Caution
1. The network module is an electronic apparatus, possible
malfunctioning cannot therefore be excluded.
2. Check the network module regularly for any damage. Any eventual
damage should be directly reported to your installer.
A damaged network module is dangerous!
3. Do not use running water (high pressure cleaners) to clean the
network module.
The network module is water resistant, not waterproof!
4. Important!
It is advisable not to switch off the network module. This could
lead to condensation caused by cooling down.

IMS
Mounting and installation
A5911573 - GB030409 7
4. Mounting and installation
Observe the following points when mounting/installing the network module:
Disconnect power before installation
1. Use the cables mentioned in the instruction diagrams and follow all
instructions.
2. Never mount the network module in a place where the weather
has direct influence; not in direct sunlight or in places where the
temperature can rise sharply etc.
3. Never mount the network module in the section itself because of
the (manual) operation.
4. Mount the network module on a flat surface, the gland nuts should
be at the bottom of the module.
5. Mount the network module at a convenient height for manual
operation.
6. Seal all gland nuts after connection to prevent the entry of dust,
humidity and/or aggressive gases.
Always observe the regulations of the electricity company.

IMS
Possibilities IMS
A5911573 - GB030409 8
5. Possibilities IMS
An IMS controls a 1~ or 3~ Fancom actuator. Control is based on the
potentiometer feedback (4K7) of the actuator.
The required air inlet position is determined by the I/O-net control or a
10-0V (or 0-10V) control signal from a control computer.
If the IMS is controlled via an I/O-Network, the IMS has more
possibilities. The analog input can be used for temperature measurement
and the air inlet position can be read out.
5.1 Pre-defined position / independent control
In certain problem situations the IMS can control the air inlet position
independently. A pre-definable position is settable, the standard factory
setting is 50%. If the IMS controls independently, a “U”appears on the
7-segment display.
No control signal (voltage)
If the control signal fails, the air inlet will open fully (10-0V control
signal) or close fully (0-10V control signal).
No control signal (communication)
If communication with the control computer fails, the following will
happen. If an individual temperature sensor has been connected to the
IMS and the control computer was able to communicate the temperature
setpoint and the control range to the IMS, the IMS will control
independently based on the last received setpoints. If this is not possible,
it will control the air inlet to the pre-defined position.

IMS
Switch
A5911573 - GB030409 9
Attention! Not all control computers can communicate these
settings. Check the manual of the control computer concerned
first.
Power out
If the input of the ‘power fail’ (PF) detection activates, the IMS will
control the air inlet to the pre-defined position - if the correct emergency
power supply has been connected.
6. Switch
The front of the IMS has a 5-position switch. The position of the switch
determines the function of the actuator. (see Figure 1).
Close manually
OffOff
Open manually
Automatic
aut.
Figure 1: Switch

IMS
DIP-switches
A5911573 - GB030409 10
7. DIP-switches
DIP-switches 1 thru 5 -type control
DIP-switches 1 thru 5 determine the type of control. If an I/O-net is used
an address between 1 .….31 should be set to identify the IMS to the
connected control computer. If an analog (0-10V or 10-0V) control is
used, the DIP switches should be all be set to ON.
DIP-switch 6 – Temperature sensor readout
If the IMS measures the temperature itself via a sensor connected to the
IMS, DIP-switch 6 should be set to OFF.
8. 7-segment display
The IMS has a 7-segment display (see figure 2).
This indicates the possible program status.
1. Adjusting maximum air inlet position.
2. Adjusting minimum air inlet position.
3. Adjusting pre-defined air inlet position successful.
b. Busy determining a stable position within the control procedure. (Busy)
E. Error during determining a stable position within the control
procedure. (Error)
c. Adjusting maximum air inlet position successful. (Close)
O. Adjusting minimum air inlet position successful. (Open)
P. Adjusting pre-defined air inlet position successful.
U. Due to problems, the IMS is now controlling based on the predefined
position or controlling independently based on setpoints.
Potmeter value indication during adjustment minimum. Too high,
good or too low.
An “A” in the display, followed by a number, indicates an alarm. The
table below contains an alarm overview.
Alarm indication Meaning
A0 Backup alarm
A1 Memory alarm
A2 Inlet position not reached within 10 min.
A3 Power failure
A4 I/O-net error; No communication with I/O-Net

IMS
Control
A5911573 - GB030409 11
9. Control
9.1 The IMS as I/O-network module
First set an I/O-address using DIP-switches 1 thru 5 (see figure. 2). In a
single I/O-network all the I/O-network module must have a unique
address.
Figure 2: Setting the IMS
I/O address
I/O
adr.
DIP
1
DIP
2
DIP
3
DIP
4
DIP
5
AN.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Re-start the module after an I/O-address
has been changed.
Temperature measurement
DIP
6
On
Off
IMS doesn’t measure the temperature itself
IMS measures the temperature itself
1 2 3 4 5 6
ON
Temp.
meas. Voltage-
meas.
JP1
Start button
adjustment
(BUTTON)
7-segment display
= On
IO-net terminal resistor:
= Off

IMS
Control
A5911573 - GB030409 12
The voltage input can be used as the temperature input if the I/O-net is
used. Place the jumpers JP1 (see figure 2).
To be able to measure the temperature, DIP switch 6 must be set to
‘OFF’ (see figure 2). The connected temperature sensor can now be read
out.
The IMS can also take over control in the event of communication
problems. If the connected computer can communicate the setpoint and
control range to the IMS, these values will be used for further control.
The IMS will continue control based on the last received settings and the
temperature it measured on the connected sensor. If DIP switch 6 is set
to NO measurement or no settings have been communicated, the IMS
will control using the value set as the pre-defined position.
Adjust the IMS according to the procedures described (see chapter 10).

IMS
Control
A5911573 - GB030409 13
9.2 The IMS as a traditional end station
If the IMS is used as a traditional end station, it is controlled by a
voltage signal.
The voltage input should be used as an analog input. Remove jumpers
JP1 (see figure 2). After these jumpers have been removed, the IMS can
be used for 0-10/10-0Vdc control.
The control signal is on the same connection as any temperature sensor.
In this case, no temperature sensor can be connected. If control is via a
10-0Vdc (or 0-10Vdc) control signal, DIP switches 1..5 must all be set to
ON (see figure 2).
Adjust the IMS according to the procedures described (see chapter 10).

IMS
Adjustment procedure
A5911573 - GB030409 14
10. Adjustment procedure
10.1 General
Before the IMS can be used, the minimum and maximum air inlet
position must be adjusted first and if any emergency power supply is
used also set the pre-defined position. The option on the 7-segment
display is important here.
In order to guarantee accurate control, the air inlet range should be at
least 30% of the total range of the actuator. Preferably use a control
whereby at least 50% of the motor stroke is used. With smaller strokes
it’s advisable to reeve the cables, to increase the range of the motor.
Table 2: Position of the 7-segment display during adjustment
'Situation'
Adjustment of:
Display
Minimum air inlet position 1 b C / E
Maximum air inlet position 2 b O / E
Predefined position 3 b P / E
Open the cover of the IMS housing.

IMS
Adjustment procedure
A5911573 - GB030409 15
10.2 Air inlet minimum / maximum
10.2.1 Adjusting air inlet minimum
With 0-10V or 10-0 V control, ensure that the analog output of the
connected outputs 1%. This is unimportant with an I/O-net controlled
system.
Method 1% adjustment
1. Press the BUTTON for about 2 seconds until number “1”appears
on the 7-segment display. The IMS is now in the 1% adjustment
mode.
2. Close the air inlet manually by setting the switch on the IMS to the
CLOSE position. This must happen within 10 minutes, otherwise
calibration will be interrupted and the display ‘cleared’.
3. When the air inlet is fully closed turn the potmeter completely anti-
clockwise using a screwdriver until it cannot be turned any further.
Then turn it a fraction clockwise to get it out of the so-called “dead
band”. The following will appear on the 7-segment display:
Signal too high, turn potmeter further to the left.
Signal too low, turn potmeter further to the right.
Signal O.K., proceed with the next step.
Poss. check: measure the voltage over the clamps at the
(0,1..0,4V)
4. Press the BUTTON to confirm the minimum position; “b”(busy)
will appear on the display. If this does not happen within 10
minutes, the adjustment procedure will be interrupted.
5. When the value for the closed position has been determined, this
will be compared to the value of the open position. For accurate

IMS
Adjustment procedure
A5911573 - GB030409 16
control of the inlet position, the difference must be a minimum of
30% of the range.
As soon as “C” (close) appears on the 7-segment display,
minimum adjustment is successful.
If “E” (error) appears on the 7-segment display this indicates that
the mutual difference is too small. Adjustment was not successful. In
this case, it is usually the maximum air inlet position that is the
problem. This should first be adjusted before the minimum position
is adjusted again.
10.2.2 Adjusting air inlet maximum
With 0-10V or 10-0 V control, ensure that the analog output of the
connected control computer outputs 99%. This is unimportant with an
I/O-net controlled system.
Method 99% adjustment
1. Press the BUTTON for about 2 seconds until “2” appears on the 7-
segment display.
2. The IMS is now in the 99% adjustment mode.
3. Open the air inlet manually by setting the switch on the IMS to the
OPEN position. This must happen within 10 minutes, otherwise
calibration will be interrupted and the display ‘cleared’.
4. Press the BUTTON to confirm the maximum position; “b” (busy)
will appear on the display. If this does not happen within 10
minutes, the adjustment procedure will be interrupted.
5. When the value of the open position has been determined, this will
be compared to the value of the closed position. For accurate
control of the inlet position, the difference must be a minimum of
30% of the range.
6. As soon as “O” (open) appears on the 7-segment display, this
indicates that the maximum adjustment was successful.
If “E” (error) appears on the 7-segment display this indicates that
the mutual difference is too small. Adjustment was not successful.
10.2.3 End of adjustment procedure minimum and/or maximum
Set the switch on the IMS to the AUT position. If the switch is not set to
AUT, the programme will shut down after max. 10 minutes anyway.
Other manuals for IMS
1
Table of contents
Other Fancom Control Unit manuals
Popular Control Unit manuals by other brands

Seneca
Seneca Z-PC SERIES installation manual

ZIEHL-ABEGG
ZIEHL-ABEGG EVAC 3C Original operating instructions

KERAFLO
KERAFLO AYLESBURY KB installation guide

ADTRAN
ADTRAN Type 400 quick start guide

IMI
IMI Buschjost 84070 Series operating manual

Applied Motion Products
Applied Motion Products Mechanical Outline 3540 user manual