manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Notifier
  6. •
  7. Control Unit
  8. •
  9. Notifier XP10-M User manual

Notifier XP10-M User manual

Shipped on Board:
(1) Shunt in Class A/B position
(Shipped in Class B position, remove shunt for Class A)
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a
compatible Notifier system control panel.
COMPONENTS
Following are descriptions of the XP10-M mounting frameworks.
There are two mounting options for XP10-M modules:
• Up to six XP10-M modules can be installed on a CHS-6 in
a CAB-3 Series cabinet, CAB-4 Series cabinet or BB-25 cabinet.
• One or two XP10-M modules can be installed in a BB-XP cabi-
net.
Chassis
The CHS-6 chassis is used to mount XP10-M modules in a BB-25,
CAB-3 or
CAB-4 Series cabinet
. It accommodates up to six XP10-
M modules in a single cabinet row three modules wide and two
modules deep.
Figure 1. CHS-6 Chassis:
The BB-XP cabinet has a built-in chassis that will accommodate
one or two XP10-M modules.
N500-77-00 1 I56-1803-007
Notifier, 12 Clintonville Rd., Northford, CT 06472-1653 Phone: (203) 484-7161
XP10-M Ten Input Monitor Module
INSTALLATION AND MAINTENANCE INSTRUCTIONS
SPECIFICATIONS
Normal Operating Voltage: 15-32 VDC
Stand-By Current: 3.5 mA
Alarm Current: 55 mA (assumes all ten LEDs solid on)
Temperature Range: 32°F to 120°F (0°C to 49°C)
Humidity: 10 to 93% Non-condensing
Dimensions: 6.8˝H x 5.8˝W x 1.25˝D
Accessories: CHS-6 Chassis; BB-25 Cabinet; BB-XP Cabinet; CAB-3 Series Cabinet; CAB-4 Series Cabinet
Wire Gauge: 12-18 AWG
Maximum IDC Wiring Resistance: 1500 Ohms
Maximum IDC Voltage: 10.2 VDC
Maximum IDC Current: 240µA (per device)
C0202-00
C0206-00
BEFORE INSTALLING
If the modules will be installed in an existing operational system,
inform the operator and local authority that the system will be
temporarily out of service. Disconnect the power to the control
panel before installing the modules. This system contains static
sensitive components. Always ground yourself with a proper
wrist strap before handling any circuits so that static charges are
removed from the body. The housing cabinet should be metallic
and suitably grounded.
NOTICE: This manual should be left with the owner/user of
this equipment.
GENERAL DESCRIPTION
The XP10-M Ten Input Monitor Module is intended for use in an
intelligent alarm system. Each monitor module is intended to inter-
face between a control panel and normally open contact devices,
such as pull stations. A common SLC input is used for all modules,
and the initiating device loops share a common supervisory supply
and ground. Otherwise, each monitor operates independently from
the others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the
first module from 01 to 150. The remaining modules are auto-
matically assigned to the next nine higher addresses. Provisions
are included for disabling a maximum of two unused modules to
release the addresses to be used elsewhere. Each module also has
panel controlled green LED indicators. The panel can cause the
LEDs to blink, latch on, or latch off.
Included:
(6) 1 x 4 Terminal Blocks (2) 1
1
/4
″
(32mm) Stand offs
(4) Machine Screws (3) Shunts (10) 47k Ohm
End of Line Resistors
(2) Nuts
I56-1803-007
Figure 2. BB-XP Cabinet:
The front XP10-M module positions of each chassis are offset
below the rear XP10-M module positions so that all of the status
indicators are visible.
Cabinets
A BB-25, CAB-3 or CAB-4 Series cabinet will house the CHS-6
chassis with up to six XP10-M modules installed on it. Refer to
cabinet installation documents for dimensions.
The BB-XP cabinet houses one or two XP10-M modules on the
internal chassis that is part of the cabinet. Refer to cabinet instal-
lation documents for dimensions.
INSTALLATION STEPS
1. Cabinet Mounting
In a clean, dry area, mount the backbox using the four holes
provided in the back surface of the cabinet (Figure 3).
2. Chassis Installation
The CHS-6 chassis is mounted in the BB-25, CAB-3 or CAB-4
Series cabinet. It is shipped with two self-threading screws,
which are used to fasten the chassis to the back wall of the
cabinet (see Figure 4).
The BB-XP cabinet comes with the chassis already installed, so no
mounting is necessary.
Figure 3. Typical mounting hole locations:
Figure 4. Mounting the CHS-6 chassis:
3. Module Installation
There are two methods for installing a module in the rear
position of a chassis. Method one is for installation of a rear
module only, when no module will be installed in front of it.
Refer to Figure 5 for instructions. Method two is for installation
of a rear module when another module will be installed in the
chassis position in front of it. Refer to Figures 6a and 6b for
method two. All necessary screws and standoffs are supplied
with the modules.
Figure 5. Installation of rear module only, method one:
Step 1: Insert the bottom of the XP10-M module down into a rear
slot on the chassis.
Step 2: Carefully swing the upper edge of the board back
towards the back of the chassis until it touches
the two standoffs.
Step 3: Align two 4-40 screws with the two standoffs
and tighten.
Step 4: Address and wire the modules
according to the instructions in this manual.
The steps in Figures 6a and 6b describe and illustrate module in-
stallation when the rear chassis position and the position in front
of it will be filled. Front position installation is possible only if
the rear position is filled with an XP module.
Figure 6a. Installation of XP10-M module in a rear
chassis position, method two:
Step 1: Insert the bottom edge of the XP10-M module down into
a rear slot of the chassis.
Step 2: Carefully swing the upper edge of the board towards
the back of the chassis until it touches the short
standoff attached to the chassis.
Step 3: Align the long standoff with the short standoff and tighten.
N500-77-00 2 I56-1803-007
C0237-00
C0234-00
C0235-00
C0236-00
C0225-00
Backbox
Mounting
Holes
23
1
0
1
2
3
456789
0
78
6
5
4
3
21
910
11
12
13
14
15
BASE ADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
0
1
2
3
456789
0
78
6
5
4
3
21
910
11
12
13
14
15
BASE ADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
Mount with self-threading screws
to back of cabinet
1
Figure. 7:
TENS
0
78
6
5
4
3
21
910
11
12
13
14
15
NOTE: Power must not be applied to the unit when changing
functionality of the shunts.
4. A shunt is provided to disable a maximum of two unused
modules in Class B operation and one unused module in Class
A operation. Modules are disabled from the highest address
and work downward. If two modules are disabled, the lowest
eight addresses will be functional, while the highest two will
be disabled. For example, in Class B operation, if the shunt for
Address Disable is placed on “two” and the base switch is set
to 28, the modules will be assigned to 28, 29, 30, 31, 32, 33,
34 and 35 while disabling the highest two positions.
5. A communications loss feature is available on some panels.
Upon a communication loss, due to a microprocessor failure at
the control unit, the XP10-M will send a signal to the control
unit to activate the notification device circuits upon initiating
of an alarm on the XP10-M. A single shunt is used to enable
(shunt on) or disable (shunt off) this feature for all modules
on the board.
NOTE: Place unused shunts on single pin to store on board for
future use.
WIRING NOTES
• Power-limited circuits must employ type FPL, FPLR, or FPLP
cable as required by Article 760 of the NEC.
PROGRAMMING
The XP10-M module operates with the following Fire Alarm
Control Panels:
• AM2020/AFP1010
• AFP-200
• AFP-300/AFP-400
• S-5000 with AIM-200
• AFC-600
• NFS-640
• NFS-3030
The modules are programmed as devices in each system according
to the programming instructions in the appropriate FACP manual.
N500-77-00 3 I56-1803-007
Figure 6b. Installation of XP10-M module in front
chassis position:
Step 1: Insert the bottom edge of the XP10-M module down into
a front slot of the chassis.
Step 2: Carefully swing the upper edge of the board towards the
back of the chassis until it touches the 1
1⁄4˝ (31.75mm)
standoffs installed on the rear module.
Step 3: Align two 4-40 screws with the two standoffs and tighten.
Step 4: Address and wire the modules according to the instruc-
tions in this manual.
WIRING
NOTE: All wiring must conform to applicable local codes, or-
dances, and regulations.
1. Install module wiring in accordance with the job drawings and
appropriate wiring diagrams.
2. All wiring to the XP10-M is done via terminal blocks. In order
to properly make electrical connections strip approximately 1⁄4˝
of insulation from the end of wire, sliding the bare end of the
wire under the clamping plate screw.
3. Set the address on the modules per the job drawing. Use the
rotary code switches to set the address of the first module
(between 01 and 150).
In Class B operation, the remaining modules are automati-
cally assigned to the next nine higher addresses. For exam-
ple, if the base address switch is set to 28, the next nine modules
will be addressed to 29, 30, 31, 32, 33, 34, 35, 36, and 37.
The module is shipped in Class B position, remove shunt for
Class A. When operating in Class A, alternate modules are paired
together (+0/+1, +2/+3, +4/+5, +6/+7, +8/+9), resulting
in a total of five modules. For example, if the base address switch
is set to 28, then 30, 32, 34 and 36 will be automatically assigned
to the modules while 29, 31, 33, 35 and 37 are available to be
used for other modules on the SLC. For Class A and B operation,
DO NOT set the lowest address above 150, as the other modules
will be assigned to nonexistent addresses.
NOTE: The XP10-M must have power cycled for shunt changes
to take effect.
NOTE: Some panels support extended addressing. In order to
set the module above address 99 on compatible systems,
carefully remove the stop on the upper rotary switch (see
Figure 7). If the panel does not support extended address-
ing, do not set the lowest address above 90.
FCC Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
C0226-00
C0227-00
2
3
1
N500-77-00 4 I56-1803-007
©2006 Notifier
0
1
2
3
456789
BASE ADDRESS
TO NEXT
DEVICE
–
STATUS
INDICATORS
—
+
—
+
—
+
—
+
—
+
—
+
IDC
ADDRESS
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
IDC
ADDRESS
IDC
ADDRESS
IDC
ADDRESS
IDC
ADDRESS
—
+
—
+
SLC
—
+
—
+
+
–
+
FROM PANEL OR
PREVIOUS DEVICE
47K
EOL
RESISTOR
ELR-47K
CONNECT MODULES TO
LISTED COMPATIBLE
NOTIFIER CONTROL
PANELS ONLY
SIGNAL LINE CIRCUIT 32 VDC MAX.
SEE PANEL INSTRUCTION MANUAL
FOR WIRE REQUIREMENTS.
CLASS B IDC (TYPICAL)
—
+
—
+
A/B SLCT
COM LOSS
DISABLE 1
DISABLE 2
0
1
2
3
45678910
11
12
13
14
15
POWER LIMITED
AND SUPERVISED
NOTE: Any number of UL listed contact closure devices may be used. DO NOT mix fire alarm initiating and supervisory devices on
the same initiating device circuit. Install contact closure devices per manufacturer’s installation instructions.
NOTE: Any number of UL listed contact closure devices may be used. DO NOT mix fire alarm initiating and supervisory devices on
the same initiating device circuit. Install contact closure devices per manufacturer’s installation instructions.
BASE ADDRESS
TO NEXT
DEVICE
–
STATUS
INDICATORS
—
+
—
+
—
+
—
+
—
+
—
+
IDC
ADDRESS
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
IDC
ADDRESS
IDC
ADDRESS
IDC
ADDRESS
IDC
ADDRESS
—
+
—
+
SLC
—
+
—
+
+
–
+
FROM PANEL OR
PREVIOUS DEVICE
CONNECT MODULES TO
LISTED COMPATIBLE
NOTIFIER CONTROL
PANELS ONLY
SIGNAL LINE CIRCUIT 32 VDC MAX.
SEE PANEL INSTRUCTION MANUAL
FOR WIRE REQUIREMENTS.
CLASS A IDC (TYPICAL)
—
+
—
+
A/B SLCT
COM LOSS
DISABLE 1
DISABLE 2
IDC 2
IDC 3
IDC 4
IDC 5
0
1
2
3
456789
0
1
2
3
45678910
11
12
13
14
15
POWER LIMITED
AND SUPERVISED
REMOVE SHUNT FOR CLASS A.
Figure 8
Figure 9
Figure 8. Typical Initiating Device Circuit Configuration – Class B, Style B:
Figure 9. Typical Fault Tolerant Initiating Device Circuit Configuration – Class A, Style D:
C0252-01
C0251-01

Other Notifier Control Unit manuals

Notifier FDM-1 User manual

Notifier

Notifier FDM-1 User manual

Notifier IDR-MD User manual

Notifier

Notifier IDR-MD User manual

Notifier FDM-1 User manual

Notifier

Notifier FDM-1 User manual

Notifier NAM-232 User manual

Notifier

Notifier NAM-232 User manual

Notifier 020-553 Instruction Manual

Notifier

Notifier 020-553 Instruction Manual

Notifier FZM-1 User manual

Notifier

Notifier FZM-1 User manual

Notifier LDM-32 Assembly instructions

Notifier

Notifier LDM-32 Assembly instructions

Notifier FMM-1 FlashScan User manual

Notifier

Notifier FMM-1 FlashScan User manual

Notifier XP6-R User manual

Notifier

Notifier XP6-R User manual

Notifier TM-4 Technical manual

Notifier

Notifier TM-4 Technical manual

Notifier XP6-MA User manual

Notifier

Notifier XP6-MA User manual

Notifier NCM-W Operator's manual

Notifier

Notifier NCM-W Operator's manual

Popular Control Unit manuals by other brands

EVA EVAstream & Piezo Quick start installation manual

EVA

EVA EVAstream & Piezo Quick start installation manual

AMX RDM-DPSM Dimensional drawing

AMX

AMX RDM-DPSM Dimensional drawing

Siemens MVS661 N Series Mounting instructions

Siemens

Siemens MVS661 N Series Mounting instructions

Norcold 322 Series Replacement manual

Norcold

Norcold 322 Series Replacement manual

FAAC E145S quick start guide

FAAC

FAAC E145S quick start guide

ProSoft Technology MVI69-GEC user manual

ProSoft Technology

ProSoft Technology MVI69-GEC user manual

National Instruments NI 9235 Getting started guide

National Instruments

National Instruments NI 9235 Getting started guide

STIEBEL ELTRON WPM Commissioning

STIEBEL ELTRON

STIEBEL ELTRON WPM Commissioning

Econ 1205 Installation & operation manual

Econ

Econ 1205 Installation & operation manual

National Instruments NI 9882 Getting started guide

National Instruments

National Instruments NI 9882 Getting started guide

Akron Style 6032 Installation, operation & maintenance manual

Akron

Akron Style 6032 Installation, operation & maintenance manual

ICP DAS USA SG-3227 quick start

ICP DAS USA

ICP DAS USA SG-3227 quick start

Woodward 505XT product manual

Woodward

Woodward 505XT product manual

SBS Technologies P-Octal Series user manual

SBS Technologies

SBS Technologies P-Octal Series user manual

Leadshine EM422S user manual

Leadshine

Leadshine EM422S user manual

Automationdirect.com Productivity 2000 P2-15TD1 manual

Automationdirect.com

Automationdirect.com Productivity 2000 P2-15TD1 manual

Geco G-403-P02 user manual

Geco

Geco G-403-P02 user manual

Kemo M202 manual

Kemo

Kemo M202 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.