F&F DR-30M User manual

- 1 -
DR-30M
Motion sensor (PIR),
detection range 30 m
The DR-30M sensor is used for automatic, temporary switching
of lighting when a moving person or other object is detected. It is
especially recommended for use in high rooms and storage halls
up to 12÷15 meters high.
The sensor detects sources of infrared radiation and analyzing
parameters such as the amount of heat emitted and the speed at
which the object moves determines the switching of the lighting.
Infrared sensors have the highest performance when detecting
motion perpendicular to the sensor axis and the lowest when
motion is directly in the direction of the sensor. Only if there is
no movement in the detection area triggers the lighting support
time. Another movement in the detection area and its subsequ-
ent disappearance in the course of time measurement starts the
support time from the beginning.
Purpose
Functioning
F&F Filipowski sp. j.
Konstantynowska 79/81, 95-200 Pabianice, POLAND
phone/fax (+48 42) 215 23 83 / (+48 42) 227 09 71
www.fif.com.pl; e-mail: biuro@fif.com.pl
Do not dispose of this device in the trash along with other waste!
According to the Law on Waste, electro coming from households free of charge and can
give any amount to up to that end point of collec� on, as well as to store the occasion of
the purchase of new equipment (in accordance with the principle of old-for-new, regard-
less of brand). Electro thrown in the trash or abandoned in nature, pose a threat to the
environment and human health.

- 2 -
Thanks to the advanced digital signal processing technology,
the DR-30M is capable of detecting movement at distances up
to 30 m (wall mounting) and in a circle with a diameter of 20
m in the case of ceiling mounting (mounting height 15 m). The
motion sensor has a built-in programmable twilight switch that
prevents the lighting from being switched on during the day. The
maximum detection range and the lighting switching time are
also programmable.
High temperatures may adversely affect the sensitivity
of the device. Also, movement that is too slow or fast
can limit the sensitivity of the sensor.
The heat emitted by a motion sensor-controlled light so-
urce can lead to accidental self-excitation of the sensor.
Therefore, the sensor should be mounted at a reasona-
ble distance from the light source (min. 60÷100 cm) and
in such a way that the light source is outside the detec-
tion area of the sensor.
Diagram

- 3 -
The DR-30M sensor is supplied with the following settings:
»the brightness level below which switching can occur: (50 lx),
»switch-on time: 6 min.
»detection range: 30 min.
Press and hold the change settings button to enter the sensor
settings mode. The number of blinks of the signal light indicates
the currently selected setting:
»first blink: switch-on time;
»second blink: brightness level (twilight switch);
»third blink: detection range.
Sensor description
Configuration

- 4 -
Release the button when the expected setting is indicated. Then
set the desired value with short presses of the button.
If the button is not pressed for 5 seconds, the signal li-
ght will flash twice quickly, after which the current set-
ting will be saved and the sensor will exit configuration
mode.
Switch-on time settings
Without pressing
a button 10 seconds
1 press 30 seconds
2 presses 1 minute
3 presses 2 minutes
4 presses 6 minutes
5 presses 10 minutes
6 presses
20 minutes
(last setting – the indicator light will flash twi-
ce quickly, the setting will be saved and the
detector will exit the configuration mode)

- 5 -
Brightness level setting1
Without pressing
a button <10 lx
1 press 50 lx
2 presses 150 lx
3 presses
2000 lx
(last setting – the indicator light will flash twi-
ce quickly, the setting will be saved and the
detector will exit the configuration mode)
Detection range setting2
Without pressing
a button 10 m
1 press 15 m
2 presses 20 m
3 presses
30 m max
(last setting – the indicator light will flash twi-
ce quickly, the setting will be saved and the
detector will exit the configuration mode)
1 The sensor will switch on the lighting if the brightness level measured by
it is lower than the value set here.
2 The range setting is for wall mounting only and is indicative. The actual
value will depend on the installation method and ambient temperature,
among other factors. The detection range for ceiling mounting depends
on the installation height, according to the figure on page 6.

- 6 -
Ceiling mounting
Mounting height Detection range (diameter)
3 m 4 m
6 m 10 m
12 m 18 m
15 m 20 m
Detection area

Wall mounting
Dimensions

- 8 -
1. Disconnect the power supply.
2. Remove the external (back) sensor cover.
3. Connect the wires according to the wiring diagram.
4. Fasten the base to the floor with two screws.
5. Assemble the sensor housing - push on the outer cover.
6. Set the desired parameters.
7. Switch on the sensor power supply.
If the motion sensor is installed too close to the switched
light source, the system may be activated, which means
that the sensor will automatically switch on and off the
light source. It is necessary to move the sensor to an ap-
propriate distance away from the light source.
Mounting

The sensor is inactive for the first 30 seconds after the
power supply is switched on. During this time, the PIR
system warms up.
The motion sensor can work indoors and outdoors in
places where it is not exposed to direct rain or snowfall
and to the possibility of splashing the sensor housing
and its electrical connection points with water or other
liquid.
Avoid locations with large objects in the detection area
such as trees that can be moved by the wind.
Do not install the sensor in the immediate vicinity of he-
ating, air-conditioning and lighting devices.

- 10 -
Ceiling mounting
Wall mounting

- 11 -
Wiring diagram

- 12 -
power supply 100÷277 V AC
maximum load current (AC-1) 16 A
maximum load
continuous 2300 W
momentary 3000 W
twilight activation threshold 10÷2000 lx
motion detection 0.6÷1.5 m/s
switch-on time 30 s÷20 min. (±10 s)
detection angle 80°
max detection range (T<22°C)
ceiling mounting diameter 20 m
wall mounting 30 m
sensor mounting height
ceiling mounting 3÷15 m
wall mounting 2÷3 m
power consumption
standby 0.45 W
on 1 W
terminal 1.5 mm² screw terminals
tightening torque 0.3 Nm
working temperature -10÷40°C
dimensions
housing 90×82 mm, h= 48 mm
housing with handle 90×104 mm, h= 48 mm
mounting surface
ingress protection IP40
Technical data

- 13 -
The maximum load capacity of the relay contacts depends on
the nature of the load and the supply voltage.
When installing the controller, observe the following indicative
load ratings:
tungsten halogen fluorescent energy-saving LED
2000 W 1250 W 1000 W 500 W 250 W
The above data are indicative and will heavily depend on the
design of a specific receiver (that is especially important for
LED bulbs, energy-saving lamps, electronic transformers and
pulse power supply units), switching frequency and operating
conditions.
For more information visit: www.fif.com.pl.
If it is necessary to control a load with parameters ex-
ceeding the limit load capacity of the relay, one of the
following solutions should be used:
»limitation of the inrush current using a soft-start sys-
tem (for example MST-01, MST-02, MST-03 – all ma-
nufactured by F&F,
»use of an auxiliary contactor (e.g. ST25 by F&F).
Power table

- 14 -
The F&F products are covered by a warranty of the 24 months
from the date of purchase. Effective only with proof of purchase.
Contact your dealer or directly with us.
F&F Filipowski sp. j. declares that the device is in conformity
with the essential requirements of The Low Voltage Directive
(LVD) 2014/35/EU and the Electromagnetic Compatibility (EMC)
Directive 2014/30/UE.
The CE Declaration of Conformity, along with the references to
the standards in relation to which conformity is declared, can be
found at www.fif.com.pl on the product page.
Warranty
CE declaration
E220523

This manual suits for next models
1
Table of contents
Other F&F Security Sensor manuals