manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Faraday
  6. •
  7. Control Unit
  8. •
  9. Faraday 8701 User manual

Faraday 8701 User manual

PAGE 1 OF 2P/N 315-049480FA-2
Figure 1
8701 Module
The 8701 contact monitoring module interfaces direct shorting devices to the
System’s Addressable Device Circuit.
The 8701 can monitor a normally open or closed dry contact and it can report
the status of the contact.
PROGRAMMING
Refer to Figure 1 to locate the red and black Addressable Device Circuit
wires of the 8701.
Connect the Addressable Device Circuit wires of the 8701 to the Model
8720 Programmer/Tester. Use the cable provided with the Programmer/
Tester and the two alligator clip to banana plug adapters provided.
To Prevent Damage To The 8720:
DO NOT connect an 8701 to the 8720 until all field wiring is removed from the red and black ad-
dressable device circuit wires of the 8701.
NOTE: Connection from the 8720 to the 8701 is not polarity sensitive. Refer to Figure 2 for the
proper connections to the control panel.
Follow the instructions in the 8720 Programmer/Tester Manual (P/N 315-033260FA) to program the
desired address into 8701.
Record the device address on the label located on the 8701. The 8701 can now be installed and wired to
the system.
WIRING
(Refer to Figure 2.) Refer to the wiring diagram and wire the addressable interface module accordingly.
NOTE: Recommended wire size: 18 AWG minimum, 14 AWG maximum
ORGBLK
LINE
2LINE
1
GRN
ORG RED
ALL CONNECTIONS AREPOWER LIMITED
EARTH
GND
8701
INSTALLATION INSTRUCTIONS AND WIRING FOR
CONTACT MONITORING MODULE
P/N 8701
Siemens Industry, Inc.
Building Technologies Division • Florham Park, NJ
Tel: (973) 593-2600 • Fax: (973) 593-6670
Web: www.faradayfirealarms.com
PAGE 2 OF 2P/N 315-049480FA-2
Figure 2
Installing the 8701 Wiring
NOTES:
1. All supervised switches must be held closed and/or open for at least a quarter of a second to guarantee detection.
2. End of line device: 470 ohm, 1/4W resistor, P/N 140-820164.
3. 8701 is polarity insensitive. Line 1 and Line 2 can be either line of the loop.
4. The supervised switches have the following ratings:
Voltage maximum: 27 VDC
Current maximum: 6mA during polling
Contact resistance maximum: 10 ohms
Maximum cable length: 200 feet (18 AWG) CLine to line: 0.02uF CLine to shield: 0.04uF
Max line size: 14 AWG Min line size: 18 AWG
CAUTION: Ground shield ONLY at the specified location on the Control Panel.
CAUTION: EOL device must be a 470 ohm, 1/4W resistor. When replacing an existing 8701 on a device loop, you must also replace
the EOL resistor if it is not 470 ohms, 1/4W.
5. The green wire must be connected to earth ground.
a. Use wire nuts to pass the shield wire through the electrical box with NO connection to the device green wire.
b. Use shielded wire to connect the switch wiring.
c. Tie the switch wiring shield to earth ground.
6. The 8701 draws 1.3mA from the addressable device circuit.
7. All circuits are power limited.
Mounting
The 8701 mounts directly into a single gang switchbox (user supplied)
Connect the appropriate wires using wire nuts.Tuck the 8701 module inside the electrical box and dress
the wiring as required. (See Figure 3.)
BLACK
GREEN
ORANGE
ORANGE
LINE 2
LINE 2
LINE 1
LINE 1
8701
RED
TO NEXT
ADDRESSABLE DEVICE
GROUND
(SEE NOTE 5)
470 OHM, 1/4W
END OF LINE DEVICE
(SEE NOTE 2)
SUPERVISED SWITCH
(SEE NOTES 1 AND 2)
FROM CONTROL PANEL
ADDRESSABLE DEVICE
CIRCUIT OR FROM PREVIOUS
ADDRESSABLE DEVICE
Figure 3
Mounting the 8701
SINGLEGANG
SWITCHBOX
(USER SUPPLIED)
DO NOT
USE REAR
CONDUIT
ENTRY
BLANK SINGLEGANG
SWITCHPLATE
(USER SUPPLIED)
ORG BLKGRNORG RED
ALL CONNECTIONS ARE POWER LIMITED
EARTH
GNDLINE
2
LINE
1
8701

Other Faraday Control Unit manuals

Faraday 8709 User manual

Faraday

Faraday 8709 User manual

Faraday 8706 User manual

Faraday

Faraday 8706 User manual

Faraday 8702 User manual

Faraday

Faraday 8702 User manual

Faraday MPC-6000 User manual

Faraday

Faraday MPC-6000 User manual

Faraday 8705 User manual

Faraday

Faraday 8705 User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.