Fenwal 35-65 Series User manual

#$!"
n
Safe start an full-time flame sensing
n
120/240 fiel selectable line voltage for use
with 120 VAC ignitor option
n
24/120/240 VAC hot surface ignitor mo els available
n
Blower control an airflow switch monitoring option
n
Diagnostic LED
n
Multiple trials for ignition
n
Automatic reset option
n
Local or remote flame sensing
n
Flame current test pins
n
Dual spee blower option for LoNox applications
n
Fail-safe gas valve control (35-66 only)
n
CE mo els available
#"
n
Pool an spa heaters
n
Gas furnaces
n
Water heaters
n
Any 24 VAC gas burner application un er 400K BTU
"!#
The Series 35-65 and 35-66 controls are designed to perform many
gas-fired 24 VAC appliance functions in a single control, resulting
in lower system cost. This series monitors the demand for heat,
controls the combustion blower, monitors proper airflow, ignites and
maintains the flame during heating, and provides diagnostic support.
The on-board diagnostics with LED output provide assistance with
troubleshooting and ensures safe and efficient burner operation.
The microprocessor circuit design provides precise, repeatable
timing sequences for ignition and purge times (pre-, inter-, and post-)
as well as multiple tries for ignition. The optional 120/240 VAC field
selectable line voltage capability provides additional field service
efficiency and lower inventory costs.
A ency Certifications
Design certified by CSA International to
CAN C22.2 #199-M89 and ANSI Z21.20
for Automatic Ignition Systems, including
UL1998 software review. M approval
and CE pending on selected models.
SERIES 35-65 & 35-66
24 VAC Microprocessor Based HSI Control
with 120/240 Field Selectable Line Volta e Capability
www.fenwalcontrols.com 1-800- ENWAL-1 Series 35-65, -66 HSI Control with 120/240 ield Selectable Line Voltage Page 1
35-65,-66.02
"
!2/5%+)
633)15
%4!%/7)
20&645-21/28)3
2()/21/9
2563*%')/)0)15
!#
#
$"
"
Control: 18 to 30 VAC 50/60 Hz
(Class 2 Transformer)
Line: 24, 120 or 240 VAC
(L1 & L2 only)
300 mA max @ 24 VAC with blower and gas
valve relay energized (Control only)
2.0A max @ 24 VAC
3.0 LA max @ 120 VAC (1/4 hp)
1.5 LA max @ 240 VAC (1/4 hp)
5.0A max @ 120/240 VAC
-40º to +176º (-40ºC to +80ºC)
0.7 microamps minimum
Natural, LP, or manufactured
24 VAC, 120 VAC, or 240 VAC
mini-ignitors and silicon carbide ignitors
depending on model
Gray (Noryl N-190)
Conformal coated to operate non-condensing
to 95% R.H. Care must be taken to protect
module from direct exposure to water
See igures on Page 7
8 oz including cover
"#"
®
DS 35 65 66:DS 35 65 66.qxd 9/27/2010 9:08 AM Page 1

" #
8-5,6//-0)28)32()/421/9
Upon applying power (24 volts) to the R terminal, the control will
reset, perform a self-check routine, flash the diagnostic LED for a
second and enter the thermostat scan state.
8-5,2656//-0)28)3)30-1%/
When a call for heat is received from the thermostat supplying 24
volts to the W terminal, the control will perform a self-check routine,
flash the diagnostic LED for a second and begin the safety timing
sequence. After an optional "pre-purge" period, the hot
surface ignitor is energized for a heat-up period, followed by the
gas valve for the "trial for ignition" (T I) period.
%//*23)%52()/4
In addition to the self-check routine described above, when a call
for heat is received from the thermostat supplying 24 volts to the
W terminal, the control will check the pressure switch for normally
open contacts. The combustion blower is then energized and,
once the pressure switch contacts close, an optional "pre-purge"
period begins. After pre-purge, the hot surface ignitor is energized
for a heat-up period, followed by the gas valve for the "trial for
ignition" (T I) period.
+1-5-212()/4
When the flame is detected during the T I period, the ignitor is
de-activated and the gas valve remain energized. The thermostat
and main burner flame are constantly monitored to assure that the
system operates properly. When the thermostat is satisfied and the
demand for heat ends, the gas valve is immediately de-energized.
+1-5-212()/4
When the flame is detected during the T I period, the ignitor is
de-activated and the gas valve and combustion blower remains on.
The thermostat, pressure switch and main burner flame are
constantly monitored to assure that the system operates properly.
When the thermostat is satisfied and the demand for heat ends,
the gas valve is immediately de-energized, the control senses the
loss of flame signal and initiates an optional "post-purge" period
before de-energizing the combustion blower.
-1+/)392()/4
Should the main burner fail to light or the flame is not detected
during the T I period, the control will lockout. The gas valve
will be turned off immediately. or 35-66 models, the combustion
blower will be turned off following an optional "post-purge"
period. With the 1 hour reset option, if the thermostat is still
calling for heat, the control will automatically reset and attempt
a new T I sequence after one hour.
(continue ):
6/5-5392()/4
Should the main burner fail to light or the flame is not detected
during the first T I period, the gas valve is de-energized and
the control performs an optional "inter-purge" delay before
attempting another T I period. The control will attempt 2
additional T I's periods before locking out. In lockout, the
gas valve will be turned off immediately. or 35-66 models, the
combustion blower will be turned off following an optional
"post-purge" period. With the 1 hour reset option, if the
thermostat is still calling for heat, the control will automatically
reset and attempt a new T I sequence after one hour.
2'.265)'27)39
Recovery from lockout requires a manual reset by either
resetting the thermostat or by removing the 24 volts for a period
of 5 seconds.
2442*/%0))-+15-21
If the established flame signal is lost while the burner is operating,
the control will respond within 0.8 seconds. The gas valve is de-
energized immediately and a new T I sequence begins. If the
burner does not relight, the control will lockout as previously
described in the " ailure to Light - Lockout" section. Multi-try
models will make 2 more attempts to light the burner. If flame is
re-established, normal operation resumes.
"
2()/421/9
1. Combustion airflow is continually monitored during the ignition
sequence by the pressure switch (PSW terminal). If the pressure
switch contacts remain closed for 30 seconds at the start of the
ignition sequence without an output signal to the combustion blower,
an airflow fault is signaled and the control will remain in this fault
mode with the combustion blower off. If the pressure switch
contacts later open while there is still a call for heat, the control
begins the pre-purge period followed by a normal T I sequence.
2. If the pressure switch contacts remain open for more than 30
seconds after the combustion blower output ( 1 and 2 terminals)
is energized, an airflow fault is signaled and the control will remain
in this fault mode with the combustion blower on. If proper airflow
is later detected from the pressure switch input (PSW terminal),
the control begins the pre-purge period followed by a normal
T I sequence.
3. If the airflow signal is lost while the burner is firing, the control
will immediately de-energize the gas valve and an airflow fault is
signaled. The combustion blower will remain on for the post-purge
period and the control continues to monitor the PSW input waiting
for airflow to return. If proper airflow is detected during the
post-purge period, a normal T I sequence begins preceded by
any pre-purge period. If not, the control will enter a lockout
condition with the combustion blower off.
" $!#!%!("#($#
Page 2 Series 35-65, -66 HSI Control with 120/240 ield Selectable Line Voltage www.fenwalcontrols.com 1-800- ENWAL-1
DS 35 65 66:DS 35 65 66.qxd 9/27/2010 9:08 AM Page 2

Internal Control ailure
Airflow ault (35-66 models)
Erroneous lame Signal
Lockout
$#&!
The 35-65 and 35-66 models are not position sensitive and can be
mounted vertically or horizontally. The control may be mounted on
any surface and fastened with #6 sheet metal screws. Secure the
control in an area that will experience a minimum of vibration and
remain below the maximum ambient temperature of 80°C (175º ).
All connections should be made with UL approved, 105°C (221° )
rated 18 gauge, stranded wire with .054" minimum insulation.
Refer to wiring diagram on Pages 5 or 6 when connecting the
control to other components in the system.
#
2)412545%35
,)30245%52112-+1-5-21
!%/7)2112-+1-523
+1-52321127%/7)
/%0)2.%9(63-1+
12*/%0)4)14)%*5)3
Steady On
1 lash
2 lashes
3 lashes
A. Miswired
B. 24 VAC Transformer bad
C. use/Circuit breaker bad
D. Bad control, check LED for steady
on or flashing codes
A. Miswired
B. Bad thermostat, no voltage
at thermostat terminal W
C. ailed ignitor
A. Defective ignitor
B. Miswired
C. Bad control, check voltage at ignitor
A. Valve coil open
B. Open valve wire
C. Bad control, check voltage at gas
valve terminal
A. Bad ignitor
B. Bad S1 wire
C. Poor ground at burner
D. Poor flame, check flame current
24 VAC supply to processor
(optional full time power)
Thermostat Input
120/240VAC Input (Hot)
Neutral
System Ground
Gas Valve
Remote lame Sense
120 VAC Ignitor
Ignitor
240 VAC Ignitor
lame Current Test Pins
2()/41/9
Blower Output
Blower Output
Pressure Switch Input
R
W
L1
L2
GND
GV
S
S1 - 120
S2
S1 - 240
C+ & C-
1
2
PSW
¼ in. Quick Connect
¼ in. Quick Connect
¼ in. Quick Connect
(or 5-pin Mate-N-Loc)
¼ in. Quick Connect
(or 5-pin Mate-N-Loc)
¼ in. Quick Connect
3/16 in. Quick Connect
¼ in. Quick Connect
¼ in. Quick Connect
(or 5-pin Mate-N-Loc)
¼ in. Quick Connect
(or 5-pin Mate-N-Loc)
¼ in. Quick Connect
¼ in. Quick Connect
(or 2-pin Mate-N-Loc)
¼ in. Quick Connect
(or 2-pin Mate-N-Loc)
¼ in. Quick Connect
#!$"#$
Terminal Desi nations
5
Label all wires prior to disconnection when servicing the control.
Wiring errors can cause improper and dangerous operation.
5
Operation outside specifications could result in failure of the
enwal product and other equipment with injury or death to people
and damage to property. Service to this product should only be
performed by a qualified technician.
/%0)%6/56//-0)28)32()/41/9
During normal sequence if an erroneous flame signal occurs,
due to the gas valve failing to close completely, the controller will
energize the combustion blower. Should the gas valve later close
completely and the flame signal be removed, the combustion
blower will power off following an optional post-purge period.
""!$!!#
lame current is the current that passes through the flame from
the sensor to ground. The minimum flame current necessary to
keep the system from lockout is 1 microamp. To measure flame
current, connect an analog DC microammeter to the C terminals
per diagram below. Meter should read 1 microamp or higher.
If meter reads below "0" on scale, meter leads are reversed.
Disconnect power and reconnect meter leads for proper polarity
www.fenwalcontrols.com 1-800- ENWAL-1 Series 35-65, -66 HSI Control with 120/240 ield Selectable Line Voltage Page 3
DS 35 65 66:DS 35 65 66.qxd 9/27/2010 9:08 AM Page 3

#!&!!""
Select the proper harness based on the 35-65 and 35-66 control's termination connection on back page. Once the terminal configuration is
determined, complete the part number by replacing the last two digits ("XX") with the length in inches ("l" dimension). Standard wire lengths
are 12, 18, 24 30, 36 and 48 inches. Example 05-129845-018 = 18 inches. or other lengths, please contact enwal
Page 4 Series 35-65, -66 HSI Control with 120/240 ield Selectable Line Voltage www.fenwalcontrols.com 1-800- ENWAL-1
)6892*,6''
)6892*,6'''
)6892*,6
)6892*,6
!#""!"
Custom configurations
are available
Custom configurations
are available
DS 35 65 66:DS 35 65 66.qxd 9/27/2010 9:08 AM Page 4

www.fenwalcontrols.com 1-800- ENWAL-1 Series 35-65, -66 HSI Control with 120/240 ield Selectable Line Voltage Page 5
&!!""!"
35-65
35-65
DS 35 65 66:DS 35 65 66.qxd 9/27/2010 9:08 AM Page 5

&!!""!"
Page 6 Series 35-65, -66 HSI Control with 120/240 ield Selectable Line Voltage www.fenwalcontrols.com 1-800- ENWAL-1
35-66
35-66
DS 35 65 66:DS 35 65 66.qxd 9/27/2010 9:08 AM Page 6

www.fenwalcontrols.com 1-800- ENWAL-1 Series 35-65, -66 HSI Control with 120/240 ield Selectable Line Voltage Page 7
"""!"
!"
DS 35 65 66:DS 35 65 66.qxd 9/27/2010 9:08 AM Page 7

400 MAIN S REE , ASHLAND, MA 01721
EL: (508) 881-2000 FAX: (508) 881-6729
www.fenwalcontrols.com
© 2003 Kidde-Fenwal Printed in U.S.A. AG
hese instructions do not purport to cover all the details or variations in the equipment
described, nor do they provide for every possible contingency to be met in connection with
installation, operation and maintenance. All specifications are subject to change without notice.
Should further information be desired or should particular problems arise which are not covered
sufficiently for the purchaser’s purposes, the matter should be referred to KIDDE-FENWAL,
Inc., Ashland, Massachusetts.
P/N 35.65, 66.02 6/20/03
®
Page 8 Series 35-65, -66 HSI Control with 120/240 ield Selectable Line Voltage www.fenwalcontrols.com 1-800- ENWAL-1
#!$!#
- X X X
#60)146.308043
1 = 4 Seconds
3 = 7 Seconds
5 = 10 Seconds
7 = 15 Seconds
38,696.,
0 = None
1 = 15 Seconds
2 = 30 Seconds
6,96.,
0 = None
1 = 15 Seconds
2 = 30 Seconds
#60,746.308043
0 = Single Try without Automatic Reset
1 = Single Try with 1 Hour Automatic Reset
5 = Three Tries without Automatic Reset
6 = Three Tries with 1 Hour Automatic Reset
31;414:,6!,1);#,6203)8043464+,17
0 = ALL Q.C. Terminals Without ull Time Power (W Only)
1 = Mate-N-Loc (5 Pos.) with Q.C. Terminals without ull Time Power (W Only)
2 = Mate-N-Loc (2 Pos.) with Q.C. Terminals without ull Time Power (W Only)
5 = ALL Q.C. Terminals with ull Time Power (R Terminal)
6 = Mate-N-Loc (5 Pos.) with Q.C. Terminals with ull Time Power (R Terminal)
31;&08/14:,6!,1);#,6203)8043)3+47896.,-464+,17
0 = No Post-Purge All Q.C. Terminals without ull Time POWER (W Only)
1 = No Post-Purge All Q.C. Terminals with ull Time POWER (R Terminal)
2 = 30 Second Post-Purge All Q.C. Terminals *
3 = 60 Second Post-Purge All Q.C. Terminals *
5 = No Post-Purge Mate-N-Loc (5 Pos.) with Q.C. Terminals without ull Time Power (W Only)
6 = No Post-Purge Mate-N-Loc (5 Pos.) with Q.C. Terminals with ull Time Power (R Terminal)
7 = 30 Second Post-Purge Mate-N-Loc (5 Pos.) with Q.C. Terminals *
8 = 60 Second Post-Purge Mate-N-Loc (5 Pos.) with Q.C. Terminals *
* Post-Purge Requires ull Time Power (R)
.30846580437
0 = 120/240 VAC Mini-Ignitor (6 Second Heat-Up)
2 = 24 VAC Mini-Ignitor (4 Second Heat-Up) CE Approved
5 = 120/240 VAC Ignitor (20 Second Heat-Up)
6 = 120/240 VAC Ignitor (40 Second Heat-Up)
7 = 24 VAC Mini-Ignitor (4 Second Heat-Up)
97842,70.37"8)3+)6+)6892*,643-0.96)80434,748551;
3 = Customer Special eatures CE Approved (Refer To Drawing)
8 = Aftermarket Kit (Refer To Drawing)
9 = Customer Special eatures (Refer To Drawing)
58043)1,)896,7
1 = Dual Speed Blower (35-66 Model Only)
2 = 120/240 ield Selectable Line Voltage
3 = Dual Speed BLOWER AND 120/240 ield Selectable Line Voltage (35-66 Model Only)
5 = None
4+,1
5 = Without Combustion Blower Relay (Model 35-65)
6 = With Combustion Blower Relay (Model 35-66)
35 - 6X X XXX Description
DS 35 65 66:DS 35 65 66.qxd 9/27/2010 9:08 AM Page 8
This manual suits for next models
1
Table of contents
Other Fenwal Control Unit manuals
Popular Control Unit manuals by other brands

AUMA
AUMA SG 12.1 Operation instructions

CARDINAL DVM
CARDINAL DVM SYSWALL45 Series Assembly and Configuration Instructions

Aspen
Aspen LCM-Twin T38 Assembly, installation and operation instructions

Elan
Elan SIM2 manual

Lenze
Lenze E82ZAFVC010 Mounting instructions

KWC
KWC F5EF4003 Installation and operating instructions