FIBARO ROLLER SHUTTER 3 User manual

Fibaro
Roller Shutter 3
SKU: FIBEFGR-223
Quickstart
This is a secure Roller Shutter for Europe. To run this device please connect it to your mains
power supply. To add this device to your network execute the following action:
Quickly, triple click the S1 switch.
Important safety information
Please read this manual carefully. Failure to follow the recommendations in this manual may be
dangerous or may violate the law. The manufacturer, importer, distributor and seller shall not be
liable for any loss or damage resulting from failure to comply with the instructions in this manual
or any other material. Use this equipment only for its intended purpose. Follow the disposal
instructions. Do not dispose of electronic equipment or batteries in a fire or near open heat
sources.
What is Z-Wave?
Z-Wave is the international wireless protocol for communication in the Smart Home. This device
is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by
reconfirming every message (two-way
communication) and every mains powered node
can act as a repeater for other nodes (meshed
network) in case the receiver is not in direct
wireless range of the transmitter.
This device and every other certified Z-Wave
device can be used together with any other
certified Z-Wave device regardless of brand
and origin as long as both are suited for the same frequency range.
If a device supports secure communication it will communicate with other devices secure as
long as this device provides the same or a higher level of security. Otherwise it will
automatically turn into a lower level of security to maintain backward compatibility.
For more information about Z-Wave technology, devices, white papers etc. please refer to
www.z-wave.info.
Product Description
FIBARO Roller Shutter 3 is a device designed to control roller blinds, awnings,
venetian blinds, gates and other single phase, AC powered devices.
Roller Shutter 3 allows precise positioning of roller blinds or venetian blind lamellas.
The device is equipped with power and energy monitoring. It allows to control
connected devices either via the Z-Wave network or via a switch connected directly to it.
Prepare for Installation / Reset
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory default state.
Please make sure to reset the device into factory default. You can do this by performing an
Exclusion operation as described below in the manual. Every Z-Wave controller is able to
perform this operation however it is recommended to use the primary controller of the previous
network to make sure the very device is excluded properly from this network.
Reset to factory default
This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.
1. Press and hold the B-button to enter the menu.

2. Wait for the LED indicator to glow yellow.
3. Quickly release and click the B-button again.
4. After few seconds the device will be restarted, which is signalled with the red LED
indicator color.
Safety Warning for Mains Powered Devices
ATTENTION: only authorized technicians under consideration of the country-specific
installation guidelines/norms may do works with mains power. Prior to the assembly of the
product, the voltage network has to be switched off and ensured against re-switching.
Installation
Installation with standard blinds:
Notes for the diagrams:
S1 – terminal for 1st switch (used to add/remove the device)
S2 – terminal for 2nd switch
Q2 – 2nd output terminal for shutter motor DOWN
Q1 – 1st output terminal for shutter motor UP

L– terminal for live lead
N– terminal for neutral lead
B– service button (used to add/remove the device and navigate the menu)
Installation of blinds with built-in driver
Installation of gate motors
Installation of the gate driver may be performed only by certified professionals.
The motor must be equipped with the appropriate limit switches.
It is recommended to connect a NC (normally closed) contact of an IR barrier to S2
terminal. Opening the contact will stop the gate.
In addition, it is recommended to connect an emergency stop button to the motors neutral
(N) wire. In emergency, pushing the emergency stop button will cut the power and stop
the gate.

Calibration
Calibration is a process during which a device learns the position of the limit switches and a
motor characteristic.
Calibration is mandatory in order for the device to correctly recognize a roller blind position.
The procedure consists of an automatic, full movement between the limit switches (up, down,
and up again).
Note: If you notice the calibration process fail (e.g. it does not start, movement times are really
short or highly inaccurate), adjust parameter 155 value (e.g. reduce it by half).
Standard roller blind positioning
Calibration using a connected momentary switch
1. Make sure:
othe device is supplied,
othe momentary switch is connected to S1 and S2 terminals,

othe device added to the Z-Wave network,
oparameter 151 is set to 1 or 2.
2. Press and hold UP or DOWN switch for at least 3 seconds
3. Press and hold the same switch again for at least 3 seconds.
4. Press and hold the same switch again for at least 3 seconds.
5. The device will perform the calibration process, completing full cycle – up, down and up
again.
6. Test whether the positioning works correctly.
Calibration using the B-button
1. Make sure:
othe device is supplied,
othe device added to the Z-Wave network,
oparameter 151 is set to 1 or 2.
2. Press and hold the B-button.
3. Wait for the LED to glow white.
4. Quickly release and click the B-button again.
5. The device will perform the calibration process, completing full cycle – up, down and up
again
6. Test whether the positioning works correctly.
Calibration using parameter
1. Make sure:
othe device is supplied,
othe device added to the Z-Wave network,
oparameter 151 is set to 1 or 2.
2. Set the parameter 150 value to 2
3. The device will perform the calibration process, completing full cycle – up, down and up
again
4. The parameter 150 value will be set to 1 after calibration finishes.
5. Test whether the positioning works correctly.
Slats positioning in Venetian blinds mode
Calibration using a connected momentary switch
1. Make sure:
othe device is supplied,
othe momentary switch is connected to S1 and S2 terminals,
othe device added to the Z-Wave network,
oparameter 151 is set to 2,

oblinds are calibrated.
2. By default, time of transition between extreme positions is set to 150 (1.5 seconds) in
parameter 152.
3. Turn slats between extreme positions by holding UP or DOWN switch:
oIf after full cycle a blind starts moving up or down – decrease the value of
parameter 152,
oIf after full cycle the slats do not reach end positions – increase the value of
parameter 152,
4. Repeat the previous step until satisfactory positioning is achieved.
5. Test whether the positioning works correctly. Correctly configured slats should not force
the blinds to move up or down.
Roller blind with built-in driver positioning
1. Make sure:
othe device is supplied,
othe momentary switch is connected to S1 and S2 terminals,
othe device added to the Z-Wave network,
oparameter 151 is set to 5 or 6.
2. By default, time of transition between extreme positions is set to 600 (6 seconds) in
parameters 155 and 156.
3. Move roller blinds between extreme positions by clicking UP or DOWN switch:
oIf roller blind stops before reaching top – increase the value of parameter 155,
oIf roller blind does not stop after reaching top – decrease the value of parameter
155,
oIf roller blind stops before reaching bottom – increase the value of parameter
156,
oIf roller blind does not stop after reaching bottom – decrease value of parameter
156,
4. Repeat the previous step until satisfactory positioning is achieved.
5. Test whether the positioning works correctly.
Inclusion/Exclusion
On factory default the device does not belong to any Z-Wave network. The device needs to be
added to an existing wireless network to communicate with the devices of this network. This
process is called Inclusion.
Devices can also be removed from a network. This process is called Exclusion. Both processes
are initiated by the primary controller of the Z-Wave network. This controller is turned into
exclusion respective inclusion mode. Inclusion and Exclusion is then performed doing a special
manual action right on the device.
Inclusion
Quickly, triple click the S1 switch.

Exclusion
Quickly, triple click the S1 switch.
Product Usage
Range test
To make Z-Wave range test possible, the device must be added to the Z-Wave controller. Testing
may stress the network, so it is recommended to perform the test only in special cases.
The device has a built in Z-Wave network main controller’ s range tester.
Follow the below instructions to test the main controller’ s range:
1. Switch off the mains voltage (disable the fuse).
2. Remove the device from the wall switch box.
3. Switch on the mains voltage.
4. Press and hold the B-button to enter the menu.
5. Wait for the visual LED indicator to glow violet.
6. Quickly release and click the B-button again.
7. Visual indicator will indicate the Z-Wave network’ s range (range signalling modes
described below).
8. To exit Z-Wave range test, click the B-button.
Note: Communication mode of the device may switch between direct and one using routing,
especially if the device is on the limit of the direct range.
Z-Wave range tester signaling modes:
Visual indicator pulsing green – the device attempts to establish a direct communication with
the main controller. If a direct communication attempt fails, the device will try to establish a
routed communication, through other modules, which will be signalled by visual indicator
pulsing yellow.
Visual indicator glowing green – the device communicates with the main controller directly.
Visual indicator pulsing yellow – the device tries to establish a routed communication with the
main controller through other modules (repeaters).
Visual indicator glowing yellow – the device communicates with the main controller through the
other modules. After 2 seconds the device will retry to establish a direct communication with the
main controller, which will be signalled with visual indicator pulsing green.

Visual indicator pulsing violet – the device does communicate at the maximum distance of the
Z-Wave network. If connection proves successful it will be confirmed with a yellow glow. It’ s
not recommended to use the device at the range limit.
Visual indicator glowing red – the device is not able to connect to the main controller directly or
through another Z-Wave network device (repeater).
Menu
Menu allows to perform Z-Wave network actions. In order to use the menu:
1. Switch off the mains voltage (disable the fuse).
2. Remove the device from the wall switch box.
3. Switch on the mains voltage.
4. Press and hold the B-button to enter the menu.
5. Wait for the LED to indicate the desired menu position with colour:
oWHITE – start calibration
oGREEN – reset energy consumption memory
oVIOLET – start range test
oYELLOW – reset the device
6. Quickly release and click the B-button again.
Quick trouble shooting
Here are a few hints for network installation if things dont work as expected.
1. Make sure a device is in factory reset state before including. In doubt exclude before
include.
2. If inclusion still fails, check if both devices use the same frequency.
3. Remove all dead devices from associations. Otherwise you will see severe delays.
4. Never use sleeping battery devices without a central controller.
5. Dont poll FLIRS devices.
6. Make sure to have enough mains powered device to benefit from the meshing
Association - one device controls an other device
Z-Wave devices control other Z-Wave devices. The relationship between one device controlling
another device is called association. In order to control a different device, the controlling device
needs to maintain a list of devices that will receive controlling commands. These lists are called
association groups and they are always related to certain events (e.g. button pressed, sensor
triggers, ...). In case the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a 'Basic Set' Command.
Association Groups:

Group Number
Maximum Nodes
Description
1
1
Lifeline
2
5
Roller Shutter
3
5
Slats position control
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however certain
configuration can adapt the function better to user needs or unlock further enhanced features.
IMPORTANT: Controllers may only allow configuring signed values. In order to set values in
the range 128 ... 255 the value sent in the application shall be the desired value minus 256. For
example: To set a parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may needed to be
given as negative values too.
Parameter 20: Switch type
This parameter defines as what type the device should treat the switch connected to the S1 and
S2 terminals.
This parameter is not relevant in gate operating modes (parameter 151 set to 3 or 4). In this case
switch always works as a momentary and has to be connected to S1 terminal.
Size: 1 Byte, Default Value: 2
Setting
Description
0
momentary switches
1
toggle switches
2
single, momentary switch (the switch should be connected to S1 terminal)
Parameter 24: Inputs orientation
This parameter allows reversing the operation of switches connected to S1 and S2 without
changing the wiring.
Size: 1 Byte, Default Value: 0
Setting
Description
0
default (S1 – 1st channel, S2 – 2nd channel)
1
reversed (S1 – 2nd channel, S2 – 1st channel)
Parameter 25: Outputs orientation

This parameter allows reversing the operation of Q1 and Q2 without changing the wiring (in
case of invalid motor connection) to ensure proper operation.
Size: 1 Byte, Default Value: 0
Setting
Description
0
default (Q1 – 1st channel, Q2 – 2nd channel)
1
reversed (Q1 – 2nd channel, Q2 – 1st channel)
Parameter 30: Alarm configuration - 1st slot
This parameter determines to which alarm frames and how the device should react. The
parameters consist of 4 bytes, three most significant bytes are set according to the official Z-
Wave protocol specification.
For a setting of this parameter, please refer to the manufacturer‘ s manual.
Size: 4 Byte, Default Value: 0
Setting
Description
Parameter 31: Alarm configuration - 2nd slot (Water)
This parameter determines to which alarm frames and how the device should react. The
parameters consist of 4 bytes, three most significant bytes are set according to the official Z-
Wave protocol specification.
For a setting of this parameter, please refer to the manufacturer‘ s manual.
Size: 4 Byte, Default Value:
Setting
Description
Parameter 32: Alarm configuration - 3rd slot (Smoke)
This parameter determines to which alarm frames and how the device should react. The
parameters consist of 4 bytes, three most significant bytes are set according to the official Z-
Wave protocol specification.
For a setting of this parameter, please refer to the manufacturer‘ s manual.
Size: 4 Byte, Default Value:
Setting
Description
Parameter 33: Alarm configuration - 4th slot (CO)
This parameter determines to which alarm frames and how the device should react. The
parameters consist of 4 bytes, three most significant bytes are set according to the official Z-
Wave protocol specification.For a setting of this parameter, please refer to the manufacturer‘ s
manual.

For a setting of this parameter, please refer to the manufacturer‘ s manual.
Size: 4 Byte, Default Value:
Setting
Description
Parameter 35: Alarm configuration - 5th slot (Heat)
This parameter determines to which alarm frames and how the device should react. The
parameters consist of 4 bytes, three most significant bytes are set according to the official Z-
Wave protocol specification.
Size: 4 Byte, Default Value:
Setting
Description
Parameter 40: S1 switch - scenes sent
This parameter determines which actions result in sending scene IDs assigned to them.
Size: 1 Byte, Default Value: 0
Setting
Description
1
Key pressed 1 time
2
Key pressed 2 times
4
Key pressed 3 times
8
Key hold down and key released
15
All
Parameter 42: S2 switch - scenes sent
This parameter determines which actions result in sending scene IDs assigned to them.
Size: 1 Byte, Default Value: 0
Setting
Description
1
Key pressed 1 time
2
Key pressed 2 times
4
Key pressed 3 times
8
Key hold down and key released
15
All
Parameter 60: Measuring power consumed by the device itself
This parameter determines whether the power metering should include the amount of active
power consumed by the device itself.
Size: 1 Byte, Default Value: 0

Setting
Description
0
function inactive
1
function active
Parameter 61: Power reports - on change
This parameter determines the minimum change in consumed power that will result in sending
new power report to the main controller.
For loads under 50W, the parameter is not relevant and reports are sent every 5W change.
Power reports are sent no often than every 30 seconds.
Size: 2 Byte, Default Value: 15
Setting
Description
0
reports are disabled
1 - 500
change in power in %
Parameter 62: Power reports - periodic
This parameter determines in what time intervals the periodic power reports are sent to the main
controller. Periodic reports do not depend on power change (parameter 61).
Size: 2 Byte, Default Value: 3600
Setting
Description
0
periodic reports are disabled
30 - 32400
report interval in seconds
Parameter 65: Energy reports - on change
This parameter determines the minimum change in consumed energy that will result in sending
new energy report to the main controller.
Size: 2 Byte, Default Value: 10
Setting
Description
0
reports are disabled
1 - 500
(0.01 – 5 kWh) – change in energy
Parameter 66: Energy reports - periodic
This parameter determines in what time intervals the periodic energy reports are sent to the
main controller. Periodic reports do not depend on energy change (parameter 65).
Size: 2 Byte, Default Value: 3600
Setting
Description

0
periodic reports are disabled
30 - 32400
report interval in seconds
Parameter 150: Force calibration
By setting this parameter to 2 the device enters the calibration mode. The parameter relevant
only if the device is set to work in positioning mode (parameter 151 set to 1, 2 or 4).
Size: 1 Byte, Default Value: 0
Setting
Description
0
device is not calibrated
1
device is calibrated
2
force device calibration
Parameter 151: Operating mode
This parameter allows adjusting operation according to the connected device.
Size: 1 Byte, Default Value: 1
Setting
Description
1
roller blind (with positioning)
2
Venetian blind (with positioning)
3
gate (without positioning)
4
gate (with positioning)
5
roller blind with built-in driver
6
roller blind with built-in driver (impulse)
Parameter 152: Venetian blind - time of full turn of the slats
For Venetian blinds (parameter 151 set to 2) the parameter determines time of full turn cycle of
the slats.
For gates (parameter 151 set to 3 or 4) the parameter determines time after which open gate will
start closing automatically (if set to 0, gate will not close).
The parameter is irrelevant for other modes.
Size: 5 Byte, Default Value: 150
Setting
Description
0 - 90000
(0 – 900s, every 0.01s) – time of turn
Parameter 153: Set slats back to previous position
For Venetian blinds (parameter 151 set to 2) the parameter determines slats positioning in
various situations.

The parameter is irrelevant for other modes.
Size: 1 Byte, Default Value: 1
Setting
Description
0
slats return to previously set position only in case of the main controller operation.
1
slats return to previously set position in case of the main controller operation,
momentary switch operation, or when the limit switch is reached.
2
slats return to previously set position in case of the main controller operation,
momentary switch operation, when the limit switch is reached or after receiving the
Switch Multilevel Stop control frame
Parameter 154: Delay motor stop after reaching end switch
For blinds (parameter 151 set to 1, 2, 5 or 6) the parameter determines the time after which the
motor will be stopped after end switch contacts are closed.
For gates (parameter 151 set to 3 or 4) the parameter determines the time after which the gate
will start closing automatically if S2 contacts are opened (if set to 0, gate will not close).
Size: 2 Byte, Default Value: 10
Setting
Description
0 - 60
(0 – 60s) – time
Parameter 155: Motor operation detection
Power threshold to be interpreted as reaching a limit switch.
Size: 2 Byte, Default Value: 10
Setting
Description
0
reaching a limit switch will not be detected
1 - 255
report interval in watt
Parameter 156: Time of up movement
This parameter determines the time needed for roller blinds to reach the top.
For modes with positioning value is set automatically during calibration, otherwise, it must be
set manually.
Size: 4 Byte, Default Value: 6000
Setting
Description
1 - 90000
(0.01 – 900.00s, every 0.01s) – movement time
Parameter 157: Time of down movement

This parameter determines time needed for roller blinds to reach the bottom.
For modes with positioning value is set automatically during calibration, otherwise, it must be
set manually.
Size: 4 Byte, Default Value: 6000
Setting
Description
1 - 90000
(0.01 – 900.00s, every 0.01s) – movement time
Technical Data
Dimensions
42.50 x 38.25 x 20.30 mm
Weight
27.83 gr
EAN
5905279987197
IP Class
IP 20
Voltage
230 V
Load
1,7 A
Device Type
Roller Shutter
Generic Device Class
Multilevel Switch
Specific Device Class
Motor Control Device (B)
Firmware Version
05.00
Z-Wave Version
06.02
Z-Wave Product Id
0x010f.0x0303.0x1000
Frequency
Europe - 868,4 Mhz
Maximum transmission power
5 mW
Supported Command Classes
Basic
Application Status
Switch Multilevel
Meter
Crc 16 Encap
Association Grp Info
Device Reset Locally
Central Scene
Zwaveplus Info
Multi Channel
Supervision
Configuration
Alarm
Manufacturer Specific
Powerlevel

Protection
Firmware Update Md
Association
Version
Multi Channel Association
Security
Transport Service
Security 2
Controlled Command Classes
Transport Service
Security 2
Explanation of Z-Wave specific terms
Controller —is a Z-Wave device with capabilities to manage the network. Controllers
are typically Gateways,Remote Controls or battery operated wall controllers.
Slave —is a Z-Wave device without capabilities to manage the network. Slaves can be
sensors, actuators and even remote controls.
Primary Controller —is the central organizer of the network. It must be a controller.
There can be only one primary controller in a Z-Wave network.
Inclusion —is the process of adding new Z-Wave devices into a network.
Exclusion —is the process of removing Z-Wave devices from the network.
Association —is a control relationship between a controlling device and a controlled
device.
Wakeup Notification —is a special wireless message issued by a Z-Wave device to
announces that is able to communicate.
Node Information Frame —is a special wireless message issued by a Z-Wave device to
announce its capabilities and functions.
(c) 2019 Z-Wave Europe GmbH, Antonstr. 3, 09337 Hohenstein-Ernstthal, Germany, All rights
reserved, www.zwave.eu. The template is maintained by Z-Wave Europe GmbH. The product
of the product data: 2019-02-08 13:50:00
Other manuals for ROLLER SHUTTER 3
1
This manual suits for next models
1
Table of contents
Popular Window Blind manuals by other brands

Dometic
Dometic SKYSOL Oceanair Track Small 9600023478 Installation and operating manual

SelectBlinds
SelectBlinds OPEN ROLL Z-125 installation instructions

Blumfeldt
Blumfeldt 10030627 manual

Bali
Bali Horizontal Blinds How to install

The Shann Group
The Shann Group URBAN TRACK care guide

Betta
Betta VEUE installation manual

WAREMA
WAREMA Lamaxa L60 User instructions

rollease acmeda
rollease acmeda SKYLINE BOTTOM UP installation manual

Eclipse
Eclipse POWERSHADE MH005 Programming instructions

Victoria M
Victoria M MINI ROLLO installation instructions

Style selections
Style selections 70816 installation instructions

Outbound
Outbound RA Series installation manual