DF-51726 — Page 1 of 2
GENERAL
System Sensor 100 Series low-profile detectors use state-
of-the-art sensing chambers to meet all applicable UL per-
formance criteria. The backs of the smoke detectors are
sealed against back pressure, air flow, and dirt. A fine
mesh screen also protects the chamber against the entry
of insects. These detectors are intended for open area
protection and for use with UL-listed control panels.
Photoelectric/Thermal — The unique design of the
optical sensing chamber in 100 Series photoelectric smoke
detectors can sense smoke particles from a wide range of
combustion sources. These detectors minimize nuisance
alarms by using a custom integrated circuit for signal pro-
cessing.
FEATURES
• Smart-Check™ self-diagnostic maintenance feature to
satisfy NFPA 72 sensitivity testing requirements.
• Larger plug-in terminal block with captured SEMS screws
decreases wiring and installation time.
• Removable insect screen protects sensor from insects
and airborne dust.
• Includes auxiliary Form-C relay (“R” suffix).
• Built-in test switch.
• Visual alarm, power, and maintenance indicator.
• Refined insect screen for a tight seal; simplified,
removable for cleaning.
• Thermal models available.
• Ceiling white color.
• 12/24 VDC operation.
• Built-in sounder and temporal tone.
• Three-year warranty.
System Sensor 100 Series
low-profile, direct-wire detec-
tors pack superb performance and reliability into a small
package. Their sleek, 1.7" (43 mm) profile is the lowest in
the industry, and the advanced circuitry provides superior
false-alarm immunity, while reducing maintenance.
Other key features include:
• Low current draw.
• Stable performance in high air velocities.
• Built-in tamper-resistant base design.
SPECIFICATIONS
• Operating voltage: 12 or 24 VDC (nominal).
• Contact rating: 1 Form-C, 1.0 A @ 30 VDC.
• Standby current: 50 µA maximum average.
• Alarm current:
2-wire models:
100 mA maximum
limited by panel.
4-wire models:
12 VDC = 35 mA
maximum; 24 VDC = 45 mA maximum (
2112/24AITR:
60 mA maximum and 70 mA maximum respectively).
• Temperature range: 32°F to 120°F (0°C to 50°C).
For
2100TD, 2112/24TR models:
32°F to 100°F (0°C to
39°C).
• Dimensions: 5.5" (140 mm) diameter. Height 1.7" (43
mm) including adapter bracket.
• Shipping weight (approximate): 5.3 oz. (150 g).
• Humidity range: 10% - 93% RH, noncondensing.
• Smoke detector spacing: On smooth ceilings (as
defined in NFPA 72), spacing of 30 feet (900 sq.ft.) may
be used as a guideline. Other spacing may be used
depending on ceiling height, high air movements, and
other conditions or response requirements. Refer to
NFPA 72 and local authority having jurisdiction.
•Air velocity: 0 to 3,000 ft./min. (914.4 m/min.) maximum.
100 Series™ and Smart-Check™ are trademarks of System Sensor, a division of Pittway Corporation.
S911
100 Series™
Low-Profile Direct-Wire
Conventional Smoke Detectors
August 3, 1998 F-495
Section: Conventional Initiating Devices
7272-1209:159
(2100D, 2100TD)
California
State Fire
Marshal
2212/24T
100 Series
with Sounder
This document is not intended to be used for installation purposes. We try to keep our product
information up-to-date and accurate. We cannot cover all specific applications or anticipate all
requirements. All specifications are subject to change without notice. For more information,
contact Fire•Lite Alarms, One Fire-Lite Place, Northford, Connecticut 06472. Phone: (800) 627-
3473, Toll Free FAX: (877) 699-4105, FAX Back:(888) 388-3299
WEB: www.firelite.com
Page 2 of 2 —DF-51726
WIRING
DIAGRAMS
(TOP TO BOTTOM)
Figure 1:
2100D, 2100TD.
Figure 2:
2112/24R, 2112/24TR.
Figure 3: 2112/24ATR,
2112/24AITR.
Figure 1
Figure 2
Figure 3
PRODUCT LINE INFORMATION
2100D –Low-profile photoelectric smoke detector, two-wire, 12/24 VDC.
2100TD –Low-profile photoelectric with 135°F (57°C) thermal, two-wire, 12/24 VDC.
2100TR –Low-profile photoelectric with 135°F (57°C) thermal, two-wire, 12/24 VDC, auxiliary Form-C relay.
2100AT –Low-profile photoelectric with sounder and 135°F (57°C) thermal, two-wire, 12/24 VDC.
2112/24R –Low-profile photoelec-
tric smoke detector, four-wire, 12/24
VDC, auxiliary Form-C relay.
2112/24TR –Low-profile photo-
electric with 135°F (57°C) thermal,
four-wire, 12/24 VDC, auxiliary
Form-C relay.
2112/24ATR –Low-profile photo-
electric with sounder and 135°F
(57°C) thermal, four-wire, 12/24
VDC, auxiliary Form-C relay.
2112/24AITR –Low-profile photo-
electric with sounder and isolated
135°F (57°C) thermal, four-wire,
12/24 VDC, auxiliary Form-C relay.
A77-716B –EOL power supervi-
sion relay module for 12/24 VDC
smoke detectors.
MOD400R –Sensitivity
test tool for 100 Series
smoke detectors.
RR1 –Polarity-reversal re-
lay module for 2-wire or 4-
wire sounder models, acti-
vated by panel alarm out-
put.
RA400Z –Remote annun-
ciator, 7 mA, 3.1 - 32 VDC.

This manual suits for next models

1

Other Fire-Lite Alarms Smoke Alarm manuals

Fire-Lite Alarms BG-12LXSP User manual

Fire-Lite Alarms

Fire-Lite Alarms BG-12LXSP User manual

Fire-Lite Alarms D350PL User manual

Fire-Lite Alarms

Fire-Lite Alarms D350PL User manual

Fire-Lite Alarms BG-12L User manual

Fire-Lite Alarms

Fire-Lite Alarms BG-12L User manual

Fire-Lite Alarms BG-12 User manual

Fire-Lite Alarms

Fire-Lite Alarms BG-12 User manual

Fire-Lite Alarms OSI-RI-FL User manual

Fire-Lite Alarms

Fire-Lite Alarms OSI-RI-FL User manual

Fire-Lite Alarms BG-12LPS User manual

Fire-Lite Alarms

Fire-Lite Alarms BG-12LPS User manual

Fire-Lite Alarms 6424 User manual

Fire-Lite Alarms

Fire-Lite Alarms 6424 User manual

Fire-Lite Alarms BG-12LX User manual

Fire-Lite Alarms

Fire-Lite Alarms BG-12LX User manual

Fire-Lite Alarms OSI-RI-FL User manual

Fire-Lite Alarms

Fire-Lite Alarms OSI-RI-FL User manual

Fire-Lite Alarms BG-12LR User manual

Fire-Lite Alarms

Fire-Lite Alarms BG-12LR User manual

Fire-Lite Alarms 1400 User manual

Fire-Lite Alarms

Fire-Lite Alarms 1400 User manual

Fire-Lite Alarms D350P User manual

Fire-Lite Alarms

Fire-Lite Alarms D350P User manual

Popular Smoke Alarm manuals by other brands

ELRO PS4910 instruction manual

ELRO

ELRO PS4910 instruction manual

olympia electronics BS-506/ALKALINE quick start guide

olympia electronics

olympia electronics BS-506/ALKALINE quick start guide

Perel SSD01 manual

Perel

Perel SSD01 manual

EMC FC-610-001 installation guide

EMC

EMC FC-610-001 installation guide

Bosch FCS-320-TP Series Quick installation guide

Bosch

Bosch FCS-320-TP Series Quick installation guide

AROHA SM11R4 Quick reference guide

AROHA

AROHA SM11R4 Quick reference guide

Orientalert VST-WS588IH user manual

Orientalert

Orientalert VST-WS588IH user manual

Red Smoke Alarms R240RC installation instructions

Red Smoke Alarms

Red Smoke Alarms R240RC installation instructions

Solo 365 user manual

Solo

Solo 365 user manual

Nittan EVC-PY-IS instruction manual

Nittan

Nittan EVC-PY-IS instruction manual

U-Line H-9472 quick start guide

U-Line

U-Line H-9472 quick start guide

SONA Electronics SM-SN-1 Installation and user guide

SONA Electronics

SONA Electronics SM-SN-1 Installation and user guide

Inovonics EE1265 Installation and operation manual

Inovonics

Inovonics EE1265 Installation and operation manual

teko Astra-421 RF user guide

teko

teko Astra-421 RF user guide

jablotron JA-85ST quick start guide

jablotron

jablotron JA-85ST quick start guide

Eminent EM8690-R1 user manual

Eminent

Eminent EM8690-R1 user manual

BRK electronic P H O T O & I O N 3120B Technical specifications

BRK electronic

BRK electronic P H O T O & I O N 3120B Technical specifications

pyrexx PX-1C operating manual

pyrexx

pyrexx PX-1C operating manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.