manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. FireClass
  6. •
  7. Control Unit
  8. •
  9. FireClass FC410DIM User manual

FireClass FC410DIM User manual

TECHNICAL SPECIFICATION
Type Value: 146
System Compatibility: Use only with FC Fire Alarm Controllers
Environment: Indoor Application only
Operating Temperature: -25 to +70 oC
Storage Temperature: -40 to +80 oC
Operating Humidity: Up to 95% non-condensing
Dimensions (HxWxD): 87x148x14mm
Mounting Requirements: One FC backbox surface mount
Battery Requirements:
From Addressable Loop
Class B Standby Current: 0.28mA
From 24V (not including detector
load)
Class B Standby Current: 14.mA
Class B Alarm Current: 50mA for spur
24V Input Power Voltage Requirement:
26.4V max., 21.9V min. This allows for 0.9V max. voltage drop between the
power supply and the FC410DIM
Addressable Device Condi-
tions: – Normal
– Active
– Short Circuit wiring fault
– Open Circuit wiring fault
– PSU fault
– Device Type Invalid
– Device No Response
Detector Circuit:
Min. Detector Voltage: 16V dc
Max. Standby Detector Load per
FC410DIM Circuit: 3mA
Detector Circuit EOL: 4k7W
Max. Circuit Impedance: 50W
Recommended Wire Size: Min. 1.5 mm2Max. 2.5 mm2
INTRODUCTION
Installation of the FC410DIM comprises the following:
ØInstallation of cables.
ØCable continuity, Insulation and Resistance checks.
ØInstallation of ancillary devices and connection.
The Addressable FC410DIM provides the ability to connect and Interface
one or two zones of 24V dc 2-wire conventional detectors (non-address-
able) to the Fire Alarm Controller.
The FC410DIM monitors the status of detectors and wiring to detectors and
signals detector and wiring status back to the Controller.
FEATURES
The FC410DIM can be configured to:
ØMonitor 1 or 2 Class B spur circuits.
A Monitored Detector going into Alarm, on either spur circuit, will cause
FC410DIM to report the Alarm State back to the Controller.
Status LED provides status of all detectors monitored by the FC410DIM:
ØThe LED is normally off.
ØThe LED turns ON when a detector monitored by the FC410DIM has
gone into Alarm.
ØThe LED will pulse when the Controller polls the FC410DIM.
WIRING & INSTALLATION NOTES
The following notes apply:
1) There are no user-required settings on the FC410DIM.
2) All wiring must conform to the applicable standards.
3) All wiring must be free of earths.
4) Fit the PCB to the FC470CV cover.
5) Connect the wiring for the monitored circuit as shown in wiring diagrams.
6) When monitoring only one Class B circuit, terminate the unused circuit
with the proper EOL resistor.
7) Verify the correct polarity of wiring before connecting FC410DIM to the
addressable loop circuit.
+Refer to Fig.4.
1) If one spur circuit is used , the other circuit must be terminated by 4k7
EOL.
INSTALLATION TO FC470CV ANCILLARY COVER
1) Assemble the FC410DIM to FC470CV Double Gang cover, using the
four screw and washers provided.
2) Fit cover onto FC backbox.
ADDRESS SETTINGS
The FC410DIM has a default factory set address of 255, this must be set to
the loop address of the device using the FC490ST Loop Service Tool. The
FC410DIM may be programmed with the address prior to being installed by
using the internal programming port or after being installed by using the pro-
gramming port on the front cover (see Fig. 2 and Fig.3).
+Note: once the address has been programmed, take note of the device
location and address number, to include on site drawings.
+Note: this device use one address only on the loop.
CABLING
The maximum section of the cable that can be connected at any one termi-
nal is 2.5mm2. The section is calculated based on the characteristics of the
cable and the load.
ORDERING INFORMATION
FC410DIM: Detector Input Module
FC470CV: Double-Gang cover
RECYCLING INFORMATION
Customers are recommended to dispose of their used equipments (panels,
detectors, sirens, and other devices) in an environmentally sound manner.
Potential methods include reuse of parts or whole products and recycling of
products, components, and/or materials.
WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT (WEEE)
DIRECTIVE
In the European Union, this label indicates that this product
should NOT be disposed of with household waste. It should be
deposited at an appropriate facility to enable recovery and re-
cycling.
The manufacturer reserves the right to change the technical specifications
of this product without prior notice.
ENGLISH
www.acornfiresecurity.com
www.acornfiresecurity.com
PORTA DI PROGRAMMAZIONE
PROGRAMMING PORT
PROGRAMMIERANSCHLUSS
L+ L- L+ L- COM +24 A+ A- B+ B-
TB2 TB3
TB1
FIG. 2 FC410DIM fissata al coperchio
FC410DIM ins Gehäuse eingebaut
FC410DIM fitted to cover
PORTA DI PROGRAMMAZIONE
ADDRESS SETTING PORT
PROGRAMMIERAN
S
CHLU
SS
FIG. 3 FC410DIM Placca
Kurzschlussisolator Vorderseite
Facia Plate
FIG. 1 FC410DIM Modulo d'ingresso per rivelatori convenzionali
FC410DIM Detector Interface Module
FC Adapter fur Konventionelle Melder - FC410DIM
PORTA DI PROGRAMMAZIONE
PROG PORT
PROGRAMMIERSTECKER
ALIMENTATORE ESTERNO 24 Vcc
EXTERNAL POWER SUPPLY 24V d.c.
EXTERNE ENERGIEVERSORGUNG 24 VDC
CENTRALE FC
FC CONTROLLER
AL DISPOSITIVO SEGUENTE
TO NEXT DEVICE
ZUM NÄCHSTEN ELEMENT
+L1
-L1
LEFT
FIG. 4 Circuito SPUR (Classe B)
'Spur Circuit' (Class B)
Stich-Verdrahtung
www.acornfiresecurity.com
www.acornfiresecurity.com

Other FireClass Control Unit manuals

FireClass FC410SNM User manual

FireClass

FireClass FC410SNM User manual

FireClass FC410LI User manual

FireClass

FireClass FC410LI User manual

FireClass FC410RIM Manual

FireClass

FireClass FC410RIM Manual

FireClass FC430SAM User manual

FireClass

FireClass FC430SAM User manual

FireClass FC500MFI User manual

FireClass

FireClass FC500MFI User manual

FireClass FC500IP User manual

FireClass

FireClass FC500IP User manual

FireClass FC410LI User manual

FireClass

FireClass FC410LI User manual

FireClass FC500PSTN User manual

FireClass

FireClass FC500PSTN User manual

FireClass FC410BDM Quick start guide

FireClass

FireClass FC410BDM Quick start guide

Popular Control Unit manuals by other brands

pizzato CS MP302M0 manual

pizzato

pizzato CS MP302M0 manual

Highcross ECM-RS2D Quick reference guide

Highcross

Highcross ECM-RS2D Quick reference guide

Gascat BRISE PLUS Installation & operation manual

Gascat

Gascat BRISE PLUS Installation & operation manual

Apacer Technology EFC-D Series user manual

Apacer Technology

Apacer Technology EFC-D Series user manual

M-system R7L-EC16B instruction manual

M-system

M-system R7L-EC16B instruction manual

Icop VEX2-DIP168 user manual

Icop

Icop VEX2-DIP168 user manual

Nibe VVM 320 Installer manual

Nibe

Nibe VVM 320 Installer manual

BNC 106H instruction manual

BNC

BNC 106H instruction manual

MSA M1 operating manual

MSA

MSA M1 operating manual

ATEQ G6 Series manual

ATEQ

ATEQ G6 Series manual

Grundfos RSL instructions

Grundfos

Grundfos RSL instructions

Sencon BCM500 instruction manual

Sencon

Sencon BCM500 instruction manual

PT Coupling Maxi-Dry Disassembly instructions

PT Coupling

PT Coupling Maxi-Dry Disassembly instructions

ADTRAN Octal E&M user manual

ADTRAN

ADTRAN Octal E&M user manual

Richter KA-N/F Series Installation and operating manual

Richter

Richter KA-N/F Series Installation and operating manual

Nor-Cal Products Intellisys TBV-D Operator's manual

Nor-Cal Products

Nor-Cal Products Intellisys TBV-D Operator's manual

Festo CPX-E-1CI Instructions for use

Festo

Festo CPX-E-1CI Instructions for use

Allen-Bradley Rockwell Automation 1734-4IOL user manual

Allen-Bradley

Allen-Bradley Rockwell Automation 1734-4IOL user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.