Firetrol FTA560F User manual

1
�
INSTALLATION AND OPERATION INSTRUCTIONS
Jockey Pump Controllers - Models FTA560F,
FTA560E, FTA566E

Table of Contents
Warnings............................................................................................................................................................................................1
Introduction.....................................................................................................................................................................................2
Mounting Controller ..................................................................................................................................................................2
Making System Pressure Connections........................................................................................................................ 3
Making Electrical Connections......................................................................................................................................... 3
Methods of Starting/Stopping ..........................................................................................................................................4
Control Buttons and Items on Keypad........................................................................................................................5
Programmable Settings........................................................................................................................................................6
Keypad Programming Procedure ...................................................................................................................................7
Keypad Shortcuts....................................................................................................................................................................... 8
Visual Setup Instructions ................................................................................................................................................9, 10
Inspections of Controller and Operation................................................................................................................... 11
i

DANGER
RISK OF ELECTROCUTION
Personal injury or death could occur.
Ensure all power is disconnected before
installing or servicing this equipment.
DANGER
DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE
IT IS ENERGIZED! DEATH, PERSONAL INJURY OR SUBSTANTIAL PROPERTY DAMAGE
MAY RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. ALWAYS VERIFY THAT
NO VOLTAGE IS PRESENT BEFORE PROCEEDING AND ALWAYS FOLLOW GENERALLY
ACCEPTED SAFETY PROCEDURES. CONTROLLER DISCONNECT SWITCH MUST BE
IN THE “OFF” POSITION IN ORDER TO OPEN THE ENCLOSURE DOOR. FIRETROL, INC.
CANNOT BE LIABLE FOR ANY MISAPPLICATION OR INCORRECT INSTALLATION OF
ITS PRODUCTS.
1
WARNING: This product can expose you to chemicals including DINP,
which is known to the State of California to cause cancer, and DIDP
which is known to the State of California to cause birth defects or other
reproductive harm.
WARNING: This product can expose you to chemicals including lead
and lead compounds, which are know to the State of California to cause
cancer and birth defects or other reproductive harm.
For more information go to: www.P65Warnings.ca.gov
California Proposition 65 Warning

Introduction
Firetrol FTA560 Jockey Pump Controllers are intended for use with fire pump systems. They
are used for pressure maintenance in fire pump installations to prevent unnecessary cy-
cling of the main fire pump.
Firetrol Jockey Pump Controllers are listed by Underwriters’ Laboratories, Inc., in accor-
dance with UL508, Standard for Industrial Controllers, and CAS, Standard for Industrial
Control Equipment. They are built to meet or exceed the requirements of the approving
authorities as well as NEMA and the latest edition NFPA, National Electrical Code.
These instructions are intended to assist in the understanding of the installation and op-
eration of these controllers. Read the instructions thoroughly prior to connecting or oper-
ating the controller. If there are any unanswered questions, please contact the local Firet-
rol representative or the factory service department.
Mounting Controller
NOTE- Consult the appropriate job plans to determine the controller mounting location.
Tools and materials (all mounting) required:
1. Assortment of common hand tools of the type used to service electromechanical
equipment.
2. Drill for drilling wall anchor holes.
3. Hole (conduit) punch.
4. Hand level.
5. Tape measure.
6. Four anchors with bolts and washers, per enclosure.
Procedure-
Note- Refer to the controller dimension drawing for necessary mounting dimensions.
The controller is wall mounted by using at least four (4) wall anchors, 2 anchors for the top
mounting brackets and 2 anchors for the bottom mounting brackets. The brackets are
dimensionally on the same centerline for ease in mounting.
1. Using either the dimension print or by measuring the distance between the center
lines of the lower bracket slots, transcribe this dimension on to the wall. Note: The
bottom edge of the enclosure should be a minimum of 12” (305mm.) from the floor in
case flooding of the pump room occurs.
2. Drill and put anchors into the wall for the lower mounting brackets.
3. Mark on the wall, the location of the holes in the upper mounting brackets.
4. Drill and put anchors into wall for the upper mounting brackets.
5. Install bolts and washers in lower anchors.
6. Align holes in upper mounting brackets and install bolts and washers in anchors.
7. Shim anchors as necessary to ensure rear of enclosure is vertical level and enclosure
is not stressed. Tighten all anchor bolts.
8. Check to be sure enclosure door open and closes freely and that enclosure is level.
2

Making System Pressure Connections
The controller requires one (1) “System Pressure” connection from the system piping to
the enclosure. The connection fitting, 1/2” FNPT, is provided on the bottom, external side of
the enclosure for this purpose. Refer to NFPA 20 (or Publication GF100-30) for correct field
piping procedure of the sensing line between the pumping system and the controller.
Making Electrical Connections
Important Precautions-
Prior to making any field connections:
1. Open door of enclosure and inspect internal components and wiring for any signs of
frayed or loose wires or other visible damage.
2. Verify that the controller information is what is required on the project:
• Firetrol catalog number
• Motor voltage matches incoming line voltage and frequency
- Confirm incoming voltage matches nameplate before energizing controller
• Pump motor horsepower size matches controller
3. Project electrical contractor must supply all necessary wiring for field connections
in accordance with the National Electrical Code, local electrical code and any other
authority having jurisdiction.
4. Refer to the appropriate field connection drawing for wiring information.
Procedure-
All field connections, remote alarm functions and AC wiring are brought into the enclosure
through the top or bottom conduit entrances as indicated on the dimensional drawing.
Do not place conduit entrances in the sides of the enclosure.
1. Using a hole (conduit) punch, create a hole in the enclosure for the size conduit be-
ing used.
2. Install necessary conduit.
3. Pull all wires necessary for field connections, remote alarm functions, AC power and
all other optional features. Bring enough wire inside the enclosure to make up con-
nections to the appropriate line, load and control terminal block points. Be sure to
consult the appropriate field connection diagram included with the manual. For
proper wire sizing, refer to the National Electrical Code, NFPA 70.
4. Make all field connections to the remote alarm functions and any other optional fea-
tures. Connect motor to controller load terminals.
5. Find nameplate on jockey pump motor and make note of its full load amp rating.
Verity the overload within the controller is set for that number of amps.
6. Verify AC line voltage, phase and frequency with the controller data plate on the en-
closure door prior to connecting. Connect AC power.
7. Check to see that all connections are both correctly wired (in accordance with the
field connection diagram) and tight.
8. Close the enclosure door.
3

Methods of Starting/Stopping
• Automatic Start
The controller will start automatically on low pressure detection by the pressure transduc-
er when pressure drops below the programmed Start Pressure point.
• Manual Start
The motor can be started by pressing the START push button, regardless of the system
pressure.
• Manual Stop
Manual stop is done by pressing the STOP push button. If system pressure is above the
Stop Pressure Point, pressing the STOP pushbutton will stop the motor. If the system pres-
sure is below the Start Pressure Point, pressing the STOP button will stop the motor for as
long as the button is held pressed. The motor will restart once button is released.
• Bump For Rotation
The combination of the Manual Start and the Manual Stop can be used to bump for rota-
tion. If the rotation is incorrect, turn OFF power with the door mounted disconnect. Swap
any two existing motor lead wires that are on the motor contactor in the controller.
• Automatic Stop
The motor is automatically stopped after the restoration of the pressure (if the Stop Pres-
sure point has been reached or exceeded), after a programmable run period timer, if a
timer has been set.
• Emergency Stop
The emergency stop is always possible in any starting condition by turning the door-
mounted disconnect to the OFF position.
4

1
2
3
4
5
6
7
Control Buttons and Items on Keypad
1. ON/OFF LED. It is located on the upper right-hand corner of the keypad. When this LED is lit in
green, the controller is ready for automatic operation. When it is lit in red, the controller can be
started in manual only (display screen will show “OFF”).
2. Display Screen. A four-character display that shows programming values and the pressure
reading.
3. Three vertical LEDs. To the right of the display screen, these represent the incoming sensing
line pressure status. The upper green LED is lit when the pressure the controller measures is
above the Stop Pressure point, the middle amber LED is lit when the pressure is in between the
Start Pressure and Stop pressure points and the bottom red LED is lit when the pressure is be-
low the Start Pressure point.
4. Arrow Pushbuttons. The Up/Down (+/-) arrow buttons are used for increasing or decreasing
a parameter value shown on the screen. The Left/Right buttons are used to scroll through the
five available programming settings.
5. Enter Pushbutton. Looks like a check-mark inside of a gear. This is used to access the pa-
rameters to program and to confirm programming changes. The programming procedure is
described below.
6. ON/OFF Pushbutton. This is located on the lower right-hand corner of the keypad. This is used
to place the controller in manual/non-automatic mode (display screen will show “OFF”) or
place the controller in automatic mode.
7. Start and Stop Pushbuttons. These are on the left-hand side of the keypad. Pressing the green
Start pushbutton starts the pump in manual mode. If the pump is started in manual mode, it
must be stopped manually by pressing the Stop Pushbutton. If the controller starts the pump
in automatic mode by the system pressure dropping to or below the Start Pressure point,
pressing the STOP button will stop the motor for as long as the button is held pressed. The mo-
tor will restart once button is released.
5

Programmable Settings
There are five available parameters to set:
1. Pump Stop Pressure (shown on screen as “Cu.Ou” for “Cut-Out”)
2. Pump Start Pressure (shown on screen as “Cu.In” for “Cut-In”)
3. Pressure Display Units (shown on screen as “Unit”)
4. Pump Stop Delay Timer (shown on screen as “t.OFF”)
5. Pump Start Delay Timer (shown on screen as “t.On”)
1 & 2. Pressure set-points are adjustable from 0 to 600 PSI equivalent. Program the Stop
Pressure point first. The keypad will not allow the Stop Pressure point to be lower than
the Start Pressure point nor the Start Pressure point to be above the Stop Pressure point.
NOTE: If the intent is for the connected pressure to be above 300 PSI, confirm that the con-
troller has been rated for this pressure level.
3. Selectable units are: PSI, BAR, Kpa, Feet H2O and Meter H2O. The keypad display will
show the pressure measured by the controller from the connected sensing line using that
selected unit of pressure.
4. Once the pump is running in automatic mode from the controller, it will run for the pro-
grammed number of seconds after the Stop Pressure point has been reached. This setting
is adjustable from 0 to 9999 seconds. A small red dot will flash On and Off if the timer is
counting down. If the pressure drops below the Stop Pressure point before the timer has
expired, the timer is reset.
5. Once the pressure level measured by the controller drops to or below the Start Pressure
point, the controller will delay starting the pump for the programmed number of seconds.
This setting is adjustable from 0 to 9999 seconds. A small red dot will flash On and Off if
the timer is counting down. If the pressure rises above the Start Pressure point before the
timer has expired, the timer is reset.
6

Keypad Programming Procedure
A. Apply power to the controller and turn ON the door mounted disconnect. If the con-
troller is in OFF mode, the display screen will alternate between showing “OFF” and the
incoming pressure along with a red ON/OFF LED on the upper right-hand corner of the
keypad. (If “0000” is shown, then the controller does not see any incoming pressure.)
If the controller is in automatic mode, the ON/OFF LED on the upper right-hand corner
of the keypad will be green and a constant pressure reading shown on the display
screen.
B. Press and hold the Enter Pushbutton for about five seconds (the 3 LED’s to the right of
the display should be flashing). This accesses the programmable settings. First shown
will be “Cu.Ou”. Press the Enter Pushbutton again and a number will be shown. This is
the Stop Pressure point. Use the up or down (+ or -) buttons to select the desired Stop
Pressure point. The longer a button is kept pressed, the faster the displayed number
will change. Once completed, press Enter again. “Cu.Ou” will be shown.
C. Press the right arrow pushbutton once. Now, “Cu.In” will be shown. Press the Enter
Pushbutton and a number will be shown. This is the Start Pressure point. Use the up or
down (+ or -) buttons to select the desired Start Pressure point. The longer a button
is kept pressed, the faster the displayed number will change. Once completed, press
Enter again. “Cu.In” will be shown.
D. Press the right arrow pushbutton once. Now, “Unit” will be shown. The default setting
for the unit of pressure measurement is PSI. If another unit of measurement is desired
(available choices listed above), press the Enter button. Then, use the up or down (+
or -) buttons to select the desired unit of pressure measurement and then press the
Enter button. “Unit” will be shown.
E. Press the right arrow pushbutton once. Now, “t.OFF” will be shown. As described above,
this is the Stop Delay timer. Default setting is 0 seconds. If a Stop Delay is desired,
press the Enter button. Then, use the up or down (+ or -) buttons to select the desired
number of seconds and press the Enter button. “t.OFF” will be shown.
F. Press the right arrow pushbutton once. Now, “t.On” will be shown. As described above,
this is the Start Delay timer. Default setting is 0 seconds. If a Start Delay is desired,
press the Enter button. Then, use the up or down (+ or -) buttons to select the desired
number of seconds and press the Enter button. “t.On” will be shown.
G. Press the right arrow pushbutton once. Now, “Cu.Ou” will be shown and programming
is complete then press and hold the ON/OFF Pushbutton for about two seconds. The
ON/OFF LED on the upper right-hand corner of the keypad should be green and a con-
stant pressure reading should be shown on the display screen.
H. The controller is now ready for automatic operation.
7

Keypad Shortcuts to See Parameter Settings and Recorded Values
Place controller into Auto mode by pressing ON/OFF pushbutton (for about 2 seconds) so
the ON/OFF LED on the upper right-hand corner of the keypad will be lit in green.
• Stop Pressure: press Up arrow button
• Start Pressure: press Down arrow button
• ON Delay Timer: simultaneously press the Down arrow button and left arrow button
• OFF Delay Timer: simultaneously press the Up-arrow button and left arrow button
• Number of times pump has started: simultaneously press the Up-arrow button and
right arrow button
• Pump Running Elapsed Time: simultaneously press the down arrow button and right
arrow button
Stop Pressure Off Delay Timer # of Starts
Start Pressure On Delay Timer Elapsed Run Time
(Hours)
AUTOHAND
AUTOHAND
AUTOHAND
AUTOHANDAUTOHAND
AUTOHAND
8

Serial #
Options
LRC AmpSchema
Ampacity NEMA Type
FLCMax. Pres.
HP Ctr. Volt.
Line Volt Phase / H
Model #
Mfg Date:
7
6
Firetrol Models: FTA560F, FTA560E, FTA566E
12
5
L1 L2 L3
T1
C1
T2 T3
AUTOHAND
AUTOHAND
AUTOHAND
5 sec.
AUTOHAND
43
AUTOHAND
C1
T1 T2 T3
C1
T1 T2 T3
9
1/2 NPT

AUTOHAND AUTOHAND
2 sec.
OK
9
8
UNIT
CUT-OUT
CUT-IN
ON TIMER
OFF TIMER
GREEN
CUT-IN
CUT-OUT
10

.
VISUAL INSPECTION YES NO
Inspect cleanliness of controller.
Remove any objects from the top of the controller.
Dust and clean the controller.
Inspect controller for any evidence of external corrosion.
Inspect controller for any evidence of internal corrosion.
Check for water leaks on pressure transducer and piping.
Inspect door for proper alignment and function of door locks.
Check tightness of all wiring connections.
Inspect the controller for proper grounding
Inspect internal and external components for any damage.
Inspect motor starter power contacts.
Check tightness of all component mounting hardware.
OPERATIONAL INSPECTION YES NO
Verify proper motor rotation.
Confirm automatic start from water pressure control.
11

3412 Apex Peakway
Apex, North Carolina 27502
P +1 919 460 5200
F +1 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-
ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2021 Firetrol, Inc., All Rights Reserved.
Publication NS560-01
This manual suits for next models
2
Table of contents
Other Firetrol Controllers manuals

Firetrol
Firetrol FTA1100 Series Product manual

Firetrol
Firetrol Jockey XG FTA550 Installation instructions

Firetrol
Firetrol FTA740 Series Product manual

Firetrol
Firetrol FTA2000 Series Product manual

Firetrol
Firetrol FTA570F-AG003E Manual

Firetrol
Firetrol Emerson Mark IIXG User manual

Firetrol
Firetrol FTA3100S Product manual