1
ED.95.R9.02 © Danfoss 03/2014
DEN-SMT/SI
Actuators for three point control
AMV 25, AMV 35
Data sheet
Description
AMV electric actuators are used with, VRB, VRG,
VF, VL valves with additional adapter
(Code No.
065Z0311, not supplied) and VFS 2 valves up to
DN 50 diameter.
The actuator automatically adapts its
stroke to valve end positions which reduces
commissioning time. Optional auxiliary switches,
feedback potentiometer and valve stem heater
are available.
The actuator has some special features:
• Theadvanceddesignincorporatesload
related ‘switch-off’ to ensure that actuators
and valves are not exposed to overload;
• Digitalefeedbackendpositionindication
signal for valve end position is available by
terminal 4 or 5;
• Lowweightandrobust;
Main data:
• Nominalvoltage:
- 24 VAC, 50 Hz/60 Hz
- 230 VAC, 50 Hz/60 Hz
• Controlinputsignal:
3 point
• Force:450N
• Stroke:15mm
• Speed:15 s/mm
•Max. medium temperature: 150 °C
•End-position signals
Ordering Actuators
Type Supply voltage Code No.
(VAC)
AMV 25 230 082G3024
AMV 25 24 082G3023
AMV 35 230 082G3021
AMV 35 24 082G3020
Accessories
Type Code No.
Additional switch (2×) 082H7015
Additional switch (2×)
and potentiometer (10 kΩ) 082H7016
Additional switch (2×)
and potentiometer (1 kΩ) 082H7017
Adapter for VFS 2 valves DN 15-50
(for media temp. over 150 °C) 065Z7548
Stem heater (for valves DN 15-50) 065B2171
Adapter for valves VRB/VRG/VF/VL (2009)
DN 15-50 065Z0311*
* Need to be ordered separately.
Technical data
Type AMV 25 AMV 35
Power supply V 24 AC, 230 AC; +10 to –15 %
Power consumption VA 2 7
Frequency Hz 50/60
Control input 3-point
Closing force N1000 600
Max. stroke mm 15
Speed by 50 Hz (60 Hz) s/mm 11 (8, 8) 3 (2,4)
Max. medium temperature
°C
150 (200 - with adapter or mounted horizontally)
Ambient temperature 0 … 55
Storage and transport temperature –40 … 70
Grade of enclosure IP 54
Weight kg 1,55
- marking in accordance with standards Low Voltage Directive 73/23/EEC,
EMC-Directive 2006/95/EEC: EN 60730-1, EN 60730-2-14