Installation- and maintenance instruction
FläktGroup DC_9108GB 20190206_R1Specifications are subject to alteration without notice
Alarm indication
Fault condition/Action required
S E Fault
Green LED
flashes slowly
Purging/
low control signal
Check EMX-R by running the drive system with the test switch located next to
terminal 37. The motor should accelerate to its maximum speed.
If the motor does accelerate to the maximum speed when the test switch is
activated, the fault is external. Can 0-10 V (2-10 V) be measured between 33(+) and
34 (-)? Have + and – been swapped?
Red and green
LED flash rapidly
Pre-alarm,
rotation monitor
The drive system has switched to a softer speed controller because the motor shaft
is jerking sharply. Check that the drive belt is not slipping on the pulley.
Red LED
flashes rapidly Rotation monitor
The exchanger rotor is not rotating; check the drive belt.
The rotor is rotating; check that the indication is given when the magnet passes the
rotation sensor, see the section “Operating indicators”. If not, replace the rotation
sensor. Check that the rotor or belt pulley is not smaller than 630 mm or 63 mm
respectively.
Red LED is lit
and green
LED flashes rapidly
Pre-alarm,
overload/
motor protection
The motor protection has been activated due to excessive load. After a cool-down
period of 10 minutes, the system restarts automatically. If the overload protection
trips 3 times within 120 minutes, the drive system will be shut down, see also“
Overload”. (only red LED is lit).
Red LED is lit Overload/
motor protection
The motor protection has been activated due to excessive load. Check that the
motor cables are connected correctly, see the section on Connection.
Check also that the rotor runs freely and that the diameters of the rotor and pulley
are not too large. If the fault remains, carry out motor diagnosis.
Replace the motor if it is faulty. If the fault does not lie within the motor, replace
thecontrol unit.
No LED lit Supply voltage
Missing Check that 230 VAC ±15% is connected to the supply terminal.
Red and green LED
flash slowly and
alternately
Over voltage The supply voltage exceeds 264 V AC
Under voltage The supply voltage is below 196 V AC
Red and green
LED flash rapidly and
alternately
Earth connection in
the motor
Disconnect the supply voltage, check the connection of the motor cable and check
that the correct motor is connected.
If the fault remains, carry out a motor diagnosis. If the motor is faulty, replace it.
If the motor is not faulty, replace the control unit
Red LED
flashes slowly
Short circuit in
the motor.
Circuit break in
the motor
TROUBLESHOOTING
Check that the equipment has been correctly installed, i.e. that the
cables are properly stripped, no loose cables, etc., and check that the
DIPswitches are correctly set.
It is always possible to test run the drive system usingthe TEST switch
located under the cover next to terminal 37. The switch has two fixed
positions, when it is in the up position, the motor accelerates to its
maximum speed independent of the control signal, and when it is in the
down position the rotation speed is controlled by the control signal. If the
motor does no treach maximum speed or respond to the control signal,
check DIPswitches 1-3 and 7 and 8. If the heat exchang-er rotates in the
wrong direction, change the setting of DIPswitch 6.
MOTOR DIAGNOSIS
Disconnect the supply voltage. Disconnect the motor
cables from the control unit.
Measure the motor resistance between 1–2, 3–4 and 5–6.
The values should be: 15M: 30–90 Ohm; 25M: 5–15 Ohm; 35M: 5–15 Ohm
The resistance should not differ by more than 5 Ohm between the phases
for 15M, and by no more than 2 Ohm for 25M/35M.
Also check the insulation resistance between 1–3, 1–5, 3–5, 1-earth,
3–earth and 5–earth.