GETTINGSTARTED(continued)StepSix
Howtoconfigureapanelmeterwhenapressuretransmitterisused?
ThismethodworkswiththeLI55series,LI25Series,LI10SeriesandLI50Series.Thesepanelmetersare
configuredusingtheSCALEfunction.TheSCALEfunctiontypicallyhasfoursettings.Thesesettingsareas
follows:
SettingsDefaultRepresentsTypicalSetting
Input104.000Inputcurrent@Empty04.000(mA)
Display1(Empty)04.000Displayvalue@EmptyEmptyvalue
Input220.000Inputcurrent@Full20.000
Display2(Full)20.000Displayvalue@FullFullValue(mA)
Remember,pressuretransmittersareconfiguredso0psi=4mAandthemaximumpsi=20mA.Most
pressuretransmitterapplicationswillnotusethefullrangeofthetransmitterandrequiresyouto
proportionallyscalethecurrentoutputofthepressuretransmitter.Therefore,afulltankwilltypicallyhavea
currentlessthan20mA.Thegoalinconfiguringthepanelmeteristocalculatethecurrentwhenthetankis
full.Todothis,usethefollowingformula:
(FullTankHeight/MaximumLiquidHeight)x16+4=CurrentatFull
Example:A16foottankwithaSG=0.9willhaveamaximumpressureof6.23psi.A15psisensorisselected
foruse.TheMaximumLiquidHeight=(15psix2.31’/psi)/0.9=38.5feet.Usingtheaboveformula,the
CurrentatFull=[(40feet/51.33feet)x16+4]=10.649mA.
TheCurrentatFullwillbeusedastheInput2value.Thismeansthatwhenthedisplayreadsacurrentequal
toCurrentatFull,itwilldisplaytheFullvalue(Display2value).Thepanelmeterwillbeconfiguredasfollows:
SettingsConfigured
Input104.000
Display1Empty
Input210.649
Display2Full
Note:ThevaluesforemptyandfullrepresentwhatthedisplaywillshowwhenthetankiseitherEmptyorFull.
EmptyandFullmustbethesameunits(example:Gallons,Inches,percent).
ThedefaultfortheInput1is4mAandtypicallywillneverbechanged.
Typically,theEmptysettingwillbewhatisinthetankwhenitisempty(example:000.0Gallons,000.0
inches,000.0feetetc.).
TheFullsettingwillbewhatisinthetankwhenitisfull(example:500.0Gallons,120.0inches,10.0
feet,etc.).