FMC Technologies Proline Promass 83 E Application guide

Description of Device Functions
Issue/Rev. 0.2 (12/12) Bulletin MN0M023
Proline Promass 83 E, F & O
The Most Trusted Name In Measurement
Coriolis Mass Flowmeters
Valid as of version
V 3.00.XX (device software)

Issue/Rev. 0.2 (12/12)
Page 2 • MN0M023
(This Page Intentionally Left Blank)

Issue/Rev. 0.2 (12/12) MN0M023 • Page 3
Device Functions Proline Promass 83 Table of Contents
Table of Contents
1 Notes on using this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.1 Using the table of contents to locate a function description . . . . . . . . . . . . . . . . . . . . . . . 7
1.2 Using the graphic of the function matrix to locate a function description . . . . . . . . . . . . 7
1.3 Using the index of the function matrix to locate a function description . . . . . . . . . . . . . . 7
2Functionmatrix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1 General layout of the function matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1.1 Blocks (A, B, C, etc.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1.2 Groups (AAA, AEA, CAA, etc.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1.3 Function groups (000, 020, 060, etc.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1.4 Functions (0000, 0001, 0002, etc.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1.5 Codes identifying cells . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2 Function matrix Proline Promass 83 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3 Block MEASURED VARIABLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.1 Group MEASURING VALUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.1.1 Function group MAIN VALUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.1.2 Function group ADDITIONAL VALUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2 Group SYSTEM UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2.1 Function group CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2.2 Function group ADDITIONAL CONFIGURATION . . . . . . . . . . . . . . . . . . . . . 20
3.3 Group SPECIAL-UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.3.1 Function group ARBITRARY UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
4 Block QUICK SETUP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.1 Setup Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.2 Pulsating flow Setup menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.3 Gas measurement Setup menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.4 Batching Setup menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4.5 Data back-up/transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5 Block USER INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.1 Group CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.1.1 Function group BASIC CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.1.2 Function group UNLOCKING/ LOCKING . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.1.3 Function group OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.2 Group MAIN LINE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.2.1 Function group CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.2.2 Function group MULTIPLEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.3 Group ADDITIONAL LINE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
5.3.1 Function group CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
5.3.2 Function group MULTIPLEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.4 Group INFORMATION LINE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
5.4.1 Function group CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
5.4.2 Function group MULTIPLEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6 Block TOTALIZERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
6.1 Group TOTALIZER (1...3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.1.1 Function group CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.1.2 Function group OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.2 Group HANDLING TOTALIZER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

Issue/Rev. 0.2 (12/12) MN0M023 • Page 4
Table of Contents Device Functions Proline Promass 83
7 Block OUTPUTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
7.1 Group CURRENT OUTPUT (1...3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
7.1.1 Function group CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
7.1.2 Function group OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
7.1.3 Function group INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
7.2 Group PULSE/FREQUENCY OUTPUT (1...2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
7.2.1 Function group CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
7.2.2 Function group OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
7.2.3 Function group INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
7.3 Group RELAY OUTPUT (1...2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
7.3.1 Function group CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
7.3.2 Function group OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
7.3.3 Function group INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
7.3.4 Information on the response of the relay output . . . . . . . . . . . . . . . . . . . . . . 108
7.3.5 Switching behavior of the relay output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
8 Block INPUTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
8.1 Group STATUS INPUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
8.1.1 Function group CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
8.1.2 Function group OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
8.1.3 Function group INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
8.2 Group CURRENT INPUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
8.2.1 Function group CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
8.2.2 Function group OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
8.2.3 Function group INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
9 Block BASIC FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
9.1 Group HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
9.1.1 Function group CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
9.1.2 Function group INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
9.2 Group PROCESS PARAMETER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
9.2.1 Function group CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
9.2.2 Function group EPD PARAMETER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
9.2.3 Function group REFERENCE PARAMETER . . . . . . . . . . . . . . . . . . . . . . . . . 127
9.2.4 Function group ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
9.2.5 Function group PRESSURE CORRECTION . . . . . . . . . . . . . . . . . . . . . . . . . . 132
9.3 Group SYSTEM PARAMETER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
9.3.1 Function group CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
9.4 Group SENSOR DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
9.4.1 Function group CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
9.4.2 Function group FLOW COEFFICIENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
9.4.3 Function group DENSITY COEFFICIENT . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
9.4.4 Function group ADDITIONAL COEFFICIENT . . . . . . . . . . . . . . . . . . . . . . . 138
10 Block SPECIAL FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
10.1 Group DENSITY FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
10.1.1 Function group CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
10.2 Group BATCHING FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
10.2.1 Function group CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
10.2.2 Function group VALVE PARAMETER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
10.2.3 Examples of setting parameters for batching processes . . . . . . . . . . . . . . . . . . 155
10.2.4 Function group SUPERVISION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
10.2.5 Function group OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
10.2.6 Function group INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164

Issue/Rev. 0.2 (12/12) MN0M023 • Page 5
Device Functions Proline Promass 83 Table of Contents
10.3 Group ADVANCED DIAGNOSIS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
10.3.1 Function group CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
10.3.2 Function group ACQUISITION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
10.3.3 Function group MASS FLOW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
10.3.4 Function group DENSITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
10.3.5 Function group REFERENCE DENSITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
10.3.6 Function group TEMPERATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
10.3.7 Function group TUBE DAMPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
10.3.8 Function group ELECTRODYNAMIC SENSORS . . . . . . . . . . . . . . . . . . . . . . 173
10.3.9 Function group OPERATING FREQUENCY FLUCTUATION . . . . . . . . . . . . . 175
10.3.10Function group TUBE DAMPING FLUCTUATION . . . . . . . . . . . . . . . . . . . . 177
11 Block SUPERVISION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
11.1 Group SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
11.1.1 Function group CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
11.1.2 Function group OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
11.2 Group VERSION-INFO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
11.2.1 Function group DEVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
11.2.2 Function group SENSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
11.2.3 Function group AMPLIFIER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
11.2.4 Function group F-CHIP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
11.2.5 Function group I/O MODULE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
11.2.6 Function groups INPUT/OUTPUT 1...4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
12 Factory settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
12.1 SI units (not for USA and Canada) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
12.1.1 Low flow cut off, full scale value, pulse value – Liquid . . . . . . . . . . . . . . . . . . 189
12.1.2 Low flow cut off, full scale value, pulse value – Gas . . . . . . . . . . . . . . . . . . . 189
12.1.3 Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
12.1.4 Density, length, temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
12.2 US units (only for USA and Canada) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
12.2.1 Low flow cut off, full scale value, pulse value – Liquid . . . . . . . . . . . . . . . . . . 191
12.2.2 Low flow cut off, full scale value, pulse value – Gas . . . . . . . . . . . . . . . . . . . 191
12.2.3 Language, density, length, temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191

Issue/Rev. 0.2 (12/12)
Page 6 • MN0M023
Table of Contents Device Functions Proline Promass 83
Registered trademarks
HART£
Registered trademark of HART Communication Foundation, Austin, USA
HistoROM™, S-DAT£, T-DAT£, F-CHIP£
Registered trademarks of Endress+Hauser Flowtec AG, Reinach, CH

Issue/Rev. 0.2 (12/12) MN0M023 • Page 7
Device Functions Proline Promass 83 1 Notes on using this Manual
1 Notes on using this Manual
There are various ways of locating the description of a function of your choice in the manual:
1.1 Using the table of contents to locate a function
description
The designations of all the cells in the function matrix are listed in the table of contents. You can
use these unambiguous designations (such as USER INTERFACE, INPUTS, OUTPUTS, etc.) to
choose whichever functions are applicable to a particular set of conditions. The page references
show you exactly where to find the detailed descriptions of the functions in question.
The table of contents is on page 3.
1.2 Using the graphic of the function matrix to locate a
function description
This step-by-step, top-down approach starts with the blocks, the highest level, and factory down
through the matrix to the description of the function you need:
1. All blocks available, and their related groups, are illustrated on page 10. Select the block (or
the group within the block) which you need for your application and use the page reference
to locate the information corresponding to the next level.
2. The page in question contains a graphic showing of the block with all its subordinate groups,
function groups and functions. Select the function which you need for your application and
use the page reference to locate the detailed function description.
1.3 Using the index of the function matrix to locate a
function description
Each “cell” in the function matrix (blocks, groups, function groups, functions) has a unique
identifier in the form of a code consisting of one or three letters or a three- or four-digit number.
The code identifying a selected “cell” appears at the top right on the local display.
Example:
A0001653-en
The function matrix index lists the codes for all the available “cells” in alphabetic and consecutive
order, complete with the page references for the corresponding functions.
The index to the function matrix is on page 193.

Issue/Rev. 0.2 (12/12)
Page 8 • MN0M023
2 Function matrix Device Functions Proline Promass 83
2 Function matrix
2.1 General layout of the function matrix
The function matrix consists of four levels:
Blocks -> Groups -> Function groups -> Functions
A0000961
2.1.1 Blocks (A, B, C, etc.)
The blocks are the highest-level grouping of the operation options for the device. The blocks
include, for example: MEASURED VARIABLES, QUICK SETUP, USER INTERFACE, TOTALIZER,
etc.
2.1.2 Groups (AAA, AEA, CAA, etc.)
A block consists of one or more groups. Each group represents a more detailed selection of the
operation options in the higher-order block. The groups in the USER INTERFACE block, for
example, include: CONTROL, MAIN LINE, ADDITIONAL LINE, etc.
2.1.3 Function groups (000, 020, 060, etc.)
A group consists of one or more function groups. Each function group represents a more detailed
selection of the operation options in the higher-order group. The function groups in the CONTROL
group, for example, include: BASIC CONFIGURATION, UN-/LOCKING, OPERATION, etc.
2.1.4 Functions (0000, 0001, 0002, etc.)
Each function group consists of one or more functions. The functions are used to operate and
configure the device. Numerical values can be entered or parameters selected and saved.
The functions in the BASIC CONFIGURATION function group include LANGUAGE, DISPLAY
DAMPING, CONTRAST LCD, etc. The procedure for changing the language of the user interface,
for example, is as follows:
1. Select the block USER INTERFACE.
2. Select the group CONTROL.
3. Select the function group BASIC CONFIGURATION.
4. Select the function LANGUAGE (here you can set the language required).
…
…
…
…
…
…
…
…
0001
2001
0401
2021
2201
0002
2002
0402
2022
2202
0003
2003
0403
2023
2203
0009
2009
0409
2029
2209
0429
2049
2069
0421
2041
0422
2042
0423
2043
20632061 2062
0000
2000
0400
2020
2200
0420
2040
2060
000
200
040
202
220
042
204
206
AAA
BAA
ACA
CAA
CBA
D, E, …
A
B
C

Issue/Rev. 0.2 (12/12) MN0M023 • Page 9
Device Functions Proline Promass 83 2 Function matrix
2.1.5 Codes identifying cells
Each cell (block, group, function group and function) in the function matrix has an individual,
unique code.
Blocks:
The code is a letter (A, B, C, etc.)
Groups:
The code consists of three letters (AAA, ABA, BAA, etc.).
The first letter matches the block code (i.e. each group in block A has a code starting with an
A _ _; the codes of the groups in block B start with a B _ _, etc.). The other two letters are for
identifying the group within the respective block.
Function groups:
The code consists of three digits (000, 001, 100, etc.).
Functions:
The code consists of four digits (0000, 0001, 0201, etc.).
The first three digits are the same as the code for the function group.
The last digit in the code is a counter for the functions in the function group, incrementing from
0 to 9 (e.g. function 0005 is the sixth function in group 000).
A0001251
Block Group Function
group Functions
200020012002200
CAAC

Issue/Rev. 0.2 (12/12)
Page 10 • MN0M023
2 Function matrix Device Functions Proline Promass 83
2.2 Function matrix Proline Promass 83
BLOCKS GROUPS Function
groups
MEASURED VARIABLES AoMEASURING VALUES AAA osee p. 12
(see p. 11) SYSTEM UNITS ACA osee p. 17
pSPECIAL-UNITS AEA osee p. 22
QUICK SETUP BoCommissioning and application setups osee p. 25
(see p. 25)
p
USER INTERFACE CoCONTROL CAA osee p. 36
(see p. 35) MAIN LINE CCA osee p. 40
pADDITIONAL LINE CEA osee p. 44
INFORMATION LINE CGA osee p. 50
TOTALIZERS DoTOTALIZER 1 DAA osee p. 57
(see p. 56) TOTALIZER 2 DAB osee p. 57
pTOTALIZER 3 DAC osee p. 57
HANDLING TOTALIZER DJA osee p. 60
OUTPUTS EoCURRENT OUTPUT 1 EAA osee p. 62
(see p. 61) CURRENT OUTPUT 2 EAB osee p. 62
pCURRENT OUTPUT 3 EAC osee p. 62
PULSE/FREQ. OUTPUT 1 ECA osee p. 74
PULSE/FREQ. OUTPUT 2 ECB osee p. 74
RELAY OUTPUT 1 EGA osee p. 101
RELAY OUTPUT 2 EGB osee p. 101
INPUTS FoSTATUS INPUT FAA osee p. 112
(see p. 111) CURRENT INPUT FCA osee p. 115
p
BASIC FUNCTION GoHART GAA osee p. 120
(see p. 119) PROCESS PARAMETER GIA osee p. 122
pSYSTEM PARAMETER GLA osee p. 133
SENSOR DATA GNA osee p. 135
SPECIAL FUNCTION HoDENSITY FUNCTIONS HAA osee p. 141
(see p. 139) BATCHING FUNCTION HCA osee p. 147
pADVANCED DIAGNOSIS HEA osee p. 166
SUPERVISION JoSYSTEM JAA osee p. 180
(see p. 179) VERSION-INFO JCA osee p. 185

Issue/Rev. 0.2 (12/12) MN0M023 • Page 11
Device Functions Proline Promass 83 3 Block MEASURED VARIABLES
3 Block MEASURED VARIABLES
Functions
CORR. CARR.
VOLUME FLOW
(0029) p. 15
% CARRIER
VOLUME FLOW
(0028) p. 15
CARRER VOL.
FLOW
(0027) p. 14
FACT. ARB.
CONCENT.
(0607) p. 24
PRESSURE
(0009) p. 12
% CARRIER MASS
FLOW
(0026) p. 14
OTHERS
(0037) p. 16
TEXT ARB.
CONCENTR.
(0606) p. 24
TEMPERATURE
(0008) p. 12
CARRIER MASS
FLOW
(0025) p. 14
°BRIX
(0036) p. 16
UNIT CORR.
VOLUME
(0405) p. 19
FACTOR ARB.
DENSITY
(0605) p. 23
REFERENCE
DENSITY
(0006) p. 12
CORR. TARGET
VOL. FLOW
(0024) p. 14
°BALLING
(0035) p. 16
UNIT CORR. VOL.
FLOW
(0404) p. 19
UNIT PRESSURE
(0426) p. 21
TEXT ARB.
DENSITY
(0604) p. 23
DENSITY
(0005) p. 12
% TARGET
VOLUME FLOW
(0023) p. 13
°PLATO
(0034) p. 16
UNIT VOLUME
(0403) p. 18
UNIT LENGTH
(0424) p. 21
FACTOR ARB.
VOLUME
(0603) p. 23
CORRECTED
VOL. FLOW
(0004) p. 12
TARGET VOLUME
FLOW
(0022) p. 13
°API
(0033) p. 15
UNIT VOLUME
FLOW
(0402) p. 18
UNIT
TEMPERATURE
(0422) p. 21
TEXT ARB.
VOLUME
(0602) p. 23
VOLUME FLOW
(0001) p. 12
% TARGET MASS
FLOW
(0021) p. 13
°BAUME
(0031) p. 15
UNIT MASS
(0401) p. 17
UNIT REFERENCE
DENSITY
(0421) p. 20
FACTOR
ARB. MASS
(0601) p. 22
MASS FLOW
(0000) p. 12
TARGET MASS
FLOW
(0020) p. 13
% BLACK LIQUOR
(0030) p. 15
UNIT MASS FLOW
(0400) p. 17
UNIT DENSITY
(0420) p. 20
TEXT
ARB. MASS
(0600) p. 22
Function
groups
MAIN VALUES
(000) p. 12
ADDITIONAL
VALUES
(002) p. 13
CONFIGURATION
(040) p. 17
ADDITIONAL
CONFIGURATION
(042) p. 20
ARBITRARY UNIT
(060) p. 22
Groups
MEASURING
VALUES
(AAA) p. 12
SYSTEM UNITS
(ACA) p. 17
SPECIAL-UNITS
(AEA) p. 22
Block
MEASURED
VARIABLES
(A)

Issue/Rev. 0.2 (12/12)
Page 12 • MN0M023
3 Block MEASURED VARIABLES Device Functions Proline Promass 83
3.1 Group MEASURING VALUES
3.1.1 Function group MAIN VALUES
MEASURED
VARIABLES AMEASURING VALUES AAA MAIN VALUES 000
Function description
MEASURED VARIABLES oMEASURING VALUES oMAIN VALUES
!Note!
• The engineering units of all the measured variables shown here can be set in the “SYSTEM UNITS” group.
• If the fluid in the pipe flows backwards, a negative sign prefixes the flow reading on the display.
MASS FLOW
(0000)
The currently measured mass flow appears on the display.
Display:
5-digit floating-point number, including unit and sign
(e.g. 462,87 kg/h; –731.63 lb/min; etc.)
VOLUME FLOW
(0001)
The calculated volume flow appears on the display. The volume flow is derived from the
measured mass flow and the measured density of the fluid.
Display:
5-digit floating-point number, including unit and sign
(e.g. 5.5445 dm3/min; 1.4359 m3/h; –731.63 gal/d; etc.)
CORRECTED VOLUME
FLOW
(0004)
The calculated corrected volume flow appears on the display. The calculated corrected
volume flow is derived from the measured mass flow and the reference density of the
fluid (density at reference temperature, measured or fixed entry).
Display:
5-digit floating-point number, including unit and sign
(e.g. 1.3549 Nm3/h; 7.9846 scm/day; etc.)
DENSITY
(0005)
The currently measured density or its specific gravity appears on the display.
Display:
5-digit floating-point number, incl. unit, corresponds to 0.1000 to 6.0000 kg/dm3
(e.g. 1.2345 kg/dm3; 993.5 kg/m3; 1.0015 SG_20 °C; etc.)
REFERENCE DENSITY
(0006)
The density of the fluid, at reference temperature, appears on the display. The reference
density can be calculated with the measured density or also specified via the function
FIXED REF. DENSITY (6461), (see page 127), or read in directly via the current input.
Display:
5-digit floating-point number, incl. unit, corresponds to 0.1000 to 6.0000 kg/dm3
(e.g. 1.2345 kg/dm3; 993.5 kg/m3; 1.0015 SG_20 °C; etc.)
TEMPERATURE
(0008)
The currently measured temperature appears on the display.
Display:
max. 4-digit fixed-point number, including unit and sign
(e.g. –23.4 °C; 160.0 °F; 295.4 K; etc.)
PRESSURE
(0009)
The currently measured pressure appears on the display. This function is not available
unless “pressure” was selected in the ASSIGN CURRENT INPUT function (5200).
Display:
max. 4-digit fixed-point number, including unit and sign
(e.g. 50.0 barg; etc.)

Issue/Rev. 0.2 (12/12) MN0M023 • Page 13
Device Functions Proline Promass 83 3 Block MEASURED VARIABLES
3.1.2 Function group ADDITIONAL VALUES
MEASURED
VARIABLES AMEASURING VALUES AAA MAIN VALUES 000
ADDITIONAL VALUES 002
Function description
MEASURED VARIABLES oMEASURING VALUES oADDITIONAL VALUES
TARGET MASS FLOW
(0020) !Note!
This function is not available unless one of the following was selected:
• in the function DENSITY FUNCTION (7000), see page 141:
– % MASS / % VOLUME
– FLEXIBLE and in the function MODE (7010), see page 144, the selection
% MASS 2D or % MASS 3D
Use this function to display the currently measured mass flow of the target fluid. Target
fluid = carried material (e.g. lime powder).
Display:
5-digit floating-point number, including unit and sign
% TARGET MASS FLOW
(0021) !Note!
This function is not available unless one of the following was selected:
• in the function DENSITY FUNCTION (7000), see page 141:
– % MASS / % VOLUME
– FLEXIBLE and in the function MODE (7010), see page 144, the selection
% MASS 2D or % MASS 3D
In this function, the currently measured mass flow of the target fluid is displayed as a %
(of the overall mass flow). Target fluid = carried material (e.g. lime powder).
Display:
5-digit floating-point number, including unit and sign
TARGET VOLUME FLOW
(0022) !Note!
This function is not available unless one of the following was selected:
• in the function DENSITY FUNCTION (7000), see page 141:
– % MASS / % VOLUME
– FLEXIBLE and in the function MODE (7010), see page 144, the selection
% VOLUME 2D or % VOLUME 3D
In this function, the currently measured volume flow of the target fluid is displayed.
Target fluid = carried material (e.g. lime powder).
Display:
5-digit floating-point number, including unit and sign
% TARGET VOLUME
FLOW
(0023)
!Note!
This function is not available unless one of the following was selected:
• in the function DENSITY FUNCTION (7000), see page 141:
– % MASS / % VOLUME
– FLEXIBLE and in the function MODE (7010), see page 144, the selection
% VOLUME 2D or % VOLUME 3D
Use this function to display the currently measured volume flow of the target fluid as a %
(of the overall volume flow). Target fluid = carried material (e.g. lime powder).
Display:
5-digit floating-point number, including unit and sign

Issue/Rev. 0.2 (12/12)
Page 14 • MN0M023
3 Block MEASURED VARIABLES Device Functions Proline Promass 83
CORRECTED TARGET
VOLUME FLOW
(0024)
!Note!
This function is not available unless % MASS / % VOLUME was selected in the DENSITY
FUNCTION function (7000), (see page 141).
Use this function to display the currently measured corrected volume flow of the target
fluid. Target fluid = carried material (e.g. lime powder).
Display:
5-digit floating-point number, including unit and sign
CARRIER MASS FLOW
(0025) !Note!
This function is not available unless one of the following was selected:
• in the function DENSITY FUNCTION (7000), see page 141:
– % MASS / % VOLUME
– FLEXIBLE and in the function MODE (7010), see page 144, the selection
% MASS 2D or % MASS 3D
Use this function to display the currently measured mass flow of the carrier fluid.
Carrier fluid = transporting liquid (e.g. water).
Display:
5-digit floating-point number, including unit and sign
% CARRIER MASS FLOW
(0026) !Note!
This function is not available unless one of the following was selected:
• in the function DENSITY FUNCTION (7000), see page 141:
– % MASS / % VOLUME
– FLEXIBLE and in the function MODE (7010), see page 144, the selection
% MASS 2D or % MASS 3D
Use this function to display the currently measured mass flow of the carrier fluid as a %
(of the overall mass flow). Carrier fluid = transporting liquid (e.g. water).
Display:
5-digit floating-point number, including unit and sign
CARRIER VOLUME
FLOW
(0027)
!Note!
This function is not available unless one of the following was selected:
• in the function DENSITY FUNCTION (7000), see page 141:
– % MASS / % VOLUME
– FLEXIBLE and in the function MODE (7010), see page 144, the selection
% VOLUME 2D or % VOLUME 3D
Use this function to display the currently measured volume flow of the carrier fluid.
Carrier fluid = transporting liquid (e.g. water).
Display:
5-digit floating-point number, including unit and sign
Function description
MEASURED VARIABLES oMEASURING VALUES oADDITIONAL VALUES

Issue/Rev. 0.2 (12/12) MN0M023 • Page 15
Device Functions Proline Promass 83 3 Block MEASURED VARIABLES
% CARRIER VOLUME
FLOW
(0028)
!Note!
This function is not available unless one of the following was selected:
• in the function DENSITY FUNCTION (7000), see page 141:
– % MASS / % VOLUME
– FLEXIBLE and in the function MODE (7010), see page 144, the selection %
VOLUME 2D or % VOLUME 3D
Use this function to display the currently measured volume flow of the carrier fluid as a %
(of the overall mass flow). Carrier fluid = transporting liquid (e.g. water).
Display:
5-digit floating-point number, including unit and sign
CORRECTED CARRIER
VOLUME FLOW
(0029)
!Note!
This function is not available unless % MASS / % VOLUME was selected in the DENSITY
FUNCTION function (7000), (see page 141).
Use this function to display the currently measured corrected volume flow of the carrier
fluid. Carrier fluid = transporting liquid (e.g. water).
Display:
5-digit floating-point number, including unit and sign
% BLACK LIQUOR
(0030) !Note!
This function is not available unless %-BLACK LIQUOR was selected in the DENSITY
FUNCTION function (7000), (see page 141).
The concentration in %-BLACK LIQUOR is displayed.
Display:
5-digit floating-point number, incl. units
°BAUME
(0031) !Note!
This function is not available unless °BAUME was selected in the DENSITY FUNCTION
function (7000), (see page 141).
The concentration in °BAUME is displayed.
Display:
5-digit floating-point number, incl. units
°API
(0033) !Note!
This function is not available unless °API was selected in the DENSITY FUNCTION
function (7000), (see page 141).
The concentration in °API is displayed.
Display:
5-digit floating-point number, incl. units
Function description
MEASURED VARIABLES oMEASURING VALUES oADDITIONAL VALUES

Issue/Rev. 0.2 (12/12)
Page 16 • MN0M023
3 Block MEASURED VARIABLES Device Functions Proline Promass 83
°PLATO
(0034) !Note!
This function is not available unless °PLATO was selected in the DENSITY FUNCTION
function (7000), (see page 141).
The concentration in °PLATO is displayed.
Display:
5-digit floating-point number, incl. units
°BALLING
(0035) !Note!
This function is not available unless °BALLING was selected in the DENSITY FUNCTION
function (7000), (see page 141).
The concentration in °BALLING is displayed.
Display:
5-digit floating-point number, incl. units
°BRIX
(0036) !Note!
This function is not available unless °BRIX was selected in the DENSITY FUNCTION
function (7000), (see page 141).
The concentration in °BRIX is displayed.
Display:
5-digit floating-point number, incl. units
OTHERS
(0037) !Note!
This function is not available unless FLEXIBLE was selected in the DENSITY FUNCTION
function (7000), (see page 141) and this function is not available unless OTHERS 2D or
OTHERS 3D was selected in the MODE function (7010), (see page 144).
Displays the concentration in the unit, which was defined in the function TEXT
ARBITRARY CONCENTRATION (0606), (see page 24).
Display:
5-digit floating-point number, incl. units
Function description
MEASURED VARIABLES oMEASURING VALUES oADDITIONAL VALUES

Issue/Rev. 0.2 (12/12) MN0M023 • Page 17
Device Functions Proline Promass 83 3 Block MEASURED VARIABLES
3.2 Group SYSTEM UNITS
3.2.1 Function group CONFIGURATION
MEASURED
VARIABLES AMEASURING VALUES AAA
SYSTEM UNITS ACA CONFIGURATION 040
Function description
MEASURED VARIABLES oSYSTEM UNITS oCONFIGURATION
You can select the units for measured variables in this function group.
UNIT MASS FLOW
(0400)
Use this function to select the unit for displaying the mass flow (mass/time).
The unit you select here is also valid for:
• Current outputs
• Frequency outputs
• Relay switch points (limit value for mass flow, flow direction)
• Low flow cut off
Options:
Metric:
gram og/s; g/min; g/h; g/day
kilogram okg/s; kg/min; kg/h; kg/day
ton ot/s; t/min; t/h; t/day
US:
ounce ooz/s; oz/min; oz/h; oz/day
pound olb/s; lb/min; lb/h; lb/day
ton oton/s; ton/min; ton/h; ton/day
For arbitrary units (see function TEXT ARBITRARY MASS on page 22)
_ _ _ _ o_ _ _ _/s; _ _ _ _/min; _ _ _ _/h; _ _ _ _/day
Factory setting:
Country-dependent (kg/h or US-lb/min)
!Note!
If you defined a unit of mass in the ARBITRARY UNIT 060 function group (see page 22)
the unit in question is shown here.
UNIT MASS
(0401)
Use this function to select the unit for displaying the mass.
The unit you select here is also valid for:
• Pulse value (e.g. kg/p)
Options:
Metric og; kg; t
US ooz; lb; ton
For free selectable units o_ _ _ _ (see function TEXT ARBITRARY MASS on page 22)
Factory setting:
Country-dependent (kg or US-lb)
!Note!
• If you defined a unit of mass in the ARBITRARY UNIT 060 function group
(see page 22) the unit in question is shown here.
• The unit of the totalizers is independent of your choice here. The unit for each
totalizer is selected separately for the totalizer in question.

Issue/Rev. 0.2 (12/12)
Page 18 • MN0M023
3 Block MEASURED VARIABLES Device Functions Proline Promass 83
UNIT VOLUME FLOW
(0402)
Use this function to select the unit for displaying the volume flow (volume/time).
The unit you select here is also valid for:
• Current outputs
• Frequency outputs
• Relay switch points (limit value for volume flow, flow direction)
• Low flow cut off
Options:
Metric:
Cubic centimeter ocm3/s; cm3/min; cm3/h; cm3/day
Cubic decimeter odm3/s; dm3/min; dm3/h; dm3/day
Cubic meter om3/s; m3/min; m3/h; m3/day
Milliliter oml/s; ml/min; ml/h; ml/day
Liter ol/s; l/min; l/h; l/day
Hectoliter ohl/s; hl/min; hl/h; hl/day
Megaliter oMl/s; Ml/min; Ml/h; Ml/day
US:
Cubic centimeter occ/s; cc/min; cc/h; cc/day
Acre foot oaf/s; af/min; af/h; af/day
Cubic foot oft3/s; ft3/min; ft3/h; ft3/day
Fluid ounce ooz f/s; oz f/min; oz f/h; oz f/day
Gallon ogal/s; gal/min; gal/h; gal/day
Kilogallon oKgal/s; Kgal/min; Kgal/h; Kgal/day
Million gallon oMgal/s; Mgal/min; Mgal/h; Mgal/day
Barrel (normal fluids: 31.5 gal/bbl) obbl/s; bbl/min; bbl/h; bbl/day
Barrel (beer: 31.0 gal/bbl) obbl/s; bbl/min; bbl/h; bbl/day
Barrel (petrochemicals: 42.0 gal/bbl) obbl/s; bbl/min; bbl/h; bbl/day
Barrel (filling tanks: 55.0 gal/bbl) obbl/s; bbl/min; bbl/h; bbl/day
Imperial
Gallon ogal/s; gal/min; gal/h; gal/day
Mega gallon oMgal/s; Mgal/min; Mgal/h; Mgal/day
Barrel (beer: 36.0 gal/bbl) obbl/s; bbl/min; bbl/h; bbl/day
Barrel (petrochemicals: 34.97 gal/bbl) obbl/s; bbl/min; bbl/h; bbl/day
For arbitrary units (see function TEXT ARBITRARY VOLUME on page 23)
_ _ _ _ o_ _ _ _/s; _ _ _ _/min; _ _ _ _/h; _ _ _ _/day
Factory setting:
Country-dependent (m3/h or US-Mgal/day)
!Note!
If you defined a unit of volume in the ARBITRARY UNIT 060 function group (see
page 22) the unit in question is shown here.
UNIT VOLUME
(0403)
Use this function to select the unit for displaying the volume.
The unit you select here is also valid for: Pulse weighting (e.g. m3/p)
Options:
Metric ocm3; dm3; m3; ml; l; hl; Ml Mega
US occ; af; ft3; oz f; gal; Kgal; Mgal; bbl (normal fluids); bbl (beer);
bbl (petrochemicals) obbl (filling tanks)
Imperial ogal; Mgal; bbl (beer); bbl (petrochemicals)
For free selectable units o_ _ _ _ (see function TEXT ARBITRARY VOLUME on
page 23)
Factory setting:
m3
!Note!
• If you defined a unit of volume in the ARBITRARY UNIT 060 function group
(see page 22) the unit in question is shown here.
• The unit of the totalizers is independent of your choice here. The unit for each
totalizer is selected separately for the totalizer in question.
Function description
MEASURED VARIABLES oSYSTEM UNITS oCONFIGURATION

Issue/Rev. 0.2 (12/12) MN0M023 • Page 19
Device Functions Proline Promass 83 3 Block MEASURED VARIABLES
UNIT CORRECTED
VOLUME FLOW
(0404)
Use this function to select the unit for displaying the corrected volume flow (corrected
volume/time).
The unit you select here is also valid for:
• Current outputs
• Frequency outputs
• Relay switch points (limit value for corrected volume flow, flow direction)
• Low flow cut off
Options:
Metric:
Nl/s
Nl/min
Nl/h
Nl/day
Nm3/s
Nm3/min
Nm3/h
Nm3/day
US:
Sm3/s;
Sm3/min;
Sm3/h;
Sm3/day
Scf/s;
Scf/min;
Scf/h;
Scf/day
Factory setting:
Nm3/h
UNIT CORRECTED
VOLUME
(0405)
Use this function to select the unit for displaying the corrected volume.
The unit you select here is also valid for:
• Pulse value (e.g. Nm3/p)
Options:
Metric:
Nm3
Nl
US:
Sm3
Scf
Factory setting:
Nm3
!Note!
The unit of the totalizers is independent of your choice here. The unit for each totalizer is
selected separately for the totalizer in question.
Function description
MEASURED VARIABLES oSYSTEM UNITS oCONFIGURATION

Issue/Rev. 0.2 (12/12)
Page 20 • MN0M023
3 Block MEASURED VARIABLES Device Functions Proline Promass 83
3.2.2 Function group ADDITIONAL CONFIGURATION
MEASURED
VARIABLES AMEASURING VALUES AAA
SYSTEM UNITS ACA CONFIGURATION 040
ADD. CONFIGURATION 042
Function description
MEASURED VARIABLES oSYSTEM UNITS oADDITIONAL CONFIGURATION
UNIT DENSITY
(0420)
Use this function to select the unit for displaying the fluid density.
The unit you select here is also valid for:
• Current outputs
• Frequency outputs
• Relay switch points (limit value for density)
• Density response value for EPD
• Density adjustment value
Options:
Metric og/cm3; g/cc; kg/dm3; kg/l; kg/m3; SD 4 °C, SD 15 °C, SD 20 °C;
SG 4 °C, SG 15 °C, SG 20 °C
US olb/ft3; lb/gal; lb/bbl (normal fluids); lb/bbl (beer); lb/bbl (petrochemicals); lb/bbl
(filling tanks)
Imperial olb/gal; lb/bbl (beer); lb/bbl (petrochemicals)
Factory setting:
kg/l
SD = Specific Density, SG = Specific Gravity
The specific density is the ratio of fluid density to water density
(at water temperature = 4, 15, 20 °C).
UNIT REFERENCE
DENSITY
(0421)
Use this function to select the unit for displaying the reference density.
The unit you select here is also valid for:
• Current outputs
• Frequency outputs
• Relay switch points (limit value for density)
• Fixed reference density (for calculation of corrected volume flow)
• Current input (read in the reference density via current input)
Options:
Metric:
kg/Nm3
kg/Nl
US:
g/Scc
kg/Sm3
lb/Scf
Factory setting:
kg/Nl
This manual suits for next models
2
Table of contents
Other FMC Technologies Measuring Instrument manuals

FMC Technologies
FMC Technologies CN3 User manual

FMC Technologies
FMC Technologies Smith Meter AccuLoad II Manual

FMC Technologies
FMC Technologies Smith Meter AccuLoad User manual

FMC Technologies
FMC Technologies Smith Meter microFlow.net Liquid User manual

FMC Technologies
FMC Technologies MPU B Series Reference guide

FMC Technologies
FMC Technologies Smith Meter AccuLoad III.net Instructions for use

FMC Technologies
FMC Technologies Smith Meter AccuLoad II Manual

FMC Technologies
FMC Technologies MPU B Series Reference guide

FMC Technologies
FMC Technologies Smith Meter I-75 User manual

FMC Technologies
FMC Technologies INVALCO 64908265 User manual