Fourgroup Full-App 2 Technical manual

PR .T : FG006234
USE AND INSTALLATION HANDBOOK
Date : 27/07/15
Rev. 02 Sw. 9.8
FOURGROUP s.r.l. - Via Enrico Fermi, 8 - 35020 Polverara (PD) - ITALY

2
1. Warnings pag. 3
2. Overview 3
3. Handling 4
4. Generaldescription 4
5. Installation 5
6. Light indications and buttons 6
7. Displays 7
8. Generaloperation 10
9. Parameter setting 10
10. General settings 11
11. Settings pumps 22
12. Operatingprograms 29
13. Gsmmodemsetting 33
14. Alarmsetting 35
15. Electric connections 39
16. Applicationexamples 44
17. Stopofthepumps 51
18. M
aintenance 51
19. Wastedisposal 51
20. Spareparts 51
21. Conformitydeclaration 52
22. General conditions of sale 53
INDEX OF TOPICS

3
The following symbols, accompanied by the words: “DANGER”, “WARNING”, indicate the potential hazard
resulting from failure to observe the associated warning, as specified below:
Failure to observe this warning may result in electric shock
Failure to observe this warning may cause personal injury
and/or damage to property
Failure to observe this warning may cause damage to the
pump, the unit or the system
-CAUTION:
Make sure the pumps are fully primed before you start them.
-CAUTION:
Ensure the correct direction of rotation of the pumps.
-CAUTION:
The control panel must be connected by a qualified electrician in compliance with the electrical regulations in force.
-CAUTION:
The electric pump or the motor and the panel must be connected to an efficient grounding system in compliance with the
electrical regulations locally in force.
-CAUTION:
Ground the unit before carrying out any other operation.
-CAUTION:
The electric pump or the motor can start up automatically.
-CAUTION:
As a general rule, always disconnect the power supply before proceeding to carry out any operation on the electrical or
mechanical components of the unit or system. If you must work inside the electrical panel is also necessary to disconnect
the internal battery (installed simultaneously with GSM module).
The purpose of this manual is to provide the necessary information for the proper installation, use and maintenance of
FULL-APP 2. The user should read this manual before operating the unit. Improper use may cause damage to the machine
and lead to the forfeiture of the warranty coverage. Always specify the model identification code and the construction
number when requesting technical information or spare parts from our Sales and Service department. The instruction and
warnings given below concern the standard version; refer to the sale contract documentation for modifications and special
version characteristics. For instructions, situations and events not considered in this manual or in the sale documents,
please contact our customer service.
Our units must be installed in sheltered, well-ventilated, non-hazardous environments and must be used at a maximum
temperature of +40°C and minimum of -5°C (relative umidity 50% at 40°C not condensed).
1. WARNINGS
2. OVERVIEW

4
The panel must be handled with care, as falls and knocks can cause damage without any visible external signs.
If for any reason the unit is not installed and starter immediately after it has reached its destination it must be stored
properly. The external packaging and the separately packed accessories must remain intact, and the whole must be
protected from the weather, especially from freezing temperatures, and from any knocks or falls.
PRELIMINARY INSPECTION: after you have removed the external packaging, visually inspect the control panel to make
sure it has suffered no damage during shipping.
If any damage is visible, inform our dealer as soon as possible, no later than five days from the delivery date.
FULL-APP² is an electronic panel for direct start-up of 2 single or three phase pumps with dry running protection via cos-
φand minimum current, remote management with gsm and app.
FOURGROUP S.r.l. shall not be liable for any damage caused or suffered by the unit as a result of its
unauthorised or improper use.
GENERAL FEATURES
multi language; password; mains supply return delay; motor self-test; protections delay; 50-60Hz frequency; various
start-up alternations; simultaneous motor operation; motor exclusion; start delay; settings via GSM-APP.
GENERAL SETTINGS
self-learning of motor data; min-max current (A);min cosφ; tart delay setting; stop delay setting; max continuous
operation; max start-ups per hours; max start-ups per minute; max klixon trips; service request.
DISPLAY VIEWS
voltage (V); frequency (Hz); motor absorption(A); motors cosφ; pulseconunter; running hours; presence of GSM;
pressure (bar); water level (mt); last alarms; service request.
ALARMS, ALARMS OUTPUT AND PROTECTIONS
acoustic alarm mode; luminous alarm mode; alarms via relay; 12V alarm output; alarm delay; alarm activation
distinction; min-max water level; min-max voltage; phase error; frequency error; min-max motor current; min motors
cosφ; motors klixon trip; max klixon trips; water in oil chamber; max start-ups per hours; max start-ups per minute; max
continuous operation
DEFAULT OPERATING MODES
CLEAN
min level probe or float switch input; pressure switch or float switch inputs; emptying-filling mode; 4-20mA sensor if
present: > level-pressure views on display, > pressure-level alarm setting on display.
DARK
float switch inputs (normal or multi-contact types); max level float switch input; self-holding; emptying-filling mode; 4-
20mA sensor if present: > level-pressure views on display, > pressure-level alarm setting on display.
DIGIT
min level probe or float switch input; 4÷20mA pressure-level probe input; motor start-up pressure-level setting; motor
stop pressure-level setting; motor stop pressure-level setting.
MULTITANK
control of pumps on different systems; setting of control program for each pump; > pump 1 - possible logic modes:
CLEAN, DARK, DIGIT; > pump 2 - possible logic modes: CLEAN, DARK; 4-20mA sensor if present: > pressure-level alarm
setting on display; > level-pressure views on display; min level probe or float switch input; 4÷20mA pressure-level probe
input; motor start-up pressure-level setting; motor stop pressure-level setting.
4. GENERAL DESCRIPTION
3. HANDLING

5
Fix the control panel for a stable support with screws and screw anchor using the holes arranged in the box (fig. 1) or the
fixing bracket if present.
To fix the cables in their terminals use a tool of the proper size to avoid the damaging of the screws or of their seat. If use
an electric screwier pay attention not to spoil the thread or the screws.
After the fixing, remove every plastic or metallic surplus (ex. Pieces of copper of the cables or plastic shavings of the box)
inside the box before suppling power.
Fig.1
NOTE: do not install the control panel close to objects in contact with flammable liquids, water or gas.
Line of supply current
Connect the unit at ground before carrying out any other operation.
The voltage input corresponds to the data written on the panel and on the pumps:
( 400V ± 10% 50/60Hz x il FULL APP 2-T)
( 230V ± 10% 50/60Hz x il FULL APP 2-M).
Make sure that the power-supply-cable can bear the nominal current and connect it to the terminals of the general switch
of the control panel.
If the cables are exposed, they must be appropriately protected.
The line must be protected with a differential magnetotermic switch measured in accordance with the regulations locally in
force.
Line of motor power supply
Connect the unit at ground before carrying out any other operation.
The voltage input corresponds to the data written on the motors:
(400V±10% 50/60Hz three-phase)
(230V±10% 50/60Hz single-phase).
Doing some starting make sure that the motors respect the right direction of rotation usually indicated by an arrow
printed on the motors.
5. INSTALLATION
ATTENTION: the display / sinoptic located on the cover of the control panel is connected through one or
more cables (even cable type flat) to electronic control unit installed on the bottom of the control panel.
Pay utmost attention and care by opening the electric panel.
Once opened the control panel, support the cover so as not to damage / tear the connection cables.

6
6. LIGHT INDICATIONS AND BUTTONS
3
DISPLAY backlit blue to display the parameters of the system
AUT button to activate the automatic mode of operation; when the green led is on it
indicates the automatic functional mode is active
START green led to indicate the pump is currently working. the flashing led indicates it’s
waiting for the start timer to expire
ALARM red led to indicate an alarm is active; when the red led is on it indicates the
presence of an alarm and that made the pump stopped
AUT+UP button with dual functionality:
- button to activate the automatic functional mode; when the green led is on it indicates
the automatic functional mode is active
- button to move upward in the program menu selection
ON blue led to indicate the voltage is on and the panel is turned on by mains supply
<button to move toward left in the program menu selection
ENTER button to activate/save the menu setting; change display of the menu parameter
settings
>button to move toward right in the program menu selection
MAN button to activate the manual mode of operation
MAN+DOWN button with dual functionality:
- button to activate the manual mode of operation;
- button to move downward in the program menu selection
0button to stop the pumps and reset related alarms
4
5
10 11
2
8 9
6
7
12
1
1
2
3
4
5
6
7
8
9
10
11
12

7
The overall menu settings are composed of a series of horizontal menus that allows access to sets of horizontal and
verticals parameters. As the following flowchart example:
NOTE: on the next page shows the complete flow chart programming
When the panel is turned on the display will light up:
Subsequently the start-up routine will execute:
At the end of the start-up routine the display will show following default main display:
The main default display shows the current working parameters. By pressing the button is possible to move to
different screens and show the working parameter of the pumps (one screen for every pump; therefore, for the full-app 2,
there will be 2 screens to display the parameters of each pump):
7. DISPLAYS
HORIZONTAL
MENU’
VERTICAL PARAMETERS HORIZONTAL PARAMETERS
SOFTWARE
REVISION
YEAR
SOFTWARE
REVISION
MODEL
LANGUAGE
WAIT TIMER DELAY
RETURN POWER
Full.app³ 2015
(I) Rev.XX
Full.app³ 2015
(I) WaitXXsec
XXXV 50Hz gsm
Lev 0.00m Dig
GSM
PRESENCE
OPERATING
MODE
MAINS
VOLTAGE
P1 X.XA St XXX
Cosø X.XX h XXX
NUMBER OF
STARTS
HOURS OF
OPERATION
PUMP 1
COSø
MEASURED
P2 X.XA St XXX
Cosø X.XX h XXX
CURRENT
MEASURED
NUMBER OF
STARTS
HOURS OF
OPERATION
PUMP 2
COSø
MEASURED
CURRENT
MEASURED
FULL-APP²
Cln= CLEAN
drk= DARK
Dig= DIGIT
mlt= MULTITANK
UNIT OF SENSOR 4-20mA (if activated)
Lev 0.00m Or Lev 0.00bar
MAINS
FREQUENCY

8
ENTER PER
USCIRE DA SETUP
(PG. 10)
TELEFONO
N. 1
(PG. 33)
CONF. ALLARME
SONORO
(PG. 35)
MODALITA'
(PG. 35)
CONFIGURAZ.
(PG. 36)
CONF. ALLARME
VISIVO
(PG. 37)
MODALITA'
(PG. 37-35)
PROGRAMMI
DI FUNZIONAM.
(PG. 29)
IMPOSTAZIONI
PARAM. POMPE
(PG. 22)
IMPOSTAZIONI
GENER. QUADRO
(PG. 11)
NOME
STAZIONE
(PG. 33)
ATTIVARE
MODEM SI/NO
(PG. 33)
IMPOSTAZIONE
ALLARMI
(PG. 35)
IMPOSTAZIONE
MODEM GSM
(PG. 33)
P2 RIT. ALLARME
IMAX
P2 RIT. ALLARME
IMIN
P2 RIT. ALLARME
COSφ
TELEFONO
N. 2
(PG. 34)
PROGRAMMA
DARK
(PG. 29)
CONFIGURAZ.
POMPA 1
(PG. 22)
CONFIGURAZ.
POMPA 2
(PG. 22)
LOGICA FUNZ.
SVUOT./RIEMP.
(PG. 30)
ABILITA
DARK
(PG. 30)
PROGRAMMA
CLEAN
(PG. 29)
LOGICA FUNZ.
SVUOT./RIEMP.
(PG. 30)
ABILITA
CLEAN
(PG. 31)
PROGRAMMA
DIGIT
(PG. 30)
LOGICA FUNZ.
SVUOT./RIEMP.
(PG. 31)
ABILITA MAX
FUNZ. CONTINUO
MAX FUNZINAM.
CONTINUO
APPRENDI
ZERO
(PG. 12)
TARATURA ZERO
APPREN/IMPOST
AZ (PG: 12)
MIN.
LIV-PRESS
(PG. 13)
ABILITA MAX
AVV. MINUTO
MAX
AVVIAMENTI PER
MINUTO
0=BAR 1=MT
(PG. 12)
FONDO SCALA
(PG. 12)
ABILITA
MAX 4-20
(PG. 12)
MAX FUNZ.
CONTINUO
(PG. 24)
ABILITA MAX
AVV. ORA
(PG. 25)
RITARDO
ARRESTO
(PG. 15)
ABIL. ALLARME
TENSIONE
(PG. 16)
SELEZIONE
LINGUA
(PG. 11)
RIT. RIENTRO
RETE
(PG. 11)
ABILITA
4-20mA
(PG. 11)
GAL MAX
POMPE ON
(PG. 15)
RIT. PARTENZA
P1-P2-P3
(PG. 15)
ABILITA MAX
AVV. MINUTO
(PG. 24)
P1 RIT. ALLARME
IMAX
(PG. 23)
P1 RIT. ALLARME
IMIN
(PG. 23)
P1 RIT.
ALLARME COSφ
(PG. 23)
ABILITA MAX
FUNZ. CONTINUO
(PG. 23)
ESCLUS. RIPART.
(PG. 21)
MAX AVV.
PER MINUTO
(PG. 24)
MAX AVV.
PER ORA
(PG. 25)
IMPOSTAZIONE
PASSWORD
(PG. 22)
IMPOSTAZIONE
RIPART. 4
(PG. 21)
IMPOSTA
ZERO
(PG. 13)
LUCE DISPLAY
(PG. 22)
SETTING
PASSWORD
(PG. 22)
RESTART
SETTING
RESTART. 4
(PG. 21)
SET-UP
ZERO
(PG. 13)
LIGHT
DISPLAY
(PG. 22)
ENABLE MAX
CONT. WORKING
(PG. 23)
EXCLUDE
RESTART
(PG. 21)
MAX START
PER MINUTE
(PG. 24)
MAX STARTS
PER HOUR
(PG. 25)
SEL.
LANGUAGE
(PG. 11)
DELAY POWER
RETURN
(PG. 11)
ENABLE
4-20mA
(PG. 11)
HI. FLOAT
PUMPS ON
(PG. 15)
START DELAY
P1-P2-P3
(PG. 15)
ENABLE MAX
START MINUTE
(PG. 24)
P1 ALARM
DELAY IMAX
(PG. 23)
P1 ALARM
DELAY IMIN
(PG. 23)
P1 ALARM
DELAY COSφ
(PG. 23)
ENABLE ALARM
VOLTAGE
(PG. 16)
0=BAR
1=MT
(PG. 12)
FULL
SCALE
(PG. 12)
ENABLE
MAX 4-20
(PG. 12)
MAX CONTIN.
WORKING
(PG. 24)
ENABLE MAX
START HOUR
(PG. 25)
STOP
DELAY
(PG. 15)
LEARN
ZERO
(PG. 12)
ZERO CALIBR.
LEARN / SETS
(PG: 12)
MIN.
LEV-PRESS
(PG. 13)
ENABLE MAX
START MINUTE
MAX START
PER MINUTE
ENABLE
CLEAN
(PG. 31)
PROGRAM
DIGIT
(PG. 30)
OPERAT. MODE
EMPTY/FILL
(PG. 31)
ENABLE MAX
CONT. WORKING
MAX CONTIN.
WORKING
CONFIGURATION
PUMP 1
(PG. 22)
CONFIGURATION
PUMP 2
(PG. 22)
OPERAT. MODE
EMPTY/FILL
(PG. 30)
ENABLE
DARK
(PG. 30)
PROGRAM
CLEAN
(PG. 29)
OPERAT. MODE
EMPTY/FILL
(PG. 30)
P2 ALARM
DELAY IMAX
P2 ALARM
DELAY IMIN
P2 ALARM
DELAY COSφ
PHONE
NR. 2
(PG. 34)
PROGRAM
DARK
(PG. 29)
OPERATING
PROGRAMS
(PG. 29)
SETTINGS
PUMPS
(PG. 22)
GENERAL
SETTINGS
(PG. 11)
STATION
NAME
(PG. 33)
ENABLE MODEM
YES/NO
(PG. 33)
ALARM
SETTING
(PG. 35)
GSM MODEM
SETTING
(PG. 33)
CONFIGURATION
SOUND ALARM
(PG. 35)
MODE
(PG. 35)
CONFIGURATION
(PG. 36)
CONFIGURATION
VISUAL ALARM
(PG. 37)
MODE
(PG. 37-35)
PRESS ENTER TO
SET-UP EXIT
(PG. 10)
PHONE
NR. 1
(PG. 33)

9
RESTART
SETTING
RESTART. 2
(PG. 20)
P1 REQUEST
SERVICE
(PG. 26)
ROTATING
PUMPS
(PG. 19)
CHANGE PUMP
EVERY
(PG. 19)
RESET
SERVICE P1
(PG. 26)
SET. FREQ. MAIN
50/60HZ
(PG. 17)
AUTO SETTING
PUMP 1
(PG. 27)
MAX
CURRENT P1
(PG. 27)
SIMULTANEITY
MAX PUMPS
(PG. 19)
RESTART
SETTING
RESTART. 1
(PG. 20)
RESTART
SETTING
RESTART. 3
(PG. 20)
MAX INT.
KLIXON
(PG. 26)
ENABLE SERVICE
REQUEST
(PG. 26)
SETTING ALARM
VMAX
(PG. 16)
SETTING ALARM
VMIN
(PG. 16)
DELAY ALARM
VOLTAGE
(PG. 16)
MAX DIFFERENCE
FREQ.
(PG. 17)
DELAY ALARM
FREQ.
(PG. 17)
MAX INT.
KLIXON
ENABLE SERVICE
REQUEST
P2 REQUEST
SERVICE
ENABLE MAX
INT. KLIXON
(PG. 25)
MIN
CURRENT P2
RESET
SERVICE P2
START
LEVEL P1
(PG. 13)
STOP
LEVEL P1
(PG. 13)
START
LEVEL P2
(PG. 14)
ENABLE
MULTITANK
(PG. 32)
ENABLE MAX
START HOUR
AUTO SETTING
PUMP 2
MAX STARTS
PER HOUR
ENABLE MAX
INT. KLIXON
PHONE
NR. 3
(PG. 34)
CONNECT TEST
SMS NR. 1
(PG. 34)
ENABLE
DIGIT
(PG. 31)
PROGRAM
MULTITANK
(PG. 30)
OPERATING
MODE PUMP 1
(PG. 32)
MODE
(PG. 37-35)
CONFIGURATION
(PG. 37-36)
CONFIGURATION
RELAY 2
(PG. 37)
MODE
(PG. 37-35)
CONFIGURATION
(PG. 37-36)
FILTER READING
COEFF. K
(PG. 15)
MAX
LEV-PRESS
(PG. 14)
STOP
LEVEL P2
(PG. 14)
CONNECT TEST
SMS NR. 2
(PG. 34)
CONNECT TEST
SMS NR. 3
(PG. 34)
OPERATING
MODE PUMP 2
(PG. 32)
CONFIGURATION
RELAY 1
(PG. 37)
CONFIGURATION
(PG. 38-36)
COSφMIN
PUMP 2
COPY SETTING
PUMP 2
(PG. 28)
CONFIGURATION
(PG. 37-36)
CONFIGURATION
GSM ALARM
(PG. 38)
MODE
(PG. 38)
MAX
CURRENT P2
MIN
CURRENT P1
(PG. 28)
COSφMIN
PUMP 1
(PG. 28)
SELF-TEST
PUMPS
(PG. 17)
TIME TEST
PUMPS
(PG. 18)
MANUAL
MODE
(PG. 18)
TURN-OFF
MANUAL
(PG. 18)

10
To modify the parameter settings of operation the user will need to enter the programming mode, then you must pressing
simultaneously the two buttons and until the display shows the following password screen:
To continue the correct password is required (the default password is 0000) and press the button .
To enter a new password you need to change the parameter "Password Setting" and press the button .
NOTE: When you enter the programming mode the pumps stop.
To navigate the menus horizontally using the buttons , between the vertical parameters keys .
To exit the programming menu you need to display the following horizontal menu and press .
To quickly return to the main horizontal menu, just press repeatedly the button .
NOTE: The exit from the programming menu without saving happens automatically if you do not press any
button for 1 minute.
To modify a parameter the user needs to enter “programming mode” (explained in details in the next chapter) and then
select the desired parameter to be modified:
Pressing the button will select the digit for modification with a flashing cursor:
The buttons and will increase or decrease the value of the parameter;
the buttons and will move the cursor to the appropriate digits to allow their settings to be changed (the flashing
cursor moves to the digit):
Once the specific parameter is set to the desired value it can be saved by pressing the button . Once the parameter is
saved, the display will show briefly the message “save” as confirmation that the setting has been saved.
8. GENERAL OPERATION
9. PARAMETER SETTING
Password
0000
Press Enter to
Set-up Exit
Parameter
XXXXXX
Parameter
XXXXXX FLASHING CURSOR
Parameter
XXXXXX
Parameter
XXXXXX
Parameter
XXXXXX
Parameter
XXXXXX
Parameter
000000
Parameter
100000
Parameter
300000
Parameter
200000
Parameter
XXXXXX save

11
Once entered in the programming mode the first horizontal menu will be:
Pressing and navigate the horizontal menus. With the button displays the corresponding vertical parameter:
To move to the next horizontal parameter press the button (as indicated in the flow-chart attached to this manual as
an example, the menu structure of the horizontal parameter is circular; therefore, by pressing the buttons or the
button to display the following parameter; to facilitate the descriptions of the parameters settings the manual will
show the navigation inside the various menus:
To move to the next horizontal parameter press the button :
10. GENERAL SETTINGS
The parameter “Select Language” will set the language selection for the alarm messages to be
displayed (the “X” indicates the position of the parameter to modify):
1=Italian; 2=English; 3=Spanish; 4=French.
Factory default selection: 1-Italian.
General
settings
Press Enter to
Set-up Exit
Settings pumps
Delay Power ret.
0=RND XXXsec
Sel.Language: X
1=I 2=EN 3=E 4=F
Enable 4-20mA
0=NO 1=YES X
Delay Power ret.
0=RND XXXsec
The parameter “Delay after Power Return” will set the timer delay to wait before reactivating
the control panel after a power-cut.
The “X” indicates the digit of the parameter to modify:
The settable range value is from 0 to 999 seconds.
0: setting the value to “0” (0=RND, random) will set the timer delay to a random value
automatically (the timer value will be between 1 and 999 seconds) by the control panel at every
restart after every power-cut (this function is useful in a station with several control panels full-
app and it’s not desired the simultaneous reactivation of several control panels).
Default setting: 3 seconds.
Note: the delay timer to reactivate of the control panel is displayed as a countdown timer to the
restart after power-cut. During the countdown the operating functions are inhibited. Therefore,
it’s not possible to operate the display/settings also it is not possible to use for programming
mode, nor manual operation.
Enable 4-20mA
0=NO 1=YES X
Delay Power ret.
0=RND XXXsec
Hi.Flt.Pumps ON
0=NO 1=YES X
Enable 4-20mA
0=NO 1=YES X
The parameter “Enable 4-20mA” will allow to activate/deactivate the use of the reading device
with signal 4-20mA (for example, pressure transducer, piezoresistive sensor, ultrasounds
sensor, etc…). The activation of input 4-20mA allows the use of working in operating mode
“DIGIT”. It is possible to utilize the 4-20mA device even as simple monitor of levels and usage
of relative alarms.
The “X” indicates the position of the parameter to modify:
0=NO: input 4-20mA DISABLE.
1=YES: input 4-20mA ENABLE.
Factory default setting: 0 (DISABLE).
General
settings
Sel.Language: X
1=I 2=EN 3=E 4=F

12
Pressing the button will gain access to the set of parameters related to the reading of the input of 4-20mA device:
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
To proceed with the setting of the calibration for relative zero press the button :
Enable 4-20mA
0=NO 1=YES X
0=bar 1=mt
Value X
In the parameter “bar/mt” is possible to select the unit of measurement used in the display of
the signal 4-20 mA. In the case of pressurized system select “bar” (typically requires the
connection with a pressure transductor; in the case of a liquid/water select “m” (typically
requires a connection with a sensor of pierzoresistive level). The selection of the unit of
measurement will result in the display of a level (in meters) or a pressure (in bar).
The “X” indicates the digit position of the parameter to modify:
Factory default setting: 0 (0=bar).
Full scale
XX.XX
0=bar 1=mt
Value X
Enable Max 4-20
0=NO 1=YES X
Full scale
XX.XX
The parameter “Full Scale” is used to indicate the full scale of the sensor device 4-20 mA being
used (bar or meter depending on the mode selected in the previous parameter).
(The “X” indicates the digit of the parameter to modify).
The range of the value is from 00.00 to 99.99 (bar or meter).
Factory default setting: 16.00.
Enable Max 4-20
0=NO 1=YES X
Full scale
XX.XX
Zero Calibration
Learn / Sets
Enable Max 4-20
0=NO 1=YES X
The parameter “Enable Max 4-20” is used to start all the pumps connected, once the maximum
level is reached (the actual value of such maximum level of the sensor 4-20 mA is to be set in
the following parameters). In the case of “bar” as the selected unit of measurement, the
maximum level set is to be intended as maximum pressure.
The “X” indicates the digit of the parameter to modify:
0=NO: DISABLE the start of all pumps once the maximum level is reached.
1=YES: ENABLE the start of all pumps once the maximum level is reached.
Factor
y
default settin
g
: 0
(
DISABLE
)
.
Zero Calibration
Learn / Sets
Enable Max 4-20
0=NO 1=YES X
min. Lev-Press
XX.XX
The parameter “Zero Calibration Learn/Sets” is used to choose whether to have an auto setting
or manual setting of the RELATIVE zero of the 4-20mA sensor being used. Therefore, it’s
possible to set the “zero” not at the actual zero level (“0” meters of level or “0” bar of
pressure), but at a different level (for example, 2 meters of level or 1 bar of pressure) to
alwa
y
s maintain a
g
au
g
e.
Zero Calibration
Learn / Sets
The parameter “Learn Zero” will set the value automatically for the relative zero setting.
Pressing the button will set the value automatically as the relative zero of level/pressure at
the moment the button is
p
ressed.
Zero Calibration
Learn / Sets
Learn
Zero: XX.XX

13
To manually set the “relative zero” press the button :
Pressing the button it is possible to continue to program all the parameters relative to the 4-20mA device.
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
min. Lev-Press
XX.XX
The parameter “Minimum level” will set the level (in bar or meter depending on the mode
previously selected) for which to trigger an alarm. The alarm of minimum level will stop the
pumps and will show in the visual display and, depending on the settings of associated menu, it
can activate one or more output relays. In the case of a pressurized system this alarm
corresponds to the pressure parameter “minimum pressure level”.
(The “X” indicates the digit of the parameter to modify).
The range of value is from 00.00 to 99.99.
Factory default setting: 00.00.
Set-up
Zero: XX.XX
Learn
Zero: XX.XX
Set-up
Zero: XX.XX
The parameter “Set-up Zero” will set the value of the relative zero manually.
The “X” indicates the digit of the parameter to modify.
The range of value is from 00.00 to 99.99 (bar or meters depending on the choice made
previously).
Factory default setting: 00.00.
Zero Calibration
Learn / Sets
Enable Max 4-20
0=NO 1=YES X
min. Lev-Press
XX.XX
min. Lev-Press
XX.XX
Zero Calibration
Learn / Sets
Start Level P1
XX.XX
Stop Level P1
XX.XX
Start Level P1
XX.XX
Start Level P2
XX.XX
Start Level P1
XX.XX
min. Lev-Press
XX.XX
Stop Level P1
XX.XX
The parameter “Start Level P1” will set the level (in bar or meter units depending on the mode
previously selected) for which to start the Pump 1. In the case of a pressurized system this
alarm corresponds to the pressure parameter “Pressure start P1”.
This parameter is usable only in the DIGIT programming mode and in the MULTITANK
programming mode (only for Pump 1). In all other programming modes this parameter is
inhibited.
(The “X” indicates the digit of the parameter to modify).
The range of value is from 00.00 to 99.99.
Factory default setting: 00.00.
Start Level P1
XX.XX

14
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
Max Lev-press
XX.XX
Start Level P2
XX.XX
Filter reading
Coeff. K= XXX
Max Lev-press
XX.XX
The parameter “Max Lev-Press” (Alarm for max level or pressure) will set the level (in bar or
meter units depending on the mode previously selected) for which to trigger the alarm (high
level). At the activation of the level’s alarm, it is possible to start all pumps by setting the
parameter “Enable Max 4-20mA” (please refer to the section “Enable Max 4-20mA”). In addition
to the displayed alarm, depending on the settings of the associated menu, it is possible to
activate one or more output relays. In case of pressurized systems this alarm corresponds to
the pressure parameter “alarm level of pressure”.
(The “X” indicates the digit of the parameter to modify).
The range of value is from 00.00 to 99.99.
Factory default setting: 00.00.
Filter reading
Coeff. K: XXX
Max Lev-press
XX.XX
0=bar 1=mt
Value X
The parameter “Stop Level P1” will set the level (in bar or meter units depending on the mode
previously selected) for which to stop Pump 1. In the case of a pressurized system this alarm
corresponds to the pressure parameter “Pressure stop P1”.
This parameter is usable only in the DIGIT programming mode and in the MULTITANK
programming mode (only for Pump 1). In all other programming modes this parameter is
inhibited.
(The “X” indicates the digit of the parameter to modify).
The range of value is from 00.00 to 99.99.
Factory default setting: 00.00.
Start Level P2
XX.XX
Stop Level P1
XX.XX
Stop Level P2
XX.XX
Similarly to the previous parameter, the parameter “Stop Level P2” will set the level (in bar or
meter units depending on the mode previously selected) for which to stop the Pump 2. In the
case of a pressurized system this alarm corresponds to the pressure parameter “Pressure stop
P2”.
This parameter is usable only in the DIGIT programming mode. In all other programming
modes this parameter is inhibited.
The range of value is from 00.00 to 99.99.
Factory default setting: 00.00.
Stop Level P1
XX.XX
Stop Level P2
XX.XX
Start Level P2
XX.XX
Similarly to the previous parameter, the parameter “Start Level P2” will set the level (in bar or
meter units depending on the mode previously selected) for which to start the Pump 2. In the
case of a pressurized system this alarm corresponds to the pressure parameter “Pressure start
P2”.
This parameter is usable only in the DIGIT programming mode. In all other programming
modes this parameter is inhibited.
(The “X” indicates the digit of the parameter to modify).
The range of value is from 00.00 to 99.99.
Factory default setting: 00.00.
Stop Level P2
XX.XX
Start Level P2
XX.XX
Max Lev-press
XX.XX

15
At this point the set of parameters associated to the input reading are complete. By pressing the button it is possible
to return to the previous vertical parameter “Enable 4-20mA”:
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
Start Delay
P1-P2-P3 XXsec
Hi.Flt.Pumps ON
0=NO 1=SI X
Stop Delay
XXsec
Start Delay
P1-P2-P3 XXsec
The parameter “Start Delay P1-P2” will set a time delay on the re-start of the pumps after the
starting condition is met; for example, the activation of a start flow switch /pressure switch (for
operating modes Dark, Clean, Multitank) or once we have reached the level of activation for
signal 4-20 mA (for operating mode DIGIT). The first pump will start immediately; the start of
the second pump will be delayed accordingly by this set time value (start delay parameter).
The “X” indicates the digit of the parameter to modify.
The range of time delay start is from 4 to 99 seconds.
Factory default setting: 4 seconds.
Filter reading
Coeff. K: XXX
In parameter "Filter reading" you can increase / decrease the delay of the reading of 4-20 mA
signal: setting a low value reading signal will be faster, with a higher value will become slower.
Increase this coefficient is particularly useful in cases in which the reading signal (pressure /
Level) of the sensor becomes unstable maybe because of rapid changes in pressure / Level.
(The “X” indicates the digit of the parameter to modify).
The range of value is from 0 to 200.
Factory default setting: 50.
Hi.Flt.Pumps ON
0=NO 1=YES X
Enable 4-20mA
0=NO 1=YES X
Start Delay
P1-P2-P3 XXsec
Enable 4-20mA
0=NO 1=YES X
Delay Power Ret
0=RND XXXsec
Hi.Flt.Pumps ON
0=NO 1=YES X
In parameter " Hi.Flt.Pumps ON " you can decide the functionality of the alarm float. The alarm
float (or more generally a consensus alarm, that is a dry contact closure at which the alarm is
activated) must be physically connected to the Full-app framework (see section "Electric
connections").
The “X” indicates the digit of the parameter to modify:
1=YES: the activation of the alarm float you will have the alarm signal and depending on the
operating mode selected (see parameters menu "mode of operation") on emptying the start of
all pumps available (respecting the parameter "contemporary maximum pump ") while on filling
the stop of the pumps.
0=NO: the activation of the alarm float switch will cause only trigger the alarm signal.
Factory default setting: 0.
Hi.Flt.Pumps ON
0=NO 1=YES X
Stop Delay
XXsec
Start Delay
P1-P2-P3 XXsec
Enable Alarm
Voltage 0=NO X

16
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
Enable Alarm
Voltage 0=NO X
Stop Delay
XXsec
Setting Alarm
Vmax XXX V
Enable Alarm
Voltage 0=NO X
With the parameter “Enable Alarm Voltage” it is possible to activate/deactivate the alarm
relative to the Mains Power Voltage of the control panel full-app (Vmax e Vmin). This alarm will:
- Stop all pumps from working
- Display the alarm
- It can activate the output relay alarm (depending on the setting of the associated menu)
The “X” indicates the digit of the parameter to modify.
0=NO: by setting “0” the Voltage alarm is disabled
1=YES: by setting “1” the Voltage alarm is enabled.
Factory default setting: 0 (disable).
Setting Alarm
Vmax XXX V
Enable Alarm
Voltage 0=NO X
Setting Alarm
Vmin XXX V
Setting Alarm
Vmax XXX V
The parameter “Setting Alarm Vmax” will set a voltage threshold over which, if enabled, will
trigger the alarm.
The “X” indicates the digit of the parameter to modify.
The range of value is from 400 to 460V for full-app-T and from 230 to 260V for full-app-M.
Factory default setting: 440V (full-app-T); 253V (full-app-M).
Setting Alarm
Vmin XXX V
Setting Alarm
Vmax XXX V
Delay alarm
voltage XXsec
Setting Alarm
Vmin XXX V
The parameter “Setting Alarm Vmin” will set a voltage threshold under which, if enabled, will
trigger the alarm.
The “X” indicates the digit of the parameter to modify.
The range of value is from 340 to 400V for full-app-T and from 200 to 230V for full-app-M.
Factory default setting: 360V (full-app-T); 207V (full-app-M)
Delay alarm
voltage XXsec
Setting Alarm
Vmin XXX V
Set Freq. Main
50/60Hz XXHz
Stop Delay
XXsec
The parameter “Stop Delay” will set a time delay on the stopping of the pumps after the
stopping condition is met; for example, the opening of a stop flow switch /pressure switch (for
operating modes Dark, Clean, Multitank). Therefore, once the trigger is set for the stopping
condition the pumps will continue to work for the amount of time set in this parameter. The
Stop Delay setting will be the same for all the pumps installed. If during the Stop Delay time a
condition for a “minimum level/pressure” is met then all the pumps will stop (for operating
mode CLEAN).
The “X” indicates the digit of the parameter to modify.
The range of time delay start is from 0 to 99 seconds.
Factory default setting: 0 seconds.

17
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
The parameter “Delay Alarm Voltage” will set a delay time on the activation of the voltage’s
alarm (if previously enabled); the trigger condition (over/under voltage) must persist for the
length of time set in this parameter in order to trigger the alarm.
For example, if the Delay Alarm is set to 10 seconds and the trigger condition persists
continuously for 10 seconds it will activate the alarm; if the trigger condition persists for less
than 10 seconds the alarm will not activate.
The “X” indicates the digit of the parameter to modify.
The range of value is from 0 to 99 seconds.
Factory default setting: 5 seconds.
Set Freq. Main
50/60Hz XXHz
Delay alarm
voltage XXsec
Max Difference
Freq. X Hz
The parameter “Set Frequency Main 50/60 Hz” will set Mains Frequency of the control panel
full-app.
The “X” indicates the digit of the parameter to modify.
The range of value is from 50 to 60 Hz.
Factory default setting: 50Hz.
Max Difference
Freq. X Hz
Set Freq. Main
50/60Hz XXHz
Delay Alarm
Freq. XXsec
Max Difference
Freq. X Hz
The menu “Max Difference Frequency” will set the value (in Hz) of maximum deviation tolerable
from the nominal value of frequency that has been set. The value being set is for both positive
and negative deviation; for example, with nominal frequency being set at 50Hz, a deviation of
max frequency set to 2Hz will set the tolerable limits between 52Hz (50+2=52) and 48Hz (50-
2=48).
The “X” indicates the digit of the parameter to modify.
The range of value is from 1 to 5Hz.
Factory default setting: 2 Hz.
Note: it is not possible to disable the alarm related to the frequency; it’s always
enable.
Delay Alarm
Freq. XXsec
Max Difference
Freq. X Hz
Self-Test pumps
0=NO XXX h
Delay Alarm
Freq. XXsec
The parameter “Delay Alarm frequency” will set a time delay for the activation of the Frequency
alarm (if previously enabled); the trigger condition (over/under frequency) must persist for the
length of time set in this parameter in order to have the alarm signal.
For example, if the Delay Alarm is set to 10 seconds and the trigger condition persists
continuously for 10 seconds it will activate the alarm; if the trigger condition persists for less
than 10 seconds the alarm will not activate.
The “X” indicates the digit of the parameter to modify.
The range of value is from 0 to 99 seconds.
Factory default setting: 2 seconds.
Self-Test pumps
0=NO XXX h
Delay Alarm
Freq. XXsec
Time test
Pumps XX sec
Set Freq. Main
50/60Hz XXHz
Delay alarm
voltage XXsec

18
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
Self-Test pumps
0=NO XXX h
The parameter “Self-test pumps” will set the timer based value to be used by the Control Panel
full-app to execute all the pumps Functional Periodic Self-test (the periodic self-test is to avoid
the possibility the pumps might be blocked after being idle for a long period due to the
conditions of the system).
The “X” indicates the digit of the parameter to modify
The range of value is from 0 to 999 hours.
-0=NO: setting “0” the Pumps Self-test is disabled.
Factor
y
default settin
g
: 0.
Time test
Pumps XX sec
Self-Test pumps
0=NO XXX h
Tasto MANUALE
0=INSTABL X
Time test
Pumps XX sec
The parameter “Time Test Pumps” will set the duration of the self-test. In the situation where
the self-test is triggered on “minimum level open” (for the operating mode Dark, Clean,
Multitank) or trigger on the level of deactivation from signal 4-20 mA (for operating mode
DIGIT), the self-test will last at maximum 3 seconds regardless of the value set in this
parameter.
The “X” indicates the digit of the parameter to modify
The range of value is from 0 to 99 seconds.
Factory default setting: 5 seconds.
Note: the self-test will be executed with the following logic:
-start pump 1; operation for the time being set; stop pump 1; start pump 2; operation for the
time being set; stop pump 2.
Manual Mode
0=INSTABL X
Time test
Pumps XX sec
Turn-Off MANUAL
0=ON XXXsec
Manual Mode
0=INSTABL X
The parameter “MANUAL Mode” will set the operating mode of the buttons “MAN” for the
manual operation of the pumps.
The “X” indicates the setting of the parameter to modify
0=UNSTABL: setting “0” the MAN button should be pressed, this indicated “Operator Presence”:
the pumps will work while the button MAN is being pushed; when the button is released the
pumps will stop.
Setting “1” the operation of the pumps will continue for a programmable time (next parameter
“Turn-off MANUAL”) even after the release of the MAN button. When the timer elapses the
pumps will stop.
Factory default setting: 0.
Note: when using the mode “Operator Presence” the operation of the pumps will bypass the
protections that have been set (it is therefore necessary to verify that the manual operation will
not damage the pumps). On the other hand, the operation mode “Turn-Off MANUAL” is subject
to the protection settings.
Turn-Off MANUAL
0=ON XXXsec
Manual Mode
0=INSTABL X
Simultaneity
Max pumps nr.X
Turn-Off MANUAL
0=ON XXXsec
The parameter “Turn-off MANUAL” will set the operating time of the pumps after the button
MAN has been pressed (only if the “MANUAL Mode” has been set to “1”).
Shutdown requires pressing the button 0.
The “X” indicates the setting of the parameter to modify.
The range of value is from 0 to 999 seconds.
Factory default setting: 5 seconds.
Note: if it is set to “0” the operating mode will be “at continuous/infinite time” (the “Turn-Off
MANUAL” operating mode is subject to the protection settings).

19
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
Simultaneity
Max pumps nr.X
Turn-Off MANUAL
0=ON XXXsec
Rotating pumps
0=NO 1=R 2=A X
Simultaneity
Max pumps nr.X
The parameter “Simultaneity Max pumps” will set the number of pumps can be used
simultaneously. For example, setting the value to “1” it will have a maximum of 1 pump even if
the conditions for both pumps are active.
The “X” indicates the setting of the parameter to modify.
The range of value is from 1 to 2.
Factory default setting: 2 (FULL-APP²).
Rotating pumps
0=NO 1=R 2=A X
Simultaneity
Max pumps nr.X
Change pump
Every XXX hours
Rotating pumps
0=NO 1=R 2=A X
With the parameter “Rotating pumps” is possible to activate/select the mode in which the
pumps will alternately start.
- 0=NO: setting “0” there will be no rotation of starting pumps. The pumps will start and stop
depending on their own settings of activation and deactivation.
Note: the condition for starting pump2 will also start pump 1.
- 1=R: setting “1” the rotation is activated with the following logic:
At every activation of the first starting condition the pumps will start in a cyclic order; at every
activation of the second condition will result in the start of the second pump. The stopping of
the pumps will be by in reverse order, firstly stopping the pump that started last, and then
stopping the pump that started first.
- 2=A: setting “2” the rotation will happen based on the number of starts of each pump
(displayed under the operating parameter “St XXX”) to balance the number of starts between
the pumps. The stopping of the pumps will order the pump with the least number of starts (in
order to have it re-start next and increase the number of restarts to try to balance it).
- Setting “3” the rotation of the pumps will be based on the number of working hours of each
pump (displayed under the operating parameter “h XXX”) in order to balance the load and
number of working hours between the pumps. The stopping of the pumps will be in order of the
most working hours.
- Setting “4” will activate the timer rotation: the rotation between pumps will be based on the
programmable timer described in the next parameter (“Change Pump every XXX hour”).
- Setting “5” the rotation will have the following logic:
At every activation of the first starting condition will result in a cyclic order of the pumps; at
every activation of the second condition will result in the start of the second pump. The
stopping of the pumps will be in sequence in which the pumps started. Firstly stopping the
pump which started first and then stopping the pump that started last.
The “X” indicates the setting of the parameter to modify.
The range of value is from 1 to 5.
Factory default setting: 1.
Change pump
Every XXX hours
Rotating pumps
0=NO 1=R 2=A X
Restart Setting
Restart1 XXX min
NOTE: in the case the pump intended to start doesn’t activate (whatever the reason), the other pump will
be activated automatically (in the case is set to the parameter "Simultaneity Max pumps" to 2).
NOTE: If there is a need to manage the pumps separately is recommended to switch the program
operating to MULTITANK

20
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
Change Pump
every XXX hours
The parameter “Change pump every XXX hours” is related to the type of timer rotation that is
enabled via the previous parameter. It is possible to set the timer to how many hours it will
swap the starting priority: pump 1/pump 2; pump 2/pump 1.
The “X” indicates the setting of the parameter to modify.
The range of value is from 1 to 999 hours.
Factor
y
default settin
g
: 24h.
Restart Setting
Restart1 XXX min
Change Pump
every XXX hours
Restart Setting
Restart2 XXX min
Restart Setting
Restart1 XXX min
The parameter “Restart Setting, Restart 1” related to the Dry Running alarm (the alarm of Dry
Running is always enabled and it will trigger when it measures an operating cosø smaller than
the minimum cosø being set (parameter “cosø min pump” under the horizontal parameter
“Pump parameters”) or a pump current consumption smaller than the value of the minimum
current (parameter “Min Current pump” set in the horizontal menu “Pump parameters”). It is
possible to set the delay timer for the automatic restart after the alarm for dry running
condition. The delay time value being set is valid for all the pumps installed.
The “X” indicates the setting of the parameter to modify.
The range of value is from 1 to 999 minutes.
Factory default setting: 5 minutes.
Note: every time there is a dry running condition alarm there will be a corresponding alarm
output (one or more alarms based on the current setting refer to menu “Alarm settings”).
Restart Setting
Restart2 XXX min
Restart Setting
Restart1 XXX min
Restart Setting
Restart3 XXX min
Restart Setting
Restart2 XXX min
The parameter “Restart Setting, Restart 2”, as previous parameter, is related to the Dry
Running alarm. It is possible to set the timer delay for the automatic restart after the first timer
delay alarm for Dry Running condition. If the alarm for Dry condition is still detected after the
first restart of the pump the pump will be restarted again after restart timer 2. The time delay
value being set is valid for all the pumps installed.
The “X” indicates the setting of the parameter to modify.
The range of value is from 1 to 999 minutes and it’s independent from restart time 1.
Factory default setting: 30 minutes.
Restart Setting
Restart3 XXX min
Restart Setting
Restart2 XXX min
Restart Setting
Restart4 XXX min
Restart Setting
Restart3 XXX min
The parameter “Restart Setting, Restart 3”, as previous 2 parameters, is related to the dry
running alarm. It is possible to set the timer delay for the automatic restart after the third Dry
running alarm. If the alarm for Dry condition is still detected after the first and second restart of
the pump the pump will be restarted again using the time setting of restart setting, “Restart 3”.
The delay time value being set is valid for all the pumps installed.
The “X” indicates the setting of the parameter to modify.
The range of value is from 1 to 999 minutes and it’s independent from restart time 2.
Factory default setting: 60 minutes.
Table of contents
Other Fourgroup Control Panel manuals
Popular Control Panel manuals by other brands

Masterbuilt
Masterbuilt GF34G1M instruction sheet

Bosch
Bosch Solution-16 safecom Quick reference guide

ZKaccess
ZKaccess C3-100 Instructions for installation and use

Panasonic
Panasonic AWRP501 - HYBRID CONTROL PANEL operating instructions

AEG
AEG S 64.9 L Instructions for use

HWH
HWH 310 SERIES Operator's manual

Mircom
Mircom FX-2000 series user guide

Whelen Engineering Company
Whelen Engineering Company WeCanX CCTL7 installation guide

Frymaster
Frymaster Computer Magic operating instructions

American Lighting
American Lighting TRULUX SRF-4Z-3P installation instructions

Environment One
Environment One E/One PLC Installation and operating manual

CAME
CAME ZG6 Original-spare parts