19
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
To move to the next horizontal parameter press the button :
Restart Setting
Restart1 XXX min
The parameter “Restart Setting, Restart 1” related to the Dry Running alarm (the alarm of Dry
Running is always enabled and it will trigger when it measures an operating cosφsmaller than
the minimum cosφbeing set (parameter “cosφmin pump” under the horizontal parameter
“Pump parameters”) or a pump current consumption smaller than the value of the minimum
current (parameter “Min Current pump” set in the horizontal menu “Pump parameters”). It is
possible to set the delay timer for the automatic restart after the alarm for dry running
condition. The delay time value being set is valid for all the pumps installed.
The “X” indicates the setting of the parameter to modify.
The range of value is from 1 to 999 minutes.
Factory default setting: 5 minutes.
Note: every time there is a dry running condition alarm there will be a corresponding alarm
output (one or more alarms based on the current setting refer to menu “Alarm settings”).
Restart Setting
Restart2 XXX min
Restart Setting
Restart1 XXX min
Restart Setting
Restart3 XXX min
Restart Setting
Restart2 XXX min
The parameter “Restart Setting, Restart 2”, as previous parameter, is related to the Dry
Running alarm. It is possible to set the timer delay for the automatic restart after the first timer
delay alarm for Dry Running condition. If the alarm for Dry condition is still detected after the
first restart of the pump the pump will be restarted again after restart timer 2. The time delay
value being set is valid for all the pumps installed.
The “X” indicates the setting of the parameter to modify.
The range of value is from 1 to 999 minutes and it’s independent from restart time 1.
Factory default setting: 30 minutes.
Restart Setting
Restart3 XXX min
Restart Setting
Restart2 XXX min
Restart Setting
Restart4 XXX min
Restart Setting
Restart3 XXX min
The parameter “Restart Setting, Restart 3”, as previous 2 parameters, is related to the dry
running alarm. It is possible to set the timer delay for the automatic restart after the third Dry
running alarm. If the alarm for Dry condition is still detected after the first and second restart of
the pump the pump will be restarted again using the time setting of restart setting, “Restart 3”.
The delay time value being set is valid for all the pumps installed.
The “X” indicates the setting of the parameter to modify.
The range of value is from 1 to 999 minutes and it’s independent from restart time 2.
Factory default setting: 60 minutes.
Restart Setting
Restart4 XXX min
The parameter “Restart Setting, Restart 4”, as previous 3 parameters, is related to the dry
running alarm. It is possible to set the timer delay for the automatic restart after the 4th dry
running alarm . If the alarm for Dry condition is still detected after the first three restarts of the
pump the pump will be restarted again using the time setting restart setting ,restart 4. The
delay time value being set is valid for all the pumps installed.
The “X” indicates the setting of the parameter to modify.
The range of value is from 1 to 999 minutes and it’s independent from restart time 3.
Factory default setting: 90 minutes.
Restart Setting
Restart4 XXX min
Restart Setting
Restart3 XXX min
Exclude Restart
0=NO 1=YES ->X