Fresh-Aire UV COMMERCIAL Series Maintenance and service guide

COMMERCIAL SERIES
TUBULAR RACK SYSTEM
INSTALLATION & MAINTENANCE
WARNING
PROTECT EYES FROM UV LIGHT
TURN OFF UNIT OR DISCONNECT
BEFORE SERVICING

Parts Included
AUV Lamp(s) 1 Year
BUV Lamp(s) 2 Year
CLamp Cable
DPower Supply(s) 10”*
EPower Supply(s) 14”**
FSheet-metal Screws
G½” Pipe Straps
H½” Pipe Couplings
ILamp Clip/Conduit Clamps
JL - Mounting Brackets
KBlack Nylon Zip-Ties
LUV Warning Sticker
MSight Glass
Parts Not Included
N½” EMT Electrical Conduit (several
lengths depending on conguration)
Optional Parts
OHVertical Support Kit TUVC-VS
PCable Strain Relief TUVC-SR½, ¾, 1
QMounting Magnet TUVC-LBRKT-MG
RCable Extensions TUV-CBL5, 10
SDoor Interlock Switch TUVC-INTLCK
TStainless Steel Tubing TUVC-SST¾
U12” Stand-o TUVC-CMBRKT
VUV Shield TUVC-SHIELD32, 46, 60
WView Port TUVC-VP-O
IMPORTANT!
• Only qualified technicians should install this product*
• Install in accordance with relevant building codes
• Read instructions carefully including safety warnings
WARNING
PROTECT EYES FROM UV LIGHT
TURN OFF UNIT OR DISCONNECT
BEFORE SERVICING
* 10” Power Supply
32” lamp single & dual
** 14” Power Supply
32” lamp HO single & dual
46” lamp HO single & dual
60” lamp HO single & dual
W
J NL
M
K
B
A
F
WARNING
G
H
I
O P Q
U
R
S
T
V
E
D
The Fresh-Aire UV® Tubular Rack System is designed for installation into commercial air handling units for the
purpose of surface or airborne disinfection using ultraviolet germicidal irradiation. For maximum
installation exibility and cost-eectiveness the UV lamps are mounted onto a framework of
standard 0.5”EMT tubing (not included). The remotely mounted weather resistant power
supply can withstand the wet environment found inside of air handlers or
the exposed conditions of outdoor packaged air conditioning systems.
The number and placement of lamps is determined by several factors
including coil dimensions and whether surface or airborne disinfection is
desired. A Fresh-Aire UV® commercial UV specialist can help congure the
best system for your application.
As a general rule, standard output UV lamps are recommended for surface
treatment applications. Higher output lamps and power supplies are only
recommended for airborne treatment. Both types of systems may be
installed in a similar fashion with the same mounting hardware.
C
*Installation of this product by anyone other than licensed HVAC or electrical contractors voids warranty.
COMMERCIAL SERIES
TUBULAR RACK SYSTEM
INSTALLATION & MAINTENANCE

System Conguration
1. Determine the dimensions of the coils or area to be irradiated.
2. Use the following guidelines to estimate the number of lamps
needed for proper coverage.
Fresh-Aire UV oers a free system conguration consultation service for commercial
projects. Contact Fresh-Aire UV for details.
UV Lamp Conguration Guidelines
• Maximum germicidal eectiveness is within an 18” radius from UV lamp center axis
• The optimal distance between UV lamp(s) and the irradiated surface is 12”
• The distance between stacked UV lamps should not exceed 35”
• The distance between end to end UV lamps should not exceed 12”
• The distance of UV lamp ends to the edge of irradiated surface should not exceed 6”
3. Before attaching the L-Brackets for mounting use the Optimal Irradiation
Distance and Lamp Spacing diagrams to conrm that when installed the UV
Lamps will be positioned properly.
4. UV lamps are mounted onto a framework of EMT tubing. When 2 or more UV lamps
are supported on a single length of EMT it is recommended to use the Optional
Vertical Support Kit.
Single UV lamp per EMT piece Multiple lamps with Optional Vertical Support to prevent sagging
Height
Width
Depth
1.
12” Max. space between lamps
6” Max. space to end of coils
Single Lamp 36”
35” Max
Overlap lamps where necessary
Lamp Spacing
Tubular Rack Congurations
2
12” Lamp to Coil
18” UV Eective Radius
35”
Max
Lamp to
Lamp
Coil
Optimal Irradiation Distance

1Assemble Conduit Framework
1. Measure and cut tubing to length then slide on conduit/
lamp clamps (do not fully tighten bolts yet).
1a. Use Optional UV Shields when there are materials (such
as older brittle insulation, lter media etc.) in the air
handler which may be damaged by UVC exposure. Snap
the shield onto the lamp ends, rotate into position .
2. Use self-tapping screws to attach L-Brackets to the air
handler wall or supporting structure. Then use the ½” Pipe
Clamps to attach tubing sections to the L-Brackets.
3. Optional 12” Stand-o adaptors are available if there is no
suitable wall surface for mounting parallel to the coil.
Use self-tapping screws to attach ½” Pipe Clamp onto the
end of the stand-o. Mount the stand-o with more screws.
Then use the ½” Pipe Clamps to attach tubing sections to
the end of the Stand-o.
3a. Alternate Mounting: Attach L-Bracket with ½” Pipe
Clamps to interior of Stand-o. Then use the ½” Pipe
Clamps to attach tubing sections to the L-Bracket. This
allows lamps to be positioned less than 12”from coil.
4. Optional Vertical Support adds strength to the conduit
tubing support framework and prevents sagging on
installations with two or more lamps per tubing length.
Measure the distance from oor to ceiling then measure
and cut tubing 1.75” less than that length. Use the ½” Pipe
Couplings to extend the Vertical Support to oor and
ceiling for a snug t.
3a. Alternate Mounting
of 12” Stand-o
3. Optional
12” Stand-o
4. Optional
Vertical Support
1. Slide On Hardware
1a. Optional UV Shield
2. Mount L-bracket and Tubing
Conduit
Conduit
Conduit
Conduit/
conduit
Clamp
Vertical Support
1/2” Pipe Coupling
1/2” Pipe Coupling
3

4
2Install UV Lamps
Snap UV Lamps into the Lamp/conduit Clamps. Be sure to clamp
to the rubber lamp connector on one end and the ceramic lamp tip
on the other end. DO NOT clamp onto the lamp glass. Use Black
Nylon Zip-Ties to secure lamp cables to Tubular Rack components
and/or supports.
3Mount Power Supply(s)
Mount the power supply in a location (inside or outside of the HVAC
system) that is convenient for access to the main power supply
and for connection to the UV lamps. The power supply is weather
resistant and is suitable for mounting inside or outside of the air
handler. An Optional Power Supply Panel Mount (part # TUVC-P) is
available for mounting two or more power supplies.
1. Use the supplied self-taping sheet metal screws to mount the
power supply in place through the mounting holes on the sides
of the base. It is recommended to use wire boxes, our Optional
3/4” or 1” Cable Strain Relief, or other sealing methods in order
to pass the power cord and lamp cables into the interior of the air
handler for connections.
2. IMPORTANT! Turn o main power before making electrical
connections. Refer to the Electrical Diagram for proper
connection of the power supply to the main power.
Electrical Diagram
UV LAMP
UV LAMP
120-277 VAC
POWER SUPPLY
L1 BLACK
CONNECTORS
L2 or N WHITE
GND GREEN
IMPORTANT! Connect in accordance with all state and local
electrical and building codes. Proper voltage is automatically
selected by the unit between 120–277 VAC Single Phase 50/60 hz.
IMPORTANT! An external power suppressor is suggested if
power surges occur often.
3. Use of Optional Door Interlock Switches is highly recommended
to prevent accidental exposure to UV Light. Interlock switches are
mounted on the access panels and doors so the UV lights turn o
when the entryway is opened.
4. Use the Optional UV Output Monitor, to monitor and alert
maintenance personnel when UV lamps should be replaced.
TRIATOMICENVIRONMENTAL
WWW.FRESHAIREUV.COM
ETLLISTED
CERTIFIEDTO
CAN/USASTD
C22.2NO. 250.0
3032782
CONFORMSTO UL STANDARD 1598
Madein USA
TUVCP-1S-I
SINGLELAMP
TUVCP-1D-I
DUALLAMP
TUVCP-1T-I
TRIPLELAMP
TUVCP-1Q-I
QUADLAMP
Current: 0.94 A/120V Thru 0.40 A/277V
Current: 1.88 A/120V Thru 0.80 A/277V
Input Power: 120-277 VAC 50/60 Hz
UV WARNING!
PROTECT EYES FROM UV LIGHT
TURN OFF UNIT OR
DISCONNECT POWER
BEFORE SERVICING
TRIATOMICENVIRONMENTAL
WWW.FRESHAIREUV.COM
ETLLISTED
CERTIFIEDTO
CAN/USASTD
C22.2NO. 250.0
3032782
CONFORMSTO UL STANDARD 1598
Madein USA
TUVCP-1S-I
SINGLELAMP
TUVCP-1D-I
DUALLAMP
TUVCP-1T-I
TRIPLELAMP
TUVCP-1Q-I
QUADLAMP
Current: 0.94 A/120V Thru 0.40 A/277V
Current: 1.88 A/120V Thru 0.80 A/277V
Input Power: 120-277 VAC 50/60 Hz
UV WARNING!
PROTECT EYES FROM UV LIGHT
TURN OFF UNIT OR
DISCONNECT POWER
BEFORE SERVICING
TRIATOMICENVIRONMENTAL
WWW.FRESHAIREUV.COM
ETLLISTED
CERTIFIEDTO
CAN/USASTD
C22.2NO. 250.0
3032782
CONFORMSTO UL STANDARD 1598
Madein USA
TUVCP-1S-I
SINGLELAMP
TUVCP-1D-I
DUALLAMP
TUVCP-1T-I
TRIPLELAMP
TUVCP-1Q-I
QUADLAMP
Current: 0.94 A/120V Thru 0.40 A/277V
Current: 1.88 A/120V Thru 0.80 A/277V
Input Power: 120-277 VAC 50/60 Hz
UV WARNING!
PROTECT EYES FROM UV LIGHT
TURN OFF UNIT OR
DISCONNECT POWER
BEFORE SERVICING
TRIATOMICENVIRONMENTAL
WWW.FRESHAIREUV.COM
ETLLISTED
CERTIFIEDTO
CAN/USASTD
C22.2NO. 250.0
3032782
CONFORMSTO UL STANDARD 1598
Madein USA
TUVCP-1S-I
SINGLELAMP
TUVCP-1D-I
DUALLAMP
TUVCP-1T-I
TRIPLELAMP
TUVCP-1Q-I
QUADLAMP
Current: 0.94 A/120V Thru 0.40 A/277V
Current: 1.88 A/120V Thru 0.80 A/277V
Input Power: 120-277 VAC 50/60 Hz
UV WARNING!
PROTECT EYES FROM UV LIGHT
TURN OFF UNIT OR
DISCONNECT POWER
BEFORE SERVICING
Optional Power Supply Panel Mount
4Connect Lamps & Cables
Arrange cables as needed for installation. If necessary
use the Optional 3/4” or 1” Cable Strain Relief to pass
cables through cabinets, air system walls, etc. Optional
5’, 10’, 20’ Cable Extensions are available for longer runs.
When UV lamps, power supplies, and cables are in place
join the lamp and power supply cables by aligning the
electrical pins and anges on the rubber connectors and
pushing them rmly together.
UV Lamp
Align Pins & Lamp Key
Push Firmly Together
UV Lamp
Power Supply
Cable
Lamp Key

5
5Sight Glass Installation
1. The sight glass allows safe viewing of the UV light system when in operation. Find a
suitable location such as a door to the HVAC system for the sight glass.
2. Drill a 1” hole and press the base of the sight glass through it.
6Power-up System
Caution: UV-C light that can cause Serious Eye Burns and Temporary Blindness, Ensure all access panels have been replaced
and doors closed before powering-up the system.
Turn on the main power then switch on the UV light power supply(s). Use the sight glass to conrm that the UV Lamp(s) is
operating.
7UV System Maintenance
Periodically wipe the UV lamps with a clean cloth or alcohol swab to remove any accumulated dust or dirt. This should be
performed at least every 6-9 months or during routine maintenance intervals. Fouling could occur if lamps are installed under
chilled water lines. Wipe clean or install optional shield.
8UV Lamp Replacement
Fresh-Aire UV® lamps are rated for either one or two years
germicidal eectiveness. The lamps will continue to glow
after they have passed their rated life span but their germ-
killing eectiveness diminishes with time so they must be
replaced on schedule for the system to function properly.
Contact your local dealer for replacement lamps.
Important! Use only Fresh-Aire UV® replacement lamps.
Use of replacement lamps from other manufacturers voids
the warranty.
9Trouble Shooting
Problem Solution
UV Lamp(s) Not Lighting 1. Check that power is applied.
2. Check that the unit is turned ON.
3. Ensure the remote lamp cables are properly connected.
4. Check the fuse. Replace only with same size and type.
5. Reset power switch on power supply (o then on).
6. Install New UV Lamp(s).
7. Consult Factory.
UV Lamp(s) Flickering 1. UV Lamp(s) have reached end of eective service life. Install new lamp(s) of
same type.
2. If unit is new, check remote cables to ensure they are properly connected.
3. Reset power switch on power supply (o then on).
4. If new lamps still icker, consult factory.
UV Lamps Have burned Out Prematurely 1. Consult Factory.
Power Supply Will Not Light UV Lamps
even after new lamps are installed
1. Consult Factory.
2. External power suppressor may be needed if power surges occur.
Part# TUVCL-132 32” 1 Year Lamp
Part# TUVCL-232HO 32” 2 Year Lamp - High Output
Part# TUVCL-232-TF 32” 2 Year Lamp - Teon®
Part# TUVCL-146 46” 1 Year Lamp
Part# TUVCL-246HO 46” 2 Year Lamp - High Output
Part# TUVCL-246-TF 46” 2 Year Lamp - Teon®
Part# TUVCL-160 60” 1 Year Lamp
Part# TUVCL-260HO 60” 2 Year Lamp - High Output
Part# TUVCL-260-TF 60” 2 Year Lamp - Teon®

Fresh-Aire UV® Commercial Series
Fresh-Aire UV® lights save energy by reducing microbial growth inside HVAC systems, lower maintenance costs and reduce
maintenance workers exposure to chemicals while improving indoor air quality. Our commercial systems are renowned for
their quality materials, innovative features, ease of installation, and flexible mounting options. Most feature our advanced
multi-voltage water-resistant power supply. All come with the Fresh-Aire UV® Lifetime Warranty on all parts except lamps.
Standard Commercial UV Light System
Standard 32” lamps with L-brackets for easy installation. Choose 32”, 46”, 60” normal-output or 32” high-output lamps.
Combine single, dual, triple, quad lamp configurations to suit any size HVAC installation.
Tubular Rack System
The Fresh-Aire UV® Tubular Rack System offers easy, flexible installation of multi-lamp configurations. The Tubular Rack
System is installed using supports made with standard ½” EMT tubing (not included). You can also choose to have custom
steel tubing prepared for you by Fresh-Aire UV®. The system includes all the hardware necessary for mounting.
APCO® Rack System
Same as our Modular Rack System with the addition of activated carbon cells for photocatalytic VOC reduction.
Airborne Duct System
Features High-Output lamps for air-steam disinfection. Ideal for hospitals, clean-rooms, and other IAQ priority situations.
Panel Mount System
Installs in hard to reach areas by allowing access to the coil from the outside of the air system.
Tight-Fit Kit™
Low-voltage UV disinfection for PTACs, fan coils, & wall-mount systems.
Manufacturer’s Warranty:
This warranty supersedes and replaces any warranty statements orally made by the Sales Person, Distributor or Dealer or contained in the written instructions or other Brochures or informational documents in
relation to this product. This warranty gives you specic legal rights, and you may also have other rights which vary from State to State.
What Does This Warranty Cover? This lifetime limited manufacturer warranty covers any defects or malfunctions in material and workmanship under the normal use and service when operated and maintained
in strict accordance with manufacturer’s instructions for the Lifetime of the equipment.
How Long Does The Coverage Last? 1) Fresh-Aire UV Power Supply: For as long as you own the real property where the product is installed. 2) TUVCL-1XX Series Ultraviolet Lamp is warranted for germicidal
output for one-year from the date of installation. 3) TUVCL-2XX Series Ultraviolet Lamp is warranted for germicidal output for two (2) years from the date of installation. This warranty is not transferable.
What Will Triatomic Environmental, Inc. Do? Triatomic Environmental, Inc. will replace any defective or malfunctioning part at no charge. You must pay any labor charges and shipping charges of defective
product to our warranty department.
What Does This Warranty Not Cover? THIS PRODUCT IS NOT INTENDED TO BE PURCHASED AND INSTALLED BY UNLICENSED HVAC OR ELECTRICAL CONTRACTORS. This warranty does not cover products or parts
purchased from any source other than licensed HVAC or electrical contractors. This warranty does not cover parts installed by unlicensed HVAC or electrical contractors. This warranty does not cover parts damaged
as a result of misuse, abuse, or any use other than its intended use, accident, acts of god, neglect, or from improper operation, maintenance, installation, modication or adjustments. Triatomic Environmental,
Inc. shall have no responsibility for charges incurred by the customer for installation or removal of warranted items.
This warranty does not cover parts or equipment used with the Fresh-Aire system that are not manufactured by Triatomic Environmental, Inc.
**This warranty shall be void if UV lamps from manufacturer’s other than Triatomic Environmental, Inc. are used with this equipment.
Consequential and incidental damages are not recoverable under this warranty. Manufacturer assumes no liability for any harm, which may occur as a result of the use of the equipment herein and shall not be
liable for consequential or any other damages whether or not caused by manufacturer’s negligence or resulting from any express or implied warranty or breach thereof. Consequential damages for the purpose of
this warranty shall include, but not be limited to, loss of use, income or prot, or loss of or damages to property or injury or death to persons or animals occasioned by or arising out of operation, use, the operation,
installation, repair or replacement of the equipment or otherwise. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply
to you.
There are no Warranties which extend beyond the description of the face hereof.
How Do You Get Service? In order to be eligible for service under this warranty you MUST return the warranty registration card or register online at www.freshaireuv.com. If something is wrong with your product,
call your installing contractor to receive a Return Merchandise Authorization (RMA) and instructions for returning the product to a licensed distributor in your area or the manufacturer.
Once the product is returned, we will inspect your product and contact you within 10 business days of our receipt of the product to give the results of our inspection. If we determine that the product is covered
under this warranty, we will ship to you at no additional cost a replacement part. Replacement parts may be refurbished. If we determine that the product is not covered under this warranty, or that this warranty
is void, the product will be returned to you COD. There is no charge for inspection.
How Does State Law Apply? This warranty gives you specic legal rights, and you may also have other rights which vary from state to state.
TUVC-TRS-MAN 5.14.18
©2018 SALES@FRESHAIREUV.COM
WWW.FRESHAIREUV.COM
Made in USA
This manual suits for next models
2
Table of contents
Other Fresh-Aire UV Air Cleaner manuals
Popular Air Cleaner manuals by other brands

SK magic
SK magic ACL20C1AUS Installation & user guide

Hunter
Hunter PERMALIFE 30750 owner's manual

Envion
Envion Therapure 540 quick start guide

Goodman
Goodman GSASD-10 Installation, operation and service instructions

Samsung
Samsung AX53A9350GE user manual

Panasonic
Panasonic F-VXR50H operating instructions

Rexair
Rexair RainMate Use & care instructions

Field Controls
Field Controls UV-AIRE UV-1500C manual

Duux
Duux Sphere user manual

Electrolux
Electrolux 350 STEAMER HAND GUN installation instructions

Winix
Winix Zero S Quick setup manual

Bioclimatic
Bioclimatic MC-880 Series Installation, operation and maintenance guide