manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Frico
  6. •
  7. Controllers
  8. •
  9. Frico FCR230 User manual

Frico FCR230 User manual

FCR-230 1
FCR-230
INSTRUCTION
FCR230
Room controller for controlling fan-coil units
FCR-230 is a room controller intended for controlling fan-coil heaters/
coolers and thermal actuators or 3-point actuators. Installation is
directly on the wall or on an electrical connection box. The fan can be
set to one of three speeds.
FCR-230 has change-over function and can be used for 2-pipe or
4-pipe systems.
For integration into a system, FCR-230 has communication via
RS485 (Modbus, BACnet or EXOline). The device can be congured
using the application Regio tool (version 1.3-1-05 or later), which can
be downloaded from the Regin web site (www.regin.se).
Technical data
Supply voltage 230 V AC ±10 %, 50/60 Hz
Power consumption < 3 W
Ambient temperature 0...50°C
Ambient humidity Max 90 % RH
Storage temperature -20...+70°C
Built-in temperature sensor NTC type, range 0...50°C
Inputs Refer to connection illustrations and
table below
Outputs Relays for fan control, 230 V AC, 3 A
DO4, DO5 for actuators, Triac, 230 V AC,
max. 300 mA
Communication RS485: Modbus, EXOline (using
automatic detection/switching) or BACnet
Modbus 8 bits, 1 or 2 stop bits. Odd, even
(FI) or no parity
Communication speed 9600, 19200, 38400 bps (EXOline, Modbus
and BACnet) or 76800 bps (BACnet only)
Terminal blocks Lift type for a maximum cable area 2.1 mm2
Protection class IP20
Pollution degree 2
Overvoltage category 3
Material casing Polycarbonate, PC
Dimensions 102 x 120 x 29 mm
Installation
Place the controller in a location that has a temperature representative for
the room. A suitable location is approx. 1.6 m above oor level in a place
with unobstructed air circulation.
Depress the locking tab in the upper edge of the controller with a
screwdriver. Carefully turn the screwdriver until the bottom plate and the
electronics unit are slightly separated (see gure 1). Then use the cutout
that becomes visible in the edge of the bottom plate to open the upper
edge completely (see gure 2). Do the same thing in the lower edge of the
controller.
Figure 1 Figure 2
Lift the electronics unit up from the bottom plate. The bottom plate with
terminals has a number of hole combinations. Select suitable holes and
fasten the bottom plate on the wall or connection box, so that the arrows
on the bottom plate point upwards. Do not tighten the screws too hard!
Note: FCR-230 does not indicate fan breakdown or overheating of the
heating coil. Therefore, all connections must be made externally. An
overheating protection or similar can be used to disconnect the supply
voltage.
Disconnection
FCR-230 should be connected to a switch or circuit breaker in the
building installation. This switch should be in close proximity to the
controller and within easy reach of the operator, and should be
marked as the disconnecting device for the equipment.
Always use the circuit breaker to disconnect the controller from the
mains supply during maintenance of the fan-coil and actuators.
Settings
Control modes
FCR-230 can control heating and cooling in sequence or be set to
seasonal switching between heating and cooling (change-over, see
below).
Change-over function
FCR-230 has an input for change-over that automatically resets the
output DO4 to operate with heating or cooling function. When the con-
troller is used together with a 3-position actuator, output DO5 is also
a󰀨ected by the change-over function in accordance with the above. A
sensor of type PT1000 can be connected to the input and be mounted
so that it senses the temperature on the supply pipe to the coil.
When the temperature exceeds 28°C, the output function is set to
heating and when the temperature drops below 16°C, the output is
set to cooling. As an alternative, a potential-free contact can be used.
The input function can be set to NO/NC.
To ensure satisfactory functioning when using a sensor, the system
must have continuous primary circuit circulation. When the change-
over function is not used, the input must be left disconnected.
When using an electric heater and the change-over function is set to
heating, the sequence of operation for FCR-230 will be heating/heat-
ing and DO5 will be activated rst.
If a change-over sensor is not connected, the sequence will be heat-
ing/heating. If cooling is to be used in the sequence, parameter 2
(change-over mode) must be changed manually.
Operating mode
There are four di󰀨erent operating modes. Switching between these
modes is performed locally.
Comfort: is shown in the display. Heating and cooling have a
smaller neutral zone NZC. An occupancy detector can be connected
to the DI in order to select between Comfort and Economy. Switching
between Comfort/Economy and O󰀨 can also be done via the On/O󰀨
button. Comfort/Economy is selected via the parameter list.
EN
Instruction for products with software version 1.2.
Read this instruction before installation and wiring
of the product. This product is BTL listed from
software version 1.2-1-00 (BACnet stack 3.0.4).
Consult documentation in all cases where this symbol
is used, in order to nd out the nature of the potential
hazards and any actions to be taken
i
FCR-230 2
Economy (Standby): “Standby” is shown in the display. The heat-
ing and cooling setpoints are freely adjustable. Factory settings:
heating=15°C, cooling=30°C.
O: The controller does not heat or cool and the fan stops (unless
mould protection has been selected or the cool-down function for the
electric heater is running, in which case the fan will still run).
Window: is shown in the display, the controller is o󰀨 and the fan
stops (unless mould protection has been selected or the cool-down
function for the electric heater is running, in which case the fan will
still run). The window contact is connected to the DI and must be
congured.
Occupancy detection
Parameter 3 determines if the DI is window contact input or
occupancy detection input. An occupancy detector can be connected
to the DI in order to switch between Comfort and Economy mode.
Setpoint
The setpoint is set using the INCREASE and DECREASE buttons.
Parameter 24 determines what is shown in the display. Refer to the
parameter list for details.
Setpoint limitation
In parameters 34 and 35, it is possible to set the maximum allowed
setpoint increase and decrease respectively.
Example: If P35=5 and P34=3, the setpoint can be changed between
17°C and 25°C (see the picture below).
The basic setpoint can be changed in parameter 64 (factory
setting=22°C).
Figure 3: Example of setpoint limitation
Fan control
The fan can be controlled via FCR-230 with the following modes: Low
speed, Medium speed, High speed, Auto. The current fan speed in
the Auto mode depends on the heating or cooling demand and the
settings for each speed.
When using automatic control, ”AUTO” is shown in the display.
The number of fan speed steps can be selected via parameter 30.
If the parameter is set to 1, the rst fan speed step will be used for fan
control.
Via parameter 31, it is possible to set the fan to the lowest speed level
when Auto mode is selected. If this parameter is set to 1, the fan will run
in all operating modes except O󰀨 and Window (unless mould protection is
active or the cool-down function for the electric heater is running, in which
case the fan will run in these modes as well).
Manual control of the fan speed
By pressing the fan button, you change the fan speed according to the
sequence IàIIàIIIàAUTO. When using manual control, ”MAN” is shown
in the display.
If the fan has been congured not to be a󰀨ected by the heating or cooling
demand, ”AUTO” will not be shown when pressing the fan button.
Indications
The display has the following indications:
HEAT Heating control
COOL Cooling control
The open window symbol is shown if this function has
been congured and a window is open.
OFF The controller does not heat or cool
On/O󰀨 button
By pressing the On/O󰀨 button, FCR-230 will switch between O󰀨 mode
and Comfort/Economy mode.
Parameter list
When the controller is in Comfort mode or Window mode, di󰀨erent param-
eter values can be set in a parameter list.
Hold the INCREASE and DECREASE buttons depressed simultaneously
for about 5 seconds until the Service symbol is displayed and then press
the INCREASE button twice.
First the display will show parameter 1. Use the INCREASE and DE-
CREASE buttons to scroll between the parameters and press the On/O󰀨
button to select the desired parameter. The parameter number will then
be replaced by the parameter value. The value can be changed using the
INCREASE and DECREASE buttons. If a button is held depressed the
value will start scrolling, rst slowly and then with increasing speed.
To exit the parameter list and go back to the basic display, press the IN-
CREASE button until “EXIT” is shown (one step before parameter 1) and
press the On/O󰀨 button. You can also exit the parameter list by pressing
down the INCREASE and DECREASE buttons simultaneously.
Parameters
The following parameters can be changed in the parameter list.
Nº = parameter number
FS = factory setting
NO = normally open
NC = normally closed
Nº Description FS
1 Control mode:
2=2-pipe system
3=4-pipe system
4=(Electric heater) N/A
3
2 Change-over mode:
0=Heating control, 1=Cooling control, 2=Automatic
change-over depending on analogue temperature
sensor or digital input
0
3 Operating mode when activating digital input 1,
terminal 40/41:
0=Economy mode (occupancy detector)
1=O󰀨 mode (window contact)
0
4 Mould protection:
0=Not active
1=Active (fan never stops)
0
5 Neutral zone at Comfort mode (NZC). If the neu-
tral zone is 2 K, the heating setpoint is equal to the
setpoint minus 1 and the cooling setpoint is equal
to the setpoint plus 1.
0 K
6 Heating setpoint when unoccupied 15°C
7 Cooling setpoint when unoccupied 30°C
8 P-band for the room controller 10 K
9 I-time for the room controller 300 s
10 Not used for this model
11 Switch o󰀨 timer for Comfort mode 0 min
12 Switch on delay for Comfort mode 0 min
13 Sensor connected to AI1, terminal 42/43:
0=Internal sensor, 1=External room sensor
0
14 Sensor connected to UI1, terminal 43/44:
0=None, 1=Change-over digital, 2=Change-over
analogue
0
15 Type of digital actuator:
0=Thermal, 1=3-point
0
16-
17
Not used for this model
FCR-230 3
Nº Description FS
18 Period time for heating actuator with
thermal actuator
60 s
19 Period time for cooling actuator with
thermal actuator
60 s
20 Runtime for heating actuator with increase/de-
crease actuator
120 s
21 Runtime for cooling actuator with increase/de-
crease actuator
120 s
22 Time in hours between exercise of heating actua-
tor
23
23 Time in hours between exercise of cooling actua-
tor
23
24 Setpoint or actual value shown in the display:
0=Actual, setpoint when changing the setpoint,
1=Actual, setpoint adjustment when changing the
setpoint, 2=Setpoint, 3=Only the setpoint adjust-
ment
0
25 Conguration of fan control:
0=No control, 1=The fan is controlled by heating
requirement, 2=The fan is controlled by cooling
requirement, 3=The fan is controlled by heating
and cooling requirement
When using an electric heater, this parameter
should only be set to 1 or 3, or the heater may be
overheated.
3
26 Start signal in % of the controller output, heating
or cooling, for fan speed 1
20 (5
when
using an
electric
heater)
27 Start signal in % of the controller output, heating
or cooling, for fan speed 2
60
28 Start signal in % of the controller output, heating
or cooling, for fan speed 3
100
29 Hysteresis for start/stop of fans in % of the control-
ler output. (N/A)
5
30 Number of fan speeds (N/A) 3
31 Fan speed in the Auto mode:
0=The fan speed follows the cooling/heating
output, 1=The fan speed is minimum limited to
the lowest speed
0
32 Temperature compensation on AI1 0 K
Nº Description FS
33 Temperature compensation for the internal room
sensor
0 K
34 Highest permitted setpoint o󰀨set upwards. Set-
table value=0...13 K. Starting point=22°C.
13 K
35 Highest permitted setpoint o󰀨set downwards. Set-
table value=0...17 K. Starting point=22°C.
17 K
36 NO/NC digital input 1:
0=NO, 1=NC
0
37 NO/NC universal input 1:
0=NO, 1=NC
0
38 NO/NC digital output 4:
0=NO, 1=NC
1
39 NO/NC digital output 5:
0=NO, 1=NC
1
40 Manual/Auto heating output signal:
0=O󰀨, 1=Manual, 2=Auto
2
41 Manual/Auto cooling output signal:
0=O󰀨, 1=Manual, 2=Auto
2
42 Heating output signal in manual mode 0
43 Cooling output signal in manual mode 0
44 Model -
45 Version Major -
46 Version Minor -
47 Released or beta version -
48 Revision -
49 Display backlight low 0
50 Display backlight high 30
51 EXOline PLA address -
52 EXOline ELA address -
53 Modbus address 254
54 Modbus communication parity bit:
0=No parity, 1=Odd parity, 2=Even parity
2
55 Modbus timeout for character (t1.5) in ms. Should
be 1.5 times a character, i.e. at least 2 ms.
2 ms
56 Modbus answer delay (t3.5) in ms. Should be 3.5
times a character, i.e. at least 5 ms.
5 ms
57 Communication protocol:
0=EXOline/Modbus, 1=BACnet MS/TP
0
58 BACnet MS/TP MAC address
0-127=master address, 128-254=slave address
-
Nº Description FS
59 The 4 low numbers in the BACnet device ID,
0-9999
-
60 The 3 high numbers in the BACnet device ID -
61 BACnet MS/TP Max. master 127
62 Communication protocol speed:
0=9600 bps, 1=19200 bps, 2=38400 bps,
3=76800 bps (alternative 3 only applies to BAC-
net)
0
63 Resets communication parameters (not address-
es) to their factory settings:
1=Factory settings (EXOline/Modbus@9600)
0
64 Basic setpoint. Settable value=5...50°C. 22°C
Recommended settings for Frico convectors:
Nº TKW heat TKW cool TKW change over
2 0 (FS) 1 2
14 0 (FS) 0 (FS) 2
31 0 (FS) 0 (FS) 0 (FS)
Nº SL/SLS R
heat
SL/SLS R
cool
SL/SLS R
change over
2 0 (FS) 1 2
14 0 (FS) 0 (FS) 2
31 1 1 1
Wiring
10 20 30
LOGIC
40 50
POWER
Figure 4: Bottom plate connections
FCR-230 4
Connection of di󰀨erent actuators
When connecting thermal actuators, DO4 is used for heating actuators
and DO5 for cooling actuators. If the installation is a 2-pipe installation
and the change-over function is used, the actuator should be connected
to DO4.
When connecting 3-point actuators, DO4 is used for increase signal and
DO5 for decrease signal, even when the change-over function is used.
10 L 230 V AC Line Power supply
11 - Not connected
12 N 230 V AC Neutral Power supply (internally con-
nected to terminal 13)
13 N Fan-coil common /
230 V AC Neutral
Common fan-coil connec-
tor (internally connected to
terminal 12)
20 DO1 Fan-coil output 1
for fan control
Relay, 230 V AC*, 3 A
21 DO2 Fan-coil output 2
for fan control
Relay, 230 V AC*, 3 A
22 DO3 Fan-coil output 3
for fan control
Relay, 230 V AC*, 3 A
30 - Not connected
31 DO4 Digital output 4 for
heating/cooling
or opening with
3-point actuator
Digital output. 230 V AC, max
300 mA. Max 2 A during 20
ms.
32 CDO45 Common DO4 & 5 Common connection for
digital outputs 4 and 5
33 DO5 Digital output 5 for
cooling or closing
with 3-point actua-
tor.
Digital output. 230 V AC, max
300 mA. Max 2 A during
20 ms.
40 DI Digital input Potential-free window contact
or occupancy contact. Con-
gurable for NO/NC.
41 Agnd Analogue ground
42 AI Analogue input External PT1000 instead of
the internal NTC
43 UI Universal input Change-over input. Potential-
free switch (congurable for
NO/NC) or PT1000.
44 Agnd Analogue ground
50 Agnd Analogue ground
51 - Analogue out A0I EC fan
52 - Not connected
53 A RS485 communication A
54 B RS485 communication B
*The sum of the current through DO1-DO3 is protected by a fuse
Low Voltage Directive (LVD) standards / EMC emissions &
immunity standards
This product conforms to the EMC and LVD requirements in the
European harmonised standards EN 60730-1:2000 and EN 60730-2-
9:2002 and carries the CE mark.
RoHS
This product conforms to the Directive 2011/65/EU of the European
Parliament and of the Council.
Contact
Frico AB, Industrivägen 41, 433 61 Sävedalen, Sweden
Tel: +46 31 336 86 00, Fax: +46 31 26 28 60
www.frico.net, [email protected]
Figure 5: Connection diagram with water heater
Figure 6: internal placement
Figure 8: External placement
ECGT1
Modbus
EXOline
BACnet
M
Modbus
EXOline
BACnet
M
B
AO1
0 V Y
EC fan

Other Frico Controllers manuals

Frico ERP User manual

Frico

Frico ERP User manual

Frico IHMC6-3 User manual

Frico

Frico IHMC6-3 User manual

Frico CIRT User manual

Frico

Frico CIRT User manual

Frico IHBD3 Operation and maintenance manual

Frico

Frico IHBD3 Operation and maintenance manual

Popular Controllers manuals by other brands

Show Tec PLE-30-080 manual

Show Tec

Show Tec PLE-30-080 manual

Lily Tech ZL-6280A instruction manual

Lily Tech

Lily Tech ZL-6280A instruction manual

effeff 750 operating instructions

effeff

effeff 750 operating instructions

Hobby-Wing XRotor Micro 20A 4IN1 user manual

Hobby-Wing

Hobby-Wing XRotor Micro 20A 4IN1 user manual

Go Power GP-PWM-10 owner's manual

Go Power

Go Power GP-PWM-10 owner's manual

EZAutomation EZ TouchPLC Micro manual

EZAutomation

EZAutomation EZ TouchPLC Micro manual

red lion Sixnet ST-IPm-8460 Hardware guide

red lion

red lion Sixnet ST-IPm-8460 Hardware guide

Oriental motor DSC Series operating manual

Oriental motor

Oriental motor DSC Series operating manual

Delta ASDA-A2 Series quick start

Delta

Delta ASDA-A2 Series quick start

Contro l4 HC-250 quick start guide

Contro l4

Contro l4 HC-250 quick start guide

3D R IRIS PIXHAWK Mounting, Electrical Connection, Adjustment

3D R

3D R IRIS PIXHAWK Mounting, Electrical Connection, Adjustment

Aqua Medic EcoDrift Wireless Master Operation manual

Aqua Medic

Aqua Medic EcoDrift Wireless Master Operation manual

V3 SOUND V3 CONTROL user manual

V3 SOUND

V3 SOUND V3 CONTROL user manual

AirLive WLAN-64GM QIG

AirLive

AirLive WLAN-64GM QIG

Black Box MCX-G2-CONTROL-24 user manual

Black Box

Black Box MCX-G2-CONTROL-24 user manual

Ebmpapst VTD-60.05-K5C-S Translation of the original operating instructions

Ebmpapst

Ebmpapst VTD-60.05-K5C-S Translation of the original operating instructions

EP Solar ViewStar Series user manual

EP Solar

EP Solar ViewStar Series user manual

Intech Instruments Ltd IN-RTB installation guide

Intech Instruments Ltd

Intech Instruments Ltd IN-RTB installation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.