Friedrich Küpper J Series Guide

1 PB
Service/ Parts Manual
J-Series Single- Zone
Cassette and Ducted
96991405_00
Type Model
Outdoor Condensor MR36UY3J
Outdoor Condensor MR24UY3J
Indoor Cassette MC36Y3J
Indoor Cassette MC24Y3J
Indoor Ducted MD36Y3J
Indoor Ducted MD24Y3J

2 PB
TABLE OF CONTENTS
Table of Contents
INTRODUCTION‑ 6
Important Safety Information‑ 6
Personal Injury Or Death Hazards‑ 8
Model Identification Guide‑ 9
Model Line Up‑ 10
Control systems (standard)‑ 11
SPECIFICATIONS‑ 12
Ceiling Cassette 4‑way ‑ 12
Ceiling Concealed Duct (High Static)‑ 13
Outdoor Units DC Inverter SINGLE ZONE‑ 14
Operation Range‑ 16
Electric characteristics‑ 17
Product Dimensions‑ 19
Ceiling Cassette 4‑way 24k‑ 19
Ceiling Cassette 4‑way 36k‑ 20
Ceiling Concealed Duct (High Static) 24k‑ 21
Ceiling Concealed Duct (High Static) 36k‑ 22
Outdoor Units DC Inverter SINGLE ZONE 24k‑ 23
Outdoor Units DC Inverter SINGLE ZONE 36k‑ 24
Capacity Tables‑ 25
Models : MR24UY3J + MC24Y3J‑ 25
Models : MR24UY3J + MC24Y3J‑ 26
Models : MR24UY3J + MD24Y3J‑ 27
Models : MR24UY3J + MD24Y3J‑ 28
Models : MR36UY3J + MC36Y3J‑ 29
Models : MR36UY3J + MC36Y3J‑ 30
Models : MR36UY3J + MD36Y3J‑ 31
Models : MR36UY3J + MD36Y3J‑ 32
Sound Pressure Data‑ 33
Ceiling cassette 4‑way‑ 33
Ceiling Concealed Duct (High Static)‑ 34
Outdoor Units DC Inverter SINGLE ZONE ‑ 35
Air flow and temperature distributions‑ 36
Ceiling cassette 4‑way‑ 36
Piping Diagrams‑ 37
Ceiling cassette 4‑way‑ 37
Ceiling Concealed Duct (High Static)‑ 38
Outdoor Units DC Inverter SINGLE ZONE‑ 39
Capacity coefficient factor‑ 40
Outdoor Units DC Inverter SINGLE ZONE‑ 40
OPERATION 41
Functions and Controls‑ 41
List of Functions and Controls‑ 41
Basic Mode Controls‑ 42
Special Mode Controls‑ 44
Utility Functions‑ 45
Ceiling Concealed Duct (High Static)‑ 48
Product Introduction‑ 48
Simple Wired Remote Controller‑ 49
Standard Operation ‑ Cooling Mode‑ 50
Standard Operation ‑ Heating Mode‑ 51
Standard Operation ‑ Dehumidification Mode‑ 52

3 PB
TABLE OF CONTENTS
Standard Operation ‑ Fan Mode‑ 53
Function Setting ‑ Fan Speed Selection‑ 54
Function Setting ‑ Room Temperature Check‑ 55
Function setting ‑ Child Lock‑ 56
Simultaneous Mode Lockout‑ 57
Maintenance and Service‑ 58
List of Functions‑ 59
How To Set E.s.p. On The Remote Controller‑ 60
Ceiling cassette‑ 62
Product Introduction‑ 62
Operation Indication Lamps‑ 63
Operating Method‑ 63
Wireless Remote Controller‑ 64
Cooling Mode ‑ Standard Operation‑ 65
Cooling Mode ‑ Power Cooling‑ 66
Heating Mode‑ 67
Dehumidification Mode‑ 68
Fan Mode‑ 69
Energy saving cooling mode‑ 70
Auto Clean operation‑ 71
Temperature setting/ room temperature check‑ 72
Celsius/Fahrenheit Switching‑ 73
Setting the Current Time‑ 73
Sleep Timer Setting‑ 73
On Timer Setting‑ 74
Off Timer Setting‑ 74
To cancel the Timer Setting‑ 74
Airflow Direction Control (Optional)‑ 75
Forced operation‑ 76
Maintenance and Service‑ 77
List of functions‑ 78
Outdoor Units DC Inverter SINGLE ZONE ‑ 79
List of functions‑ 79
INSTALLATION‑ 80
Installation process & Guideline‑ 80
Checking the drawing‑ 81
Guideline for each installation process‑ 82
Indoor Unit Ceiling Cassette‑ 117
Indoor Unit Ceiling Concealed Duct‑ 125
I nstallation of Oudoor unit‑ 137
Ventilation Kit‑ 146
Safety Precautions‑ 146
Included Items‑ 147
Assembly Diagram‑ 148
Ventilation Kit Installation (DVKA)‑ 149
Flange Installation (DVKB)‑ 150
Front Panel Installation‑ 152
Electrical Wiring To The Indoor Unit‑ 156
REPAIR‑ 157
2‑Way, 3‑Way Valve‑ 157
Pumping Down‑ 158
Evacuation (All amount of refrigerant leaked)‑ 159
Gas Charging (After Evacuation)‑ 160

4 PB
TABLE OF CONTENTS
COMPONENTS TESTING‑ 161
Circuit Board Diagram‑ 161
Ceiling Cassette 4‑way‑ 161
Ceiling Concealed Duct (High Static) 24k‑ 162
Ceiling Concealed Duct (High Static) 36k‑ 163
Outdoor 24k‑ 164
Outdoor 36k‑ 165
Branch Diagram ‑ Cassette‑ 166
Single Branch Duct _ Single Zone‑ 166
Ducting “2” side branches _ Single Zone‑ 167
Setting Vane angle using DWC1‑ 168
MC24Y3J‑ Branch Duct Dimensions‑ 170
MC36Y3J‑ Branch Duct Dimensions‑ 171
TROUBLESHOOTING‑ 172
Test Run‑ 172
Check Before Test Run‑ 172
Test Run Flow Chart‑ 173
Test Run Detail‑ 174
Cycle Troubleshooting GuideTest Run Detail‑ 175
Electronic Parts Troubleshooting Guide‑ 178
Self‑diagnosis Function‑ 182
Troubleshooting Guide (Indoor Unit)‑ 185
Check Points‑ 186
Check Points‑ 187
Resistance ‑ Temp. Sensor Table‑ 187
CH04 ‑ Float Switch‑ 188
CH05 ‑ Poor Comunication (Indoor<‑> Outdoor Unit)‑ 189
CH10 ‑ Fan Locking‑ 190
CH 21: DC Peak Error‑ 192
CH 22: CT2 Error (Input Over‑Current)‑ 195
CH23: DC Link Low Voltage Error‑ 197
CH26: DC Comp Position Error‑ 199
CH27: PSC Fault Over‑current Error‑ 201
CH29: Compressor phase Over‑current Error (only verifiable at Outdoor unit PCB Assembly)‑ 202
CH32: Inverter Compressor D‑Pipe Overheat Error‑ 203
CH40: CT Sensor Error (Open/Short)‑ 204
CH41/44/45/65: Inv D‑Pipe/Outdoor Inlet/Cond. Pipe/Heat sink Sensor Error‑ 205
CH53: Outdoor Unit <‑> Indoor Unit Communication Error‑ 206
CH60: Outdoor Unit PCB EEPROM Error‑ 209
CH62/65: Heat Sink Error‑ 211
CH67: Outdoor BLDC Fan Lock Error‑ 213
Ceiling Cassette‑ 214
Installer Setting Mode‑ 214
Ceiling Concealed Duct (High Static)‑ 216
Error Codes‑ 216
Dip Switch Setting‑ 217
24‑36k Outdoor Units‑ 218
Error Codes‑ 218
Night Silent Operation Setting‑ 219
WIRING DIAGRAMS‑ 220
Ceiling cassette 4‑way‑ 220
Ceiling Concealed Duct (High Static) 24k‑ 221
Ceiling Concealed Duct (High Static) 36k‑ 222

5 PB
TABLE OF CONTENTS
Outdoor Unit DC Inverter SINGLE ZONE 24k‑ 223
Outdoor Unit DC Inverter SINGLE ZONE 36k‑ 224
Outdoor Unit DC Inverter SINGLE ZONE ‑Field Wiring‑ 225
PARTS CATALOG‑ 226
Ceiling Cassette 4‑way ‑ 226
Ceiling Concealed Duct (High Static) 24k‑ 229
Ceiling Concealed Duct (High Static) 36k‑ 231
Outdoor Unit DC Inverter SINGLE ZONE 24k‑ 233
Outdoor Unit DC Inverter SINGLE ZONE 36k‑ 236
APPENDIX‑ 239
Appendix 1: Reference Sheet of Celsius and Farenheit‑ 239
ACCESSORIES‑ 240
LIMITED WARRANTY‑ 241
CUSTOMER SATISFACTION and QUALITY ASSURANCE‑ 242
FRIEDRICH AUTHORIZED PARTS DEPOTS‑ 242

6 PB
INTRODUCTION
The information in this manual is intended for use by a qualified technician who is familiar with the safety procedures
required for installation and repair, and who is equipped with the proper tools and test instruments required to service
this product.
Installation or repairs made by unqualified persons can result in subjecting the unqualified person making such repairs
as well as the persons being served by the equipment to hazards resulting in injury or electrical shock which can be
serious or even fatal.
Safety warnings have been placed throughout this manual to alert you to potential hazards that may be encountered. If
you install or perform service on equipment, it is your responsibility to read and obey these warnings to guard against
any bodily injury or property damage which may result to you or others.
Important Safety Information
Your safety and the safety of others is very
important.
We have provided many important safety messages in this manual and on your appliance. Always read
and obey all safety messages.
This is a safety Alert symbol.
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol with the word “WARNING”
or “CAUTION”. These words mean:
Indicates a hazard which, if not avoided, can result in severe personal
injury or death and damage to product or other property.
Indicates a hazard which, if not avoided, can result in personal injury and
damage to product or other property.
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of
injury, and tell you what will happen if the instructions are not followed.
Indicates property damage can occur if instructions are not followed.
WARNING
NOTICE
CAUTION
WARNING
Refrigeration system
under high pressure
Do not puncture, heat, expose to flame or
incinerate.
Only certified refrigeration technicians should
service this equipment.
R410A systems operate at higher pressures
than R22 equipment. Appropriate safe service
and handling practices must be used.
Only use gauge sets designed for use with
R410A.
Do not use standard R22 gauge sets.

7 PB
Important Safety Information INTRODUCTION
WARNING
Please read this manual thoroughly prior to equipment
installation or operation. It is the installer’s responsibility
to properly apply and install the equipment. Installation
must be in conformance with the NFPA 70‑2008 National
Electric Code or current edition, International Mechanic
code 2009 or current edition and any other applicable local
or national codes.
WARNING
Refrigeration system under high pressure. Do not
puncture, heat, expose to flame or incinerate. Only certified
refrigeration technicians should service this equipment.
R410A systems operate at higher pressures than R22
equipment. Appropriate safe service and handling practices
must be used. Only use gauge sets designed for use with
R410A. Do not use R22 gauge sets. Failure to do so can
result in property damage, personal injury, or death.
WARNING
Electrical shock hazard.
Turn OFF electric power before service or installation.
Unit must be properly grounded.
Unit must have correct fuse or circuit breaker
protection. Unit’s supply circuit must have the correct
wire conductor size. All electrical connections and
wiring must be installed by a qualified electrician and
conform to the National Electrical Code and all local
codes which have jurisdiction. Failure to do so can
result in property
damage, personal injury and/or death.
Your safety and the safety of others are very
important.
We have provided many important safety messages in
this manual and on your appliance. Always read and
obey all safety messages.
This is the safety Alert symbol.
This symbol alerts you to potential
hazards that can kill or hurt you
and others.
All safety messages will follow the
safety alert symbol with the word
“WARNING” or “CAUTION”.
These words mean:
Indicates a hazard which, if not avoided, can result in
severe personal injury or death and damage to product or other
property.
Indicates a hazard which, if not avoided, can result in
personal injury and damage to product or other property. All
safety messages will tell you how to reduce the chance of
injury, and tell you what will happen if the instructions are not
followed.
Indicates property damage can occur if instructions
are not followed.
Indicates property damage can occur if instructions
are not followed.
WARNING
CAUTION
NOTICE
DO NOT OPERATE EQUIPMENT DURING ACTIVE STAGES OF CONSTRUCTION
To ensure proper operation, Friedrich requires that all equipment is not operated during active construction phases. This includes active stages of
completing framing, drywalling, spackling, sanding, painting, flooring, and moulding in the equipment’s designated conditioning space. The use of
this equipment during construction could result in premature failure of the components and/or system and is in violation of our standard warranty
guidelines. The operation of newly installed equipment during construction will accelerate the commencement and/or termination of the warranty
period.
CAUTION

8 PB
INTRODUCTION
Personal Injury Or Death Hazards
SAFETY
FIRST
WARNING AVERTISSEMENT ADVERTENCIA
Do not remove, disable or
bypass this unit’s safety
devices. Doing so may cause
injuries, ordeath.
Ne pas supprime, désactiverou
contournercette l´unité des
dispositifs de sécurité, faire vous
risqueriez de provoquerle feu, les
blessures ou la mort. o muerte.
No eliminar, desactivaro pasar
poralto los dispositivos de
seguridad de la unidad. Si lo hace
podría producirse fuego, lesiones
ELECTRICAL HAZARDS:
• Shutdown and/or disconnect all electrical power to the unit before performing inspections, maintenance, or
service.
• Make sure to follow proper lockout/tag out procedures.
• Always work in the company of a qualied assistant if possible.
• Capacitors, even when disconnected from the electrical power source, retain an electrical charge potential
capable of causing electric shock or electrocution. Wait a few minutes after shutdown to allow the capacitors to
discharge the stored energy.
• Handle, discharge, and test capacitors according to safe, established, standards, and approved procedures.
• Extreme care, proper judgment, and safety procedures must be exercised if it becomes necessary to test or
troubleshoot equipment with the power turned on to the unit.
• Do not spray water on the air conditioning unit while the power is on.
• Electrical component malfunction caused by water could result in electric shock or other electrically unsafe
conditions when the power is restored and the unit is turned on, even after the exterior is dry.
• Use air conditioner on a single dedicated circuit within the specied amperage rating.
• Ensure the unit that the unit is properly grounded.
• Do not cut or modify the power supply cord or remove the ground prong of the plug.
• Never operate the unit on an extension cord.
• Follow all safety precautions and use approved protective safety equipment such as: gloves, goggles, and
clothing. Ensure that properly insulated tools, and testing equipment are are used as well to protect against
equipment damage and reduce the risk of injury.
• Failure to follow proper safety procedures and these warnings can result in serious injury or possibly death.

9 PB
INTRODUCTION
Model Identification Guide
Figure 101
M R 36 D Y 3 J M
Installation Type
M : Multi Zone
ledoM gnitekraM
Electrical rating
1 : 115V, 1Ø, 60Hz
zH06 ,Ø1 ,V032 : 3
Refrigeration Cycle
C : Cool Only
Y : Heat Pump
Application
Empty : Single
U : Universal
D : Dual Zone
T
: Tri-Zone
Q : Quad Zone
Capacity
9 : 9,000 BTU/h, 12 : 12,000 BTU/h,
18 : 18,000 BTU/h, 24 : 24000 BTU/h,
30 : 30,000 BTU/h, 36 : 36,000 BTU/h,
Model Type
W : Wall mounted
C : Cassette
D : Concealed Ducted
R : Outdoor component
WH : Wall mounted High SEER
RH : Outdoor high SEER
Series
Mini- split

10 PB
INTRODUCTION
Model Line Up
Figure 102 (Indoor Model Line Up)
Figure 103 (Outdoor Model Line Up)
Category Type Chassis
Model Name
Nominal Capacity, Btu/h(kW)
24,000 (7.03) 36,000 (10.5)
Ceiling
cassette 4way
TP
MC24Y3J
TM
MC36Y3J
Ceiling
Concealed
Duct
High
Static
BG
MD24Y3J
BR
MD36Y3J
Nominal
Capacity
Btu/h 24,000 36,000
kW 7.03 10.5
Model Names
MR24UY3J MR36UY3J
Power supply 208/230V, 1Ø, 60Hz
Chassis

11 PB
INTRODUCTION
Control systems (standard)
Figure 104
Type Individual controller Applicable model
Wireless remote
controller Ceiling cassette
Simple wired remote
controller
Ceiling Concealed Duct
(High Static)
TEMP
FAN
SPEED
OPER
MODE

12 PB
SPECIFICATIONS
Ceiling Cassette 4-way
Figure 201
Notes :
Model Name
MC24Y3J
1. Wiring cable size must comply with the applicable local and national code.
2. Due to our policy of innovation some specifications may be changed without notification.
3. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Acceptable operating voltage: 187V-253V
MC36Y3J
Power Supply V, Ø, Hz
Power Input W
Running Current A
Casing Color -
Dimensions Body W x H x D mm
W x H x D inch
Net Weight Body kg (lbs)
Heat
Exchanger
(Row x Column x Fins per
inch) x No. -
Face Area
Fan
m2(ft2)
Type -
Air Flow Rate H / M / L m3/min
H / M / L ft3/min
Fan Motor Type -
Output W x No.
Dehumidification Rate
l
/h (pts/h)
Sound Pressure Level H / M / L dB(A)
Sound Power Level dB(A)
Piping
Connections
Liquid mm(inch)
Gas mm(inch)
Drain (O.D. / I.D.) mm(inch)
Safety Devices -
-
Power and Communication Cable (included Earth) No. x mm 2(AWG)
Decoration Panel
Rated Voltage
-
Casing Color -
Dimensions W x H x D mm
W x H x D inch
Net weight kg (lbs)
208/230, 1, 60
60
0.60
-
840 × 204 × 840
20.5 (45.2)
33-1/16 x 8-1/32 x 33-1/16
(2 x 8 x 19) x 1
0.35 (3.77)
Turbo Fan
17.0 / 15.0 / 13.0
600 / 530 / 459
BLDC
60 x 1
2.4 (5.1)
38 / 36 / 34
57
Ø 9.52 (3/8)
Ø 15.88 (5/8)
Ø
32.0(1-1/4) / 25.0(1)
Fuse
Thermal Protector for Fan Motor
4 x 14ga (18)
600
Morning Fog
950 × 25 × 950
5.0 (11.0)
37-13/32 x 1 x 37-13/32
208/230, 1, 60
120
1.00
-
840 × 288 × 840
33-1/16 x 11-11/32 x 33-1/16
24.6 (54.2)
(2 x 12 x 21) x 1
0.53 (5.65)
Turbo Fan
30.0 / 28.0 / 26.0
1,060 / 989 / 918
BLDC
124 x 1
3.6 (7.7)
46 / 44 / 43
65
Ø 9.52 (3/8)
Ø 15.88 (5/8)
Ø 32.0(1-1/4) / 25.0(1)
Fuse
Thermal Protector for Fan Motor
4 x 14ga (18)
600
Morning Fog
950 × 25 × 950
37-13/32 x 1 x 37-13/32
5.0 (11.0)

13 PB
SPECIFICATIONS
Ceiling Concealed Duct (High Static)
Figure 202
Notes :
Model Name
[MD24Y3J]
1. Wiring cable size must comply with the applicable local and national code.
2. Due to our policy of innovation some specifications may be changed without notification.
3. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Acceptable operating voltage: 187V-253V
[MD36Y3J]
Power Supply
V, Ø, Hz
208/230, 1, 60 208/230, 1, 60
Power Input
W x No.
230 × 1 368 × 1
Running Current
A
1.00 1.60
Casing Color
-
- -
Dimensions Body W x H x D
mm
1,182 × 298 × 450 1,230 × 380 × 590
W x H x D
inch
46-17/32 x 11-23/32 x 17-23/32 48-7/16 x 14-31/32 x 23-7/32
Net Weight Body
kg (lbs)
33.0 (72.8) 56.5(124.6)
Heat
Exchanger
(Row x Column x Fins per inch) x No.
-
(3 x 12 x 21) x 1 (3 x 16 x 18) x 1
Face Area 0.26 (2.77)
m2(ft2)
0.36 (3.87)
Fan
Type
-
Sirocco Fan Sirocco Fan
Air
Flow
Rate
High-static
Mode
(Factory Set)
H / M / L
m3/min
19.5 / 17.5 / 15.0 32.0 / 27.0 / 20.0
H / M / L
ft3/min
688 / 618 / 530 1,130 / 953/ 706
External Static
Pressure
mmAq(in.Aq)
10(0.39) 10(0.39)
Fan Motor Type
-
BLDC BLDC
Output
W x No.
154 x 1 350 x 1
Dehumidification Rate l/ h (pts/h) 3.3 (7.0) 5.0 (10.6)
Sound Pressure Level H / M / L
dB(A)
38 / 36 / 35 39 / 38 / 37
Sound Power Level Cooling
dB(A)
56 56
Piping
Connections
Liquid
mm(inch)
Ø 9.52 (3/8) Ø 9.52 (3/8)
Gas
mm(inch)
Ø 15.88 (5/8) Ø 15.88 (5/8)
Drain (O.D. / I.D.)
mm
Ø 32.0(1-1/4) / 25.0(1) Ø 32.0(1-1/4) / 25.0(1)
Safety Devices
-
Fuse Fuse
-
- -
Power and Communication Cable (included Earth)
No. x mm
2
(AWG)
4x 14ga; 600V 4x 14ga; 600V

14 PB
SPECIFICATIONS
Outdoor Units DC Inverter SINGLE ZONE
Figure 203
Note :
1. Rated Capacity = Capacities are based on the following conditions:
- Cooling : Indoor temp: 80°FDB/67°FWB
Outdoor temp: 47°FDB/43°FWB
Outdoor temp: 95°FDB
- Heating : Indoor temp: 70°FDB
2. Due to our policy of innovation some specifications may be changed without notification.
- Piping Length : Interconnected Pipe Length = 25ft
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
Combination
Outdoor unit
MR24UY3J MR24UY3J
Indoor unit
MC24Y3J MD24Y3J
Capacity
Cooling
Min. ~ Rated ~ Max.
kW
2.84 ~ 7.03 ~ 7.81 2.84 ~ 7.03 ~ 7.81
Min. ~ Rated ~ Max.
Btu/h
9,700 ~ 24,000 ~ 26,700 9,700 ~ 24,000 ~ 26,700
Heating
Min. ~ Rated ~ Max.
kW
3.20 ~ 7.91 ~ 8.80 3.20 ~ 7.91 ~ 8.80
Min. ~ Rated ~ Max.
Btu/h
10,900 ~ 27,000 ~ 30,000 10,900 ~ 27,000 ~ 30,000
Power Input Cooling Rated kW
1.91 2.00
Heating Rated kW
2.60 2.28
EER
Btu/h·W
12.6 12.0
SEER / HSPF Btu/h·W
17.00 / 9.70 17.0 / 10.0
Combination
Outdoor unit
MR36UY3J
MR36UY3J
Indoor unit
MC36Y3J
MD36Y3J
Capacity
Cooling
Min. ~ Rated ~ Max.
kW
4.10 ~ 10.5 ~ 12.3
4.70 ~ 10.5 ~ 12.1
Min. ~ Rated ~ Max.
Btu/h
14,000 ~ 36,000 ~ 42,000
16,000 ~ 36,000 ~ 41,400
Heating
Min. ~ Rated ~ Max.
kW
4.25 ~ 11.7 ~ 13.1
5.20 ~ 11.7 ~ 13.4
Min. ~ Rated ~ Max.
Btu/h
14,500 ~ 40,000 ~ 45,000
17,500 ~ 40,000 ~ 48,000
Power Input Cooling Rated kW
2.97
2.91
Heating Rated kW
3.20
3.36
EER
Btu/h·W
13.5
12.10
SEER / HSPF Btu/h·W
19.00 / 9.50
17.60 / 9.20

15 PB
Figure 204
SPECIFICATIONS
Outdoor Units DC Inverter SINGLE ZONE
Note :
Model Name
MR24UY3J
1. Wiring cable size must comply with the applicable local and national code.
2. Due to our policy of innovation some specifications may be changed without notification.
3. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during opration.
4. For detailed electrical information, please refer to electric characteristics.
MR36UY3J
Power Supply V , Ø , Hz 208/230, 1, 60 208/230, 1, 60
Starting Current
Cooling Max. A - -
Heating Max. A - -
Wiring
Connections
Power Supply Cable
(included Earth)
3C x 2.5 (12)
No. x mm 2(AWG)
3C x 5.0 (10)
Casing Color - Warm Gray Warm Gray
Dimensions W x H x D mm 950 × 834 × 330
950 × 1,380 × 330
W x H x D inch
37-13/32 x 32-27/32 x 13
37-13/32 × 54-11/32 × 13
Net Weight kg (lbs) 60.0 (132.3)
92.0 (202.8)
Type
Compressor
- Twin Rotary Twin Rotary
Model Model x No. GJT240MAA x 1
GPT442MBA x 1
Motor type - BLDC
BLDC
Motor Output W x No. 2,137 x 1
4,000 x 1
Refrigerant
Type - R410A
R410A
Precharged Amount g (oz) 2,000 (70.5)
3,400 (119.9)
Chargeless-Pipe Length
m (ft) 7.6 (25.0)
7.6 (25.0)
Additional Charging Volume
g/m (oz/ft) 40 (0.43)
40 (0.43)
Control - Electronic Expansion Valve Electronic Expansion Valve
Refrigerant Oil Type - FVC68D FVC68D
Charged volume cc x No. 900 x 1 1,300 x 1
Heat Exchanger
(Row x Column x Fins per inch) x No.
- (2 x 38 x 14) x 1 (2 x 32 x 14) x 2
Fan Type - Propeller Propeller
Air Flow Rate 58(2,048) x 1
m3/min(ft
3/min) x No.
55(1,942) x 2
Fan Motor Type BLDC BLDC
Output W x No. 124.0 x 1 124.0 x 2
Sound Pressure
Level
Cooling Rated dB(A) 48 52
Heating Rated dB(A) 52 54
Sound Power Level
Rated dB(A) 62 67
Piping
Connections
Liquid Outer Dia. mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Gas Outer Dia. mm(inch) Ø 15.88 (5/8)
Piping Length
Ø 15.88 (5/8)
Max. m (ft) 50 (164.0) 75 (246.1)
Maximum Height
Difference
Outdoor Unit
~ Indoor Unit
Max. m (ft) 30 (98.4)
30 (98.4)
Operation Range
(Outdoor Temperature)
Cooling Min. ~ Max.
DB ( DB)
-15 (5.0) ~ 48 (118.4)
Heating
-15 (5.0) ~ 48 (118.4)
Min. ~ Max.
WB ( WB)
-18 (-0.4) ~ 18 (64.4) -18 (-0.4) ~ 18 (64.4)

16 PB
SPECIFICATIONS
Outdoor Units DC Inverter SINGLE ZONE
Operation Range
Cooling Heating
Outdoor Temp. [°F WB]
68 77
Indoor Temp. [°F DB]
Continuous
Operation
Warming up
Operation
50 59 81 86 91.3
77
-4
0
5
14
23
32
41
50
59
64
68
Indoor Temperature [°F WB]
-13
41 77 82.4
Outdoor Temperature [°F DB]
50 57 59 68
-4
5
14
23
32
41
50
59
68
77
86
95
104
113
118
122
Continuous
Operation
Figure 205

17 PB
SPECIFICATIONS
Outdoor Units DC Inverter SINGLE ZONE
Electric characteristics
- The power supply work is needed only to the outdoor unit. The power supply to the indoor unit is conducted through the
communication wiring. Therefore, the power supply work can be carried out at just one place of the outdoor unit. It will
simplify the work procedure and save cost.
- Wiring cable size must comply with the applicable local and national codes.
Earth
Circuit breaker
Power supply
Outdoor unit
External wiring procedure
Figure 206

18 PB
SPECIFICATIONS
Outdoor Units DC Inverter SINGLE ZONE
Electric characteristics
Notes :
(compressor or other motor)
- Load2 : sum of current for all other motors
- Load3 : any other load rated 1.0A or more
1. Voltage range
Voltage supplied to the unit terminals should be within the
minimum and maximum range
2. Maximum allowable voltage unbalance between phase is 2 %
3. MCA / MOP
MCA = (1.25 x Load1) + Load2 + Load3
MOP = (2.25 x Load1) + Load2 + Load3
- Load1 : Rated running current of largest motor
4. Select wire spec. based on the MCA
5. Recommended circuit breaker is ELCB (Earth Leakage circuit
breaker)
6. MSC & RLA are measured as the compressor only test
condition.
7. OFM is measured as the outdoor unit test condition
Unit Power
MCA : Minimum Circuit Amperes (A)
MOP : Maximum rating over current protective device
MSC : Maximum Starting Current
RLA : Rated Load Amperes (A)
OFM : Outdoor Fan Motor
kW : Fan Motor rated output (kW)
FLA : Full Load Amperes (A)
Compressor OFM
Model Phase Hz Voltage MCA MOP MSC RLA kW FLA
Cooling Heating
MR24UY3J
1Ø
60
Min.:187,
Max.:253
18.1 30 - 13.5 13.5 0.124 0.6
MR36UY3J
24.5 40 - 18.0 18.6
0.124 x 2
0.6 x 2
Figure 207

19 PB
SPECIFICATIONS
Product Dimensions
Ceiling Cassette 4-way 24k
Figure 208
TP Chassis
MC24Y3J

20 PB
SPECIFICATIONS
Product Dimensions
Ceiling Cassette 4-way 36k
Figure 209
TM Chassis
MC36Y3J
This manual suits for next models
6
Table of contents
Popular Temperature Controllers manuals by other brands

ThermoControl
ThermoControl HRT 6015-50 quick start guide

Watts Industries
Watts Industries CLIMATIC CONTROL-H Installation and user guide

Dynisco
Dynisco 1440 Installation and operation manual

Janam
Janam GT2 Series quick start guide

Vescent
Vescent SLICE-QTC manual

Precision Digital Corporation
Precision Digital Corporation SuperNova PD500 instruction manual