
FC Series w/ EDC Control
Thermal MNL-047-A
Division Rev. 004
FTS 7
Stone Ridge, NY USA
845.687.0071
INSTALLATION
Physical Location
The area where you place the unit should be smooth, level, and capable of safely supporting the weight of
the machine. Space should be provided so that air can properly circulate around the unit. If obstacles are
blocking the airflow, the compressor may overheat. This reduces performance, and can lead to early
compressor failure.
The environment should be well ventilated to prevent excessive build up of heat. Normal room ventilation
is usually adequate.
Electrical Requirements
Only qualified personnel should perform the installation of this unit.
The voltage and frequency requirements are specified on the serial tag on the rear of the unit. Standard
variances in frequency (+/-3Hz) and voltage (-5%, +10%) are allowed.
•Verify that the facilities voltage matches the requirement for the machine, which is printed on the
serial tag on the rear of the machine.
•The electric service wiring must be of a large enough wire gauge that the voltage is maintained to
the receptacle even when a full load is applied to the receptacle. Additionally, the receptacle
voltage should be measured while that receptacle is under load.
•Ensure the proper amperage circuit breaker is installed in the line and located near the equipment.
•Plug in the line cord. (Avoid the use of long extension cords, these cause a significant power drop
between the wall receptacle and the machine.) The MAINS lamp should light
NOTE: For Lock Out / Tag Out plug the appropriate device into the line cord.
Ambient Air Requirements
This unit is designed for operation in a normal indoor environment. (Systems should not be mounted
outside or otherwise exposed to the elements). The environment should be free from air containing large
amounts of moisture, salt or sulfur. If your system utilizes an air-cooled condenser, the fan in the system
draws ambient air across the condenser (radiator) to cool the refrigerant.
The ambient air temperature requirements are:
55°F to 69°F (12°C to 21°C) Acceptable
70°F to 75°F (21°C to 24°C) Ideal
75°F to 80°F (24°C to 27°C). Acceptable, but a reduction in the cooling capacity of the unit is to be
expected (about a 1% cooling capacity reduction per degree above
72°F).
80°F to 85°F (27°C to 29.5°C) Expect reduced reliability. Warranty may be voided.
Over 85°F (Over 29.5°C) Not Acceptable. Warranty will be voided.