Fuji Electric FRENIC-Lift WLM2A Series User manual

Instruction Manual
WLM2A series - Wall Mounted Solution
■Three-phase 400 V :FRN0010WLM2A-4E to FRN0032WLM2A-4E
Fuji Electric EuropeGmbH IM_WLM2A_EN_1.0.0
Thank you for purchasing our FRENIC-Lift WLM2A Wall Mounted solution series.
•
This product is designed to drive three-phase induction motors and three-phase permanent magnet
synchronous motors. Read through this manual to become familiar with the handling procedure and
correct use.
•
Improper handling might result in incorrect operation, short life cycle, or failure of this product as well as
the motor.
•
Deliver this manual to the end user of this product. Keep this manual in a safe place until this product
is discarded.
•
For instructions on how to use an optional device, refer to the instruction and installation manuals for
that optional device.

LM2A Wall Mounted Solution
Page 2of 20 Fuji Electric Europe GmbH
Version
Changes applied
Date
Written
Checked
Approved
1.0.0
First release
11.11.2020
C. Arjona
J. Alonso
J. Català
1.0.1
Small text corrections
xx.11.2020
C. Arjona

LM2A Wall Mounted Solution
Page 3of 20 Fuji Electric Europe GmbH
CONTENTS
0. Preface ...............................................................................................................................................................4
1. Before Use..........................................................................................................................................................8
1.1 Acceptance Inspection and Appearance of Product......................................................................................8
1.2 Usage and Storage environment...................................................................................................................9
2. Mounting and Wiring the Wall Mounted ..............................................................................................................9
2.1 Installing the cabinet......................................................................................................................................9
2.2 Circuit diagram............................................................................................................................................10
2.3 Wall Mounted diagrams...............................................................................................................................10
2.4 Wiring and terminals....................................................................................................................................13
2.4.1 Removing the front cover of the Wall Mounted......................................................................................13
2.4.2 Mounting the front cover........................................................................................................................13
2.4.3 Recommended wire sizes......................................................................................................................13
2.4.4 Terminal arrangement diagrams and screw specifications....................................................................14
2.4.5 Terminal functions .................................................................................................................................15
2.4.6 Inverter configuration.............................................................................................................................16
2.4.7 Mounting and connecting the keypad to the panel ................................................................................16
3. Operation Using the Keypad.............................................................................................................................16
4. Maintenance and Inspection.............................................................................................................................17
4.1 Daily Inspection...........................................................................................................................................17
4.2 Periodic Inspection......................................................................................................................................17
4.3 List of Replacement Parts...........................................................................................................................18
5. Dimensions.......................................................................................................................................................18
5.1 Frame 1.......................................................................................................................................................18
5.2 Frame 2.......................................................................................................................................................19
CONTACT INFORMATION....................................................................................................................................20

LM2A Wall Mounted Solution
Page 4of 20 Fuji Electric Europe GmbH
0. Preface
Thank you for purchasing our FRENIC-Lift WLM2A Wall Mounted solution series.
FRENIC-Lift WLM2A is a package including an inverter designed to drive a three-phase induction motor (hereafter
called induction motor) and a three-phase permanent magnet synchronous motor (hereafter called synchronous
motor) for exclusively controlling elevating machinery.
Improper handling might result in incorrect operation, a short life, or even a failure of this product as well as the
motor.
To drive a synchronous motor, a PG interface card option involving a pulse encoder is needed. For details, refer to
the instruction manual of PG Interface Card.
This instruction manual is the original instructions and provides only minimum requisite information for wiring and
operation of the product. Read through this manual before use.
For details about the inverter, refer to the FRENIC-Lift LM2A series Reference Manual thatcontains the precautions,
detailed functions, specifications and configuration.
Related documentation
FRENIC-Lift LM2A series Reference Manual
FRENIC-Lift LM2A series Instruction Manual
TP-A1-LM2 Installation Manual
TP-E1U Installation Manual
FRENIC-Lift LM2A series Starting Guide
These materials are subject to change without notice. Be sure to obtain the latest editions for use.
Safety precautions
Read this manual thoroughly before proceeding with installation, connections (wiring), operation, or maintenance
and inspection. Ensure you have sound knowledge of the device and familiarize yourself with all safety information
and precautions before proceeding to operate the inverter.
Safety precautions are classified into the following two categories in this manual.
Failure to heed the information indicated by this symbol may lead to dangerous
conditions, possibly resulting in death or serious bodily injuries.
Failure to heed the information indicated by this symbol may lead to dangerous
conditions, possibly resulting in minor or light bodily injuries and/or substantial
property damage.
Failure to heed the information contained under the CAUTION title can also result in serious consequences. These
safety precautions are of utmost importance and must be observed at all times.
Application
•FRENIC-Lift is equipment designed to drive induction motors and synchronous motors for exclusively
controlling elevating machinery. Do not use it for single-phase motors or for otherpurposes.
Fire or an accident could occur.
•This product may not be used for a life-support system or other purposes directly related to the human
safety.
•Although product is manufactured under strict quality control, install safety devices for applications where
serious accidents or property damages are foreseen in relation to the failure ofit.
An accident could occur.

LM2A Wall Mounted Solution
Page 5of 20 Fuji Electric Europe GmbH
Installation
Wiring
•If there isn’t zero-phase current (Earth leakage current) detective device, such as a ground-fault relay in
the upstream power supply line, which is to avoid undesirable system shutdown. Install a residual-
current-operated protective device (RCD)/earth leakage circuit breaker (ELCB) individually to break the
individual inverter’s power supply line.
Otherwise, a fire could occur.
•When wiring the inverter to the power source, insert a recommended molded case circuit breaker (MCCB)
or residual-current-operated protective device (RCD)/earth leakage circuit breaker (ELCB) (with
overcurrent protection) in the path of each pair of power lines to inverters. Use the recommended devices
within the recommended current capacity.
•Use wires in the specified size.
•Tighten terminals with specified torque.
Otherwise, a fire could occur.
•When there is more than one combination of an inverter and motor, do not use a multicore cable for the
purpose of running their wirings together.
•Do not connect a surge killer to the inverter's output (secondary) circuit.
Doing so could cause a fire.
•Be sure to ground the inverter's grounding terminals G.
Otherwise, an electric shock or a fire could occur.
•Qualified electricians should carry out wiring.
•Be sure to perform wiring after turning the power OFF.
Otherwise, an electric shock could occur.
•Be sure to perform wiring after installing the cabinet unit.
Otherwise, an electric shock or injuries could occur.
•Ensure that the number of input phases and the rated voltage of the product match the number of phases
and the voltage of the AC power supply to which the product is to be connected.
Otherwise, a fire or an accident could occur.
•Do not connect the power supply wires to the inverter output terminals (U, V, and W or U0, V0, and W0).
Doing so could cause fire or an accident.
•Do not place flammable object nearby.
Doing so could cause fire.
•Do not support the cabinet by its front cover during transportation.
Doing so could cause a drop of the inverter and injuries.
•Prevent lint, paper fibers, sawdust, dust, metallic chips, or other foreign materials from getting into the
cabinet, specially into the inverter or from accumulating on the heat sink.
•When changing the positions of the top and bottom mounting bases, use only the specified screws.
Otherwise, a fire or an accident might result.
•Do not install or operate an inverter that is damaged or lacking parts.
Doing so could cause fire, an accident or injuries.

LM2A Wall Mounted Solution
Page 6of 20 Fuji Electric Europe GmbH
•In general, sheaths of the control signal wires are not specifically designed to withstand a high voltage
(i.e., reinforced insulation is not applied). Therefore, if a control signal wire comes into direct contact with
a live conductor of the main circuit, the insulation of the sheath might break down, which would expose
the signal wire to a high voltage of the main circuit. Make sure that the control signal wires will not come
into contact with live conductors of the main circuit.
Doing so could cause an accident or an electric shock.
•Before changing the switches, turn OFF the power and wait at least 10 minutes. Make sure that the
charging lamp is turned OFF. Further, make sure, using a multimeter or a similar instrument, that the DC
link bus voltage between the terminals P(+) and N(-) has dropped to the safe level (+25 VDC or below).
Otherwise, an electric shock could occur.
•The inverter, motor and wiring generate electric noise. Be careful about malfunction of the nearby
sensors and devices. To prevent them from malfunctioning, implement noise control measures.
Otherwise an accident could occur.
•The leakage current of FRENIC-Lift is comparatively large for the EMC filter built-in type of inverters. Be
sure to perform protective grounding.
Otherwise, an accident or an electric shock could occur.
Operation
•Be sure to mount the front cover of the inverter before turning the power ON. Do not remove the cover
when the inverter power is ON.
Otherwise, an electric shock could occur.
•Do not operate switches with wet hands.
Doing so could cause electric shock.
•If the auto-reset function has been selected, the inverter may automatically restart and drive the motor
depending on the cause of tripping. Design the machinery or equipment so that human safety is ensured
at the time of restarting.
Otherwise, an accident could occur.
•If any of the protective functions have been activated, first remove the cause. Then, after checking that
all the run commands are set to OFF, release the alarm. If the alarm is released while any run commands
are set to ON, the inverter may supply the power to the motor, running the motor.
Otherwise, an accident could occur.
•If the user configures the function codes wrong without completely understanding this Instruction Manual
and the FRENIC-Lift LM2A series Reference Manual, the motor may rotate with a torque or at a speed
not permitted for the machine.
An accident or injuries could occur.
•Even if the inverter has interrupted power to the motor, if the voltage is applied to the main circuit input
terminals L1/R, L2/S and L3/T, voltage may be output to inverter output terminals U, V, and W.
•Even if the motor is stopped due to DC braking, voltage is output to inverter output terminals U, V, and
W.
An electric shock may occur.
•The inverter can easily accept high-speed operation. When changing the speed setting, carefully check
the specifications of motors or equipment beforehand.
Otherwise, injuries could occur.

LM2A Wall Mounted Solution
Page 7of 20 Fuji Electric Europe GmbH
•Do not touch the heat sink because it becomes very hot.
Doing so could cause burns.
•The DC brake function of the inverter does not provide any holding mechanism.
Injuries could occur.
•Ensure safety before modifying customizable logic related function code settings (U codes and related
function codes) or turning ON the "Cancel customizable logic" terminal command CLC. Depending upon
the settings, such modification or cancellation of the customizable logic may change the operation
sequence to cause a sudden motor start or an unexpected motor operation.
•If any abnormality is found in the inverter or motor, immediately stop it and perform troubleshooting,
referring to the FRENIC-Lift LM2A series Reference Manual.
An accident or injuries could occur.
Maintenance and inspection, and parts replacement
•Before proceeding to maintenance or inspection, turn OFF the power and wait at least 10 minutes. Make
sure that the charging lamp is turned OFF. Further, make sure, using a multimeter or a similar instrument,
that the DC link bus voltage between the terminals P(+) and N(-) has dropped to the safe level (+25 VDC
or below).
Otherwise, an electric shock could occur.
•Always carry out the daily and periodic inspections described in the this manual. Use of the inverter for
long periods of time without carrying out regular inspections could result in malfunction or damage, and
an accident or fire could occur.
•It is recommended that periodic inspections be carryout every one to two years, however, they should
be carried out more frequently depending on the usage conditions.
•It is recommended that parts for periodic replacement be replaced in accordance with the standard
replacement frequency indicated in the this manual. Use of the product for long periods of time without
replacement could result in malfunction or damage, and an accident or fire could occur.
•Contact outputs [30A/B/C] [Y5A/C] [Y4A/C] [Y3A/C] use relays, and may remain ON, OFF, or
undetermined when their lifetime is reached. In the interests of safety, equip the inverter with an external
protective function.
Fire or an accident could occur.
•Maintenance, inspection, and parts replacement should be made only by qualified persons.
•Take off the watches, rings and other metallic objects before starting work.
•Use insulated tools.
Otherwise, an electric shock or injuries could occur.
•Never modify the inverter or any other component of the cabinet. Never modify the internal cabinet wiring.
Doing so could cause an electric shock or injuries.
Disposal
•Treat the inverter as an industrial waste when disposing of it.
Otherwise injuries could occur.
GENERAL PRECAUTIONS
Drawings in this manual may be illustrated without covers or safety shields for explanation of detail parts.
Restore the covers and shields in the original state and observe the description in the manual before starting
operation.

LM2A Wall Mounted Solution
Page 8of 20 Fuji Electric Europe GmbH
Icons
The following icons are used throughout this manual.
This icon indicates information which, if not heeded, can result in the inverter not operating to full
efficiency, as well as information concerning incorrect operations and settings which can result in
accidents.
This icon indicates information that can prove handy when performing certain settings or operations.
This icon indicates a reference to more detailed information
1. BeforeUse
1.1 Acceptance Inspection and Appearance of Product
Unpack the package and check the following:
(1) An inverter with the ordered options and the following accessories are contained in the package.
(2) The inverter or any option have not been damaged during transportation—there should be no dents or parts
missing.
(3) The Wall Mounted solution options are that you ordered. All items inside the solution are shown as below.
(4) The inverter is the type you ordered. You can check the type and specifications on the main nameplate. (A
total of two nameplates and warning plates are attached to the inverter.)
Figure 1.1 Wall Mounted solution front view (without top cover)
Wall Mounted nameplate
Inverter
DC Reactor
Input contactor
Short circuit contactor
Main switch
Wall Mounted
nameplate

LM2A Wall Mounted Solution
Page 9of 20 Fuji Electric Europe GmbH
* Depending on Inverter ROM version and capacity. For additional information, check FRENIC-Lift LM2A series Starting Guide.
Figure 1.2 How to read Wall Mounted solution type name
If you suspect the product is not working properly or if you have any questions about your product, contact your Fuji
Electric representative.
1.2 Usage and Storage environment
For details of the usage environment and storage environment, refer to the FRENIC-Lift LM2A series Instruction
Manual.
2. MountingandWiringtheWallMounted
2.1 Installing the cabinet
(1) Mounting base
Make sure to install Wall Mounted solution in a surface able to support its load and
with non-flammable material. Do not mount the cabinet upside down or horizontally.
(2) Clearances
Ensure that the minimum clearances indicated in Figure 2.1 and Table 2.1 are
maintained at all times. By ensuring the clearance distances, a good ventilation
inside the cabinet is ensured. Bad ventilation can lead the temperature rise and the
malfunction of some components.
When mounting two or more cabinets
When mounting two or more cabinets in the same unit, basically lay them out side
by side. When mounting them one above the other, be sure to separate them with
a partition plate or the like so that any heat radiating from one cabinet will not affect
the one(s) above.
Table 2.1 Clearances mm (inch)
Inverter capacity
A
B
C
D *1
400V class series: FRN0010WLM2A-4E to
0
10
100
0
FRN0032WLM2A-4E
(0)
(0.39)
(3.9)
(0)
*1) D: Space required in front of the inverter unit
Figure 2.1 Mounting Direction and
Required Clearances

LM2A Wall Mounted Solution
Page 10 of 20 Fuji Electric Europe GmbH
2.2 Circuit diagram
This section shows the electrical diagram for the Wall Mounted solution. For this purpose, option S3 (main switch
and short-circuit contactor by default) is presented with the default wiring. On this section, only elements included
on the Wall Mounted solution will be drawn.
FRENIC-Lift (LM2)
DC Reactor
U V W
MOTOR
G
P2 N(-)DB P3 P(+)
GW0 V0 U0
L1/R L2/S L3/T
Input
-KIN
1/L1 3/L2 5/L3
2/T1 4/T2 6/T3
PLC
-KSC
R1
R2
R3
R4
14
13
-KSC
X4
11
12
-S1
Y3C Y3A
-KSC -KIN
1 2 3 4
-X1
220 VAC
Control
Terminals
Control
Terminals
A1 A1
A2A2
For details of inverter terminal definitions, refer to the FRENIC-Lift LM2A series Instruction Manual.
2.3 Wall Mounted diagrams
This section shows the main connection diagram for the Wall Mounted solution. In function of the Wall Mounted
version, different diagrams will be shown. For details of the electrical diagram, refer to section “2.2 Circuit diagram”
on this manual.
External components could be added to the diagram in order to clarify the concept. These external components are
not included into the Wall Mounted solution and noted in the diagram.
For details of the inverter connection diagram, refer to the FRENIC-Lift LM2A series Instruction Manual.

LM2A Wall Mounted Solution
Page 11 of 20 Fuji Electric Europe GmbH
FRN_ _ _ _WLM2A-4E –OPT-S3
FRENIC-Lift (LM2)
DC Reactor
(THR)
*10 (PLC)
U V W
MOTOR
EMC *8
G
PEN
P2 N(-)DB P3 P(+)
G
M
W0
V0
U0
(X4)
(SCCF)
*12
(Y3A)
(SCC)
(PLC)
*10
*1
*5
*4
*9
*9 *9 *9
Braking Resistor *6
L1/R L2/S L3/T
Input
KIN
KSC
Fuse *3
MCCB or
RCD/ELCB *2
Common
Terminals
[1] [2] [3] [4]
Main Switch
<220 VAC>
*7
(Y3C)
(SCC)
1/L1 3/L2 5/L3
2/T1 4/T2 6/T3
*11
*11
[1]
[KIN -A2-]
A2
A1
[4]
[2]
[KSC -A2-]
[KIN -A1-]
R1 R2
R3 R4
14 13
A1 A2
FRN_ _ _ _WLM2A-4E –OPT-S1
FRENIC-Lift (LM2)
DC Reactor
(THR)
*10 (PLC)
U V W
MOTOR
EMC *8
G
PEN
P2 N(-)DB P3 P(+)
G
M
W0
V0
U0
(X4)
(SCCF)
*12
(Y3A)
(SCC)
(PLC)
*10
*1
*5
*4
*9
*9 *9 *9
Braking Resistor *6
L1/R L2/S L3/T
Input
KSC
Fuse *3
MCCB or
RCD/ELCB *2
Common
Terminals
[1] [2] [3] [4]
<220 VAC>
*7
(Y3C)
(SCC)
*11
*11 [2]
[KSC -A2-]
R1 R2
R3 R4
14 13
A1 A2

LM2A Wall Mounted Solution
Page 12 of 20 Fuji Electric Europe GmbH
FRN_ _ _ _WLM2A-4E –OPT-N3
FRENIC-Lift (LM2)
DC Reactor
(THR)
*10 (PLC)
U V W
MOTOR
EMC *8
G
PEN
P2 N(-)DB P3 P(+)
G
M
W0
V0
U0
*1
*5
*4
*9
*9 *9 *9
Braking Resistor *6
L1/R L2/S L3/T
Input
KIN
Fuse *3
MCCB or
RCD/ELCB *2
Common
Terminals
[1] [2] [3] [4]
Main Switch
<220 VAC>
*7
1/L1 3/L2 5/L3
2/T1 4/T2 6/T3
[1] [KIN -A2-]
A2
A1
[4]
[KIN -A1-]
FRN_ _ _ _WLM2A-4E –OPT-N1
FRENIC-Lift (LM2)
DC Reactor
(THR)
*10 (PLC)
U V W
MOTOR
EMC *8
G
PEN
P2 N(-)DB P3 P(+)
G
M
W0
V0
U0
*1
*5
*4
*9
*9 *9 *9
Braking Resistor *6
L1/R L2/S L3/T
Input
Fuse *3
MCCB or
RCD/ELCB *2

LM2A Wall Mounted Solution
Page 13 of 20 Fuji Electric Europe GmbH
Note *1: All items inside this box are default or option elements of the Wall Mounted solution. Items located out
of this box are external and not included.
Note *2: Install a recommended molded case circuit breaker (MCCB) or residual-current-operated protective
device (RCD)/earth leakage circuit breaker (ELCB) (with over current protection function) in the primary
circuit of the inverter to protect wiring
Note *3: To bring the inverter into compliance with the European electrical safety standard IEC/EN 61800-5-1 or
compliance with Canadian and U.S. standards (CSA certification), be sure to insert the specified fuse
(see Instruction Manual) in the primary circuit of the inverter.
Note *4: In case of not installing the two MC between motor and inverter, please follow the procedure explained
in “AN-Lift2-0001 Use of FRENIC-Lift STO inputs in elevator applications”document.
Note *5: Use the metal plates placed on removable terminals to connect the shield by means of metal cable ties
for example.
Note *6: Braking resistor is optional.
Note *7: Connect an external power supply 230 VAC to terminals [1] and [2] of the common terminals for the
contactor coils.
Note *8: Jumper to connect/disconnect internal EMC filter. It is a metal plate placed on the EMC terminal.
Note *9: Removable terminals. For detailed information, refer to FRENIC-Lift LM2A series Instruction Manual,
section 2.2.4.
Note *10: Terminal configuration is set to SOURCE. Changing this configuration will make that the Wall Mounted
solution do not work properly.
Note *11: Wired to terminals (Y3A/C). It is mandatory to set the parameter E22 to value 123 (SCC function) for the
proper function of the Wall Mounted solution.
Note *12: Wired to the terminal (X4). It is mandatory to set the parameter E04 to value 115 (SCCF function) for the
proper function of the Wall Mounted solution.
2.4 Wiring and terminals
Follow the procedure below. In the following description, it is assumed that the Wall Mounted solution has already
been installed.
2.4.1 Removing the front cover of the Wall Mounted
[1]
Loosen up the screws of the Wall Mounted solution.
[2]
Hold the right and left ends of the top cover and remove it.
(It is possible to remove the ground connection from the cover to ease the procedure.)
Figure 2.2 Removing the Top Cover of the Wall Mounted Solution
2.4.2 Mounting the front cover
After wiring, place, wire the ground cable if it was removed and screw the top cover of the Wall Mounted solution.
2.4.3 Recommended wire sizes
Terminals for the main circuits should have insulation, insulation tubes, or similar treatment.

LM2A Wall Mounted Solution
Page 14 of 20 Fuji Electric Europe GmbH
Table 2.2 Recommended copper wire size
Power
supply
voltage
Nominal
applied
motor
(kW)
Inverter type
Recommended copper wire size (mm2)
[2/T1,
4/T2,
6/T3]*
Inverter’s
grounding
[
G]
Inverter
outputs
[U, V,W]
Inverter
outputs for
Short circuit
[U0,V0,W0]
DC reactor
connection
[P2, P3]
Block
terminals
Three-
phase
400 V
4.0
FRN0010WLM2A-4E
2.5
10
2.5
2.5
2.5
0.75
5.5
FRN0015WLM2A-4E
7.5
FRN0019WLM2A-4E
11
FRN0025WLM2A-4E
6
4
6
15
FRN0032WLM2A-4E
6
* Terminals for Wall Mounted solution option N3 or S3. In case of options N1 or S1, terminal are located in the inverter (L1/R, L2/S and
L3/T) with the same wire size detailed in the table.
For the recommended wire sizes for the main circuits of the inverter, refer to the FRENIC-Lift LM2A series
Instruction Manual.
2.4.4 Terminal arrangement diagrams and screw specifications
The tables and figures given below show the screw specifications and terminal arrangement. In case of the input
terminals, they will depend on the Wall Mounted solution option.
Block terminals
Input terminals
Output terminals
(2/T1, 4/T2, 6/T3)
(L1/R, L2/S, L3/T)

LM2A Wall Mounted Solution
Page 15 of 20 Fuji Electric Europe GmbH
Table 2.3 Terminal Characteristics
Terminal block
type
Screw
specifications
Recommended wire
size (mm2)
Type of screwdriver (tip shape)
Wire strip length
Block terminals
Screwless
0.5 to 2.5 mm2
(AWG20 to 14)
Flat screwdriver (0.5 mm x 3.0 mm)
6 mm
Input contactor
Screwless
1 to 10 mm2
(AWG18 to 8)
Flat screwdriver (0.5 mm x 3.0 mm)
10 mm
2.4.5 Terminal functions
The table below shows the main terminal functions. Differences between Wall Mounted versions are noted on each
description.
Table 2.4 Functions of Main Circuit Terminals
Classifi-
cation
Name
Symbol
Functions
Inverter
Primary grounding
terminals for inverter
enclosure
G
The two grounding terminals ( G) can be either used for the power supply
wiring (primary circuit) or motor wiring (secondary circuit). Be sure to
ground either of thetwo grounding terminals for safety and noise reduction.
Inverter output
terminals
U, V, W
Connect the three wires of the 3-phase motor to terminals U, V, and W,
taking care of the correct motor phase correspondence.
Inverter output for
Short circuit
U0, V0, W0
For a short circuit for PMS motor.
These outputs are connected internally to U, V, W.
DC reactor
connection terminals
P2, P3
Terminals for built-in DC Reactor connection. Do not unwire them. If for
any reason DCR is removed, make a bridge between these terminals.
Main circuit power
input terminals
L1/R, L2/S,
L3/T
The three-phase input power lines are connected to these terminals.
Only for options “S1” and “N1”.
WM
terminals
Input contactor
1/L1, 3/L2,
5/L3
Wired from factory to main circuit power input terminals on the inverter
(L1/R, L2/S, L3/T). Do not remove the factory wiring.
2/T1, 4/T2,
6/T3
The three-phase input power lines are connected to these terminals.
Only for options “S3” and “N3”.
Block terminals
[1], [2]
Input power supply for contactors coils, 230 VAC.
Do not remove the factory wiring.
[3], [4]
Do not remove the factory wiring.
Do not remove the jumper between terminals 2 and 3.
Wiring notes
To make the machinery or equipment compliant with the EMC standards, wire the motor and inverter in accordance
with the following.
Use shielded wires for the motor cable and route the cable as short as possible. Firmly clamp the shield to the
grounded metal plate.
Figure 2.3 Connection method with shield plate of input and output terminals
Tight wire

LM2A Wall Mounted Solution
Page 16 of 20 Fuji Electric Europe GmbH
In case of Wall Mounted solution options N1 or S1, route the cable for power supply as the black cable that it is
shown below. Proper cable route is the same for both Wall Mounted sizes.
Figure 2.4. Power supply wiring route for options N1 and S1.
For details about dimensions and frames of Wall Mounted, refer to Chapter 5 of this Instruction Manual.
For details about wiring the inverter, refer to the FRENIC-Lift LM2A series Instruction Manual.
2.4.6 Inverter configuration
It is required to set up the inverter with the proper configuration in order to enter the Wall Mounted solution into the
desired functionality. Check before to start any operation that the inverter has been set with the configuration
explained in Table 2.5. This set up is mandatory for the indicated options of the Wall Mounted solution.
Table 2.5. Inverter configuration.
Classification
Name
Configuration
WM Version
Hardware
Switch
SW1
Position: SOURCE
OPT-S1
OPT-S3
Software
Parameter
E04
Value: 115
E22
Value: 123
For detailed information about these functions, refer to the FRENIC-Lift LM2A series Reference Manual.
2.4.7 Mounting and connecting the keypad to the panel
You can remove the keypad cover from the inverter unit and to mount keypad (option) on the panel or install it at a
remote site. (e.g., for operation on hand).
For detailed instructions on how to mount the keypad on the panel, refer to the TP-A1-LM2 installation manual
or TP-E1U installation manual.
3. OperationUsingtheKeypad
The FRENIC-Lift has no keypad by default. Using the optional keypad allows you to start and stop the motor,
monitor running status, and switch to the menu mode. You may also set the function code data, monitor I/O signal
states, maintenance information, and alarm information.
For details of the keypad use, refer to the FRENIC-Lift LM2A series Reference Manual and Starting Guide.
For differences between keypads, refer to TP-A1-LM2 installation manual and TP-E1U installation manual.

LM2A Wall Mounted Solution
Page 17 of 20 Fuji Electric Europe GmbH
4. Maintenance andInspection
Perform daily and periodic inspections to avoid trouble and keep reliable operation of the inverter and components
for a long time.
4.1 Daily Inspection
Visually inspect the inverter and other components for operation errors from the outside without removing the covers
when the inverter is ON or operating.
- Check that the expected performance (satisfying the standard specifications) isobtained.
- Check that the surrounding environment satisfies the environmental requirements given in Chapter 2, Section
2.1.
- Check that the keypad displays normally.
- Check for abnormal noise, odor, or excessive vibration.
- Check for traces of overheat, discoloration and other defects.
4.2 Periodic Inspection
Before starting periodic inspections, be sure to stop the motor, shut down the power, and wait at least 10 minutes.
Make sure that the charging lamp on the inverter is turned OFF. Further, make sure, using a multimeter or a similar
instrument, that the DC link bus voltage between the main circuit terminals P(+) and N(-) has dropped to the safe
level (+25 VDC or below).
For the complete list of inverter periodic inspection, refer to the FRENIC-Lift LM2A series Instruction Manual.
Table 4.1 List of Periodic Inspections
Check part
Check item
How to inspect
Evaluation criteria
Environment
1)
Check the ambient temperature, humidity,
vibration and atmosphere (dust, gas, oil mist, or
waterdrops).
2)
Check that tools or other foreign materials or
dangerous objects are not left around the
equipment.
1)
Check visually or
measure using apparatus.
2)
Visual inspection
1)
The standard
specifications must be
satisfied.
2)
No foreign or
dangerous objects
are left.
Input voltage
Check that the input voltages of the main and
control circuit are correct.
Measure the input voltages
using a multimeter or the like.
The standard
specifications must be
satisfied.
Structure such
as frame and
cover
Check for:
1)
Abnormal noise or excessive vibration
2)
Loose bolts (at clamp sections).
3)
Deformation and breakage
4)
Discoloration caused by overheat
5)
Contamination and accumulation of dust or
dirt
1)
Visual or auditory
inspection
2)
Retighten.
3), 4), 5)
Visual inspection
1), 2), 3), 4), 5)
No abnormalities
Main circuit
Common
1)
Check that bolts and screws are tight and
not missing.
2)
Check the devices and insulators for
deformation, cracks, breakage and
discoloration caused by overheat or
deterioration.
3)
Check for contamination or accumulation of
dust ordirt.
1) Retighten.
2), 3)
Visual inspection
1), 2), 3)
No abnormalities
Conductors
and wires
1)
Check conductors for discoloration and
distortion caused by overheat.
2)
Check the sheath of the wires for cracks and
discoloration.
1), 2)
Visual inspection
1), 2) No abnormalities
Terminal
blocks
Check that the terminal blocks are not
damaged.
Visual inspection
No abnormalities
Reactor
Check for abnormal roaring noise and odor.
Auditory, visual, and
olfactory inspection
No abnormalities
Magnetic
contactors
1)
Check for chatters during operation or
vibrations.
2)
Check that contact surface is not rough.
1)
Auditory inspection
2)
Visual inspection
1), 2) No abnormalities
Main switch
1)
Check that it is not damaged.
2)
Check that it can change the position.
1), 2) Visual or auditory
inspection
1), 2) No abnormalities
Cooling
system
Check the heat sink, intake and exhaust ports
for clogging and foreign materials.
Visual inspection
No abnormalities
Remove dust accumulating on the inverter and other components with a vacuum cleaner. If a component is stained,
wipe it off with a chemically neutral cloth.

LM2A Wall Mounted Solution
Page 18 of 20 Fuji Electric Europe GmbH
4.3 List of Replacement Parts
In case that a replacement of one of the components of the Wall Mounted solution were needed, refer to Table 4.2
to check the name of the item. Replacement parts of the inverter are listed on the FRENIC-Lift LM2A series
Instruction Manual. When the inverter or DC Reactor replacement is necessary, consult your Fuji Electric
representative.
Table 4.2 Replacement Parts
Nominal
applied
motor (kW)
Inverter type
Part name
Main Switch
(S1)
Input Contactor
(KIN)
Short-circuit
Contactor (KSC)
DC Reactor
4.0
FRN0010WLM2A-4E
EATON
(M22-WKV)
(M22-A)
(M22-CK10)
(M22S-ST-X)
Siemens
(3RT2026-2AP00)
Siemens
(3RT2526-2AP00)
DCRE4-4.0-J
5.5
FRN0015WLM2A-4E
DCRE4-5.5-J
7.5
FRN0019WLM2A-4E
DCRE4-7.5-J
11
FRN0025WLM2A-4E
DCRE4-11-J
15
FRN0032WLM2A-4E
Siemens
(3RT2027-2AP00)
Siemens
(3RT2535-2AP00)
DCRE4-15-J
5. Dimensions
5.1 Frame 1
Power supply voltage
Inverter type
Three-phase 400V
FRN0010WLM2A-4E
FRN0015WLM2A-4E
FRN0019WLM2A-4E

LM2A Wall Mounted Solution
Page 19 of 20 Fuji Electric Europe GmbH
5.2 Frame 2
Power supply voltage
Inverter type
Three-phase 400V
FRN0025WLM2A-4E
FRN0032WLM2A-4E

CONTACT INFORMATION
Fuji Electric Europe Headquarters
Fuji Electric Europe GmbH
Goethering 58
63067 Offenbach am Main
Germany
Tel.: +49 69 669029 0
Fax: +49 69 669029 59
www.fujielectric-europe.com
Switzerland
Fuji Electric Europe GmbH, Swiss Branch
Rietlistrasse 5
9403 Goldach
Tel.: +41 (0) 71 858 29 49
Fax: +41 (0) 71 858 29 40
www.fujielectric-europe.com
France
Fuji Electric Europe GmbH, Succursale France
265 Rue Denis Papin
38090 Villefontaine
Tel.: +33 4 74 90 91 24
Fax: +33 4 74 90 91 75
www.fujielectric-europe.com
United Kingdom
Fuji Electric Europe GmbH, UK Branch
Bedford i-Lab
Stannard Way
Priory Business Park
Bedford MK44 3RZ
Tel.: +44 (0) 1234 834 768
www.fujielectric-europe.com
Spain
Fuji Electric Europe GmbH, Sucursal en España
Carrer dels paletes 8, Edifici B, Planta 1, Oficina B
Parc Tecnològic del Vallès
08290 Cerdanyola del Vallès (Barcelona)
Tel.: +34 935 824 333
Fax: +34 935 824 344
www.fujielectric-europe.com
Italy
Fuji Electric Europe GmbH, Filiale Italiana
Via Rizzotto 46
41126 Modena (MO)
Tel.: +39 059 4734 266
Fax: +39 059 4734 294
www.fujielectric-europe.com
Subject to change without prior notice
This manual suits for next models
5
Table of contents