Specification of Power Distribution Units
Copyright 2012 FUJITSU COMPONENT LIMITED
June. 12, 2012
Main specification for Plugs with cable Saf-D-Grid plug
Round crimp connector
No connector
10A-400V DC Power distribution units and plugs
3-5, Higashi-gotanda 2-chome, Shinagawa-ku, Tokyo, 141-0022 Japan
TEL (81-3)5449-7014 FAX (81-3)5449-2626
URL http://www.fcl.fujitsu.com/en/
zSpecifications are subject to change without notice.
For the latest information, contact your local representative.
zYou may have to comply with related state regulations or related export
rules.
zCompany names and product names mentioned in this leaflet are
trademarks or registered trademarks of their respective owners.
GLOBAL MARKETING DEPT. 2 MARKETING DIV.
Outer dimensions (5 outlets type)
Outlet bar
Outlet box
380
44.4
67
44.4
440
465
31.75
134
482
Note) The dimensions are for reference. (unit:mm)
Side view
Side view
Top view
Top view
Product name Outlet bar Outlet box
5 outlets FDU-X105
10 outlets
per outlet
per unit
5 outlets
10 outlets
FDU-X110
380 x 44.4 x 67 mm 482 x 44.4 x 134 mm
482 x 88.5 x 160 mm
FDU-A105
FDU-A110
5 outlets / 10 outlets
First make last break
10A-400VDC 4kW
25A-400VDC 10kW
400VDC +7.5% -30%、10kW (at resistive load)
Min 5MΩ(1kVDC、b/w DC power lines - ground pin)
2500VDC for 1min.
(b/w DC power lines - ground pin, b/w DC lines)
Max. 300A
5000 cycles
5000 operations
500 operations
600 x 44.4 x 67 mm
Part number
No of outlets
Configulation
Rated
power
Rated power
Insulation resistance
Dielectric
strength
Socket
-outlet
Input
Insulation
Inrush current
Insertion/withdrawal life
Rated power
Electrical life
(Switch) Inrush (300A)
Dimensions
(W x D x H)
PSE 2.0sq cableCable
5000 cycles
Insertion/withdrawal life
2500VDCfor 1min. (b/w adjacent contacts)
Dielectric strength
Min. 5MΩ(at 500VDC, b/w adjacent contacts)
Insulation resistance
Insulation
260VDC to 420VDC / 10A
Rated voltage/current
FDU-P130FDU-P120FDU-P115
No connector
FDU-P130/CTFDU-P120/CTFDU-P115/CT
Round crimp connector
FDU-P130/APFDU-P120/APFDU-P115/AP
Saf-D-Grid plug(*)
Terminal
treatment
Part
number
3.0m2.0m1.5m
Cable length (approx.)
Plug with cableProduct name
Specification of Plug with Cable
* Saf-D-Grid plug is the product of Anderson Power Products, Inc.
Types of plug with cable