Allows a defrost to start when the controller is powered. For example, when the power supply
returns (in the case of a power shortage)
Time required for dripping, i.e. to drain the last drops of the evaporator. During this period, all
outputs remain switched off. If you do not want this stage, adjust this time to [no,,].
T h e f a n o p e r a t i o n s e t t i n g s i n n o r m a l a n d p o w e r - s a v i n g m o d e a r e :
[Auto] Automatic : The fan will be permanently switched on while the compressor is activated.
When the compressor is off, the fan will cycle according to the time set in [,F48] and
[,F49].
[Cont] Continuous : The fan will be constantly activated.
[Dept] Dependent : The fan will be activated together with the compressor.
Locked temperature indication during defrost
Defrost when powering the controller
Draning time
Fan operation mode : Normal Mode
Fan operation mode : Power-Saving Mode
This function is intended to prevent an increase in room temperature, due to the defrosting
process being displayed. During the defrosting process, the last measured temperature in the
refrigeration cycle will be frozen on the display. The indication will be unfrozen when the
temperature before defrost is reached or when the time set using this function is exceeded, after
the start of the next refrigeration cycle (whichever comes first). If set to the value [,,,0], the
temperature display will only be frozen at the defrost stage. This function can be disabled if set to
[no,,].
[,F49]
[,F50]
[,F51]
[,F52]
[,F53]
This is the amount of time the fan will remain OFF if [,F46]and[,F47]are configured as
automatic, while the compressor is off.
The fan can be set to remain activated or deactivated during the period when the door is kept
open.
The purpose of this function is to stop the evaporator fan until the room temperature approaches
that listed in the project, thus preventing a high temperature and suction pressure which can
damage the compressor. If the evaporator temperature surpasses that of the value, the faz is
turned off, turning back on with a set hysteresis of 2°C/4°F. It is a valuable resource when, for
example, cooling equipment has been inactive for a few days or when freezer rooms or
refrigerated counters are refilled with stock.
After drainage, the fan’s delay cycle is enabled. The compressor is immediately turned on
because the evaporator temperature is high, but the fan is only enabled after the evaporator
temperature decrease to the set programmed value. This process is required to remove residual
heat (caused by the defrosting process) in the evaporator, preventing room temperature to rise.
For safety, in case the evaporator temperature does not reach the value in [,F52] or the
sensor S2 is disconnected, fan reactivation will occur after the function’s set time.
F a n O F F T i m e i f [ , F 4 6 ] and[ , F 4 7 ]
are in automatic mode ([Auto])
Fan operation when opening the door
Fan deactivation by high temperature in evaporator
Evaporator temperature for fan reactivation after
draining
Maximum fan reactivation time after draining (fan-
delay)
[,F48] This is the amount of time the fan will remain ON if [,F46]and[,F47]are configured as
automatic, while the compressor is off.
Fan ON Time if [,F46]and[,F47] are in automatic
mode ([Auto])
[,f35]
[,f36]
[,f37]
[,f38]
[,f39]
[,f40]
[,f41]
If the room temperature ( sensor S1) reaches the set value, the defrosting process will end,
avoiding an eventual unwanted rising of product temperature.
If the controller is configured to carry out the defrost based on temperature, this time works as a
safeguard in situations where the evaporator temperature (sensor S2) does not reach the
programmed values in [,f27],[,f28],[,f29]. This function determines the maximum
time that the controller will wait for without carrying out the defrost.
This function is used to set the maximum time for a defrost. If, within such period, defrosting is
not terminated by temperature, a dot will start blinking on the bottom-right corner of the display (it
needs to be enabled in [,f74]), indicating that the defrosting process has been terminated by
the time limit rather than by temperature. This may happen if the temperature set is too high, the
time limit is too short, or the sensor S2 is disconnected or not connected to the evaporator.
Room temperature to end the defrost (r1)
Room temperature to end the defrost (r2)
Room temperature to end the defrost (r3)
Maximum time without defrosts if [,f23] = [,,,1]
Maximum defrost time (for safety) (r1)
Maximum defrost time (for safety) (r2)
Maximum defrost time (for safety) (r3)
[,f30]
[,f31]
[,f32]
[,f33]
[,f34]
When the evaporator temperature (sensor S2) drops and reaches the value set in
[,f27],[,f28],[,f29], the countdown to start the pre-defrost begins. During this stage, if
the temperature remains low, the pre-defrost starts. Otherwise, if this temperature rises above
the set value, the system returns to the refrigeration stage.
When starting the defrosting process, the controller will only activate the fan to take advantage
of the gas residual energy.
If the temperature on the evaporator (sensor S2) reaches the set valuem the defrosting process
will end as usual, i.e. by temperature. This, it optimizes the defrosting process.
Confirmation time of low temperature (sensor S2) to
start the pre-defrost if [,f23] = [,,,1]
Pre-defrost Time (gas collecting)
Evap. temp. (sensor S2) to finalize the defrost (r1)
Evap. temp. (sensor S2) to finalize the defrost (r2)
Evap. temp. (sensor S2) to finalize the defrost (r3)
[,f27]
[,f28]
[,f29]
When the evaporator temperature ( sensor S2) reaches the value configured by this function,
the controller will initiate the countdown to defrost.
Evap. temp. to start defrost if [,f23] = [,,,1] (r1)
Evap. temp. to start defrost if [,f23] = [,,,1] (r2)
Evap. temp. to start defrost if [,f23] = [,,,1] (r3)
[,f24]
[,f25]
[,f26]
Determines how often defrost will be performed, which is the time counted from the end of the
previous defrost.
[,,,0]= Electrical defrost (by resistance), where only the defrost output is activated..
[,,,1]= Hot gas defrost, whereby the compressor and defrost output are activated..
[,,,2]= Natural defrost, where only the fan output is activated.
[,f22]
[,f23] [,,,0]= Defrost started by time;
[,,,1]= Defrost started by temperature.
Defrost type
Condition to start the defrost
Interval between defrosts if [,f23] = [,,,0](r1)
Interval between defrosts if [,f23] = [,,,0](r2)
Interval between defrosts if [,f23] = [,,,0](r3)
[,f45] Enable second defrost output
With this function activated, you can make the output FAN operate as a second defrost output.
This output is activated during the execution of the pre-defrost and drainage.
Note: With F45 = ON, the functions related to fan control are disregarded.
[no,,] 999 min.
[Off,] [On,,] -
[no,,] 999 min.
[Auto] [Dept] -
1999 min.
[Off,] [On,,] -
-50 (-58) 75.0 (167) ºC (°F)
-50 (-58) 75.0 (167) ºC (°F)
[no,,] 999 min.
1999 min.
-50 (-58) 75.0 (167) ºC (°F)
1999 H
1999 min.
-50 (-58) 75.0 (167) ºC (°F)
[no,,] 999 min.
[no,,] 999 min.
-50 (-58) 75.0 (167) ºC (°F)
1999 H
02-
01-
[Off,] [On,,] -
15
[On,,]
1
[Dept]
999
[Off,]
75.0 (167)
2.0 (36)
1
1
20.0 (68)
12
30
-5.0 (23)
10
[no,,]
40.0 (104)
12
0
0
[Off,]
CELSIUS (FAHRENHEIT)
FUN MÍN MÁX UNIT. DEFAULT
DESCRIPTION
FUNCTION