THEE OUTPUT DIGITAL CONTROLLER
WITH ALARM, CYCLICAL TIMER AND
SERIAL COMMUNICATION
Ver. 03
MT-543Ri plus
UL-Underwriters Laboratories
1.DESCRIPTION
2.APPLICATION
3.TECHNICALSPECIFICATIONS
MT-543Ri plus has three outputs of temperature control and a internal buzzer. Because of its
versatility, it permits that the second stage works as alarm and the third, besides to work as cyclical
timer,itcanworkwiththefirststageinsystemsthatneedminimumventilation.Throughtheserialoutput
RS-485,itpermitscommunicationwithSITRAD software.
ProductcomplieswithCE(EuropeanUnion)andULInc.(UnitedStatesandCanada)..
•Bloodbanks
•Multistagetemperaturesystem
•Airconditioning
•Datacenters
MT-543Riplus-115/230Vac±10%(50/60Hz)
MT-543RiLplus-12/24Vac/dc
NTC:-50to105ºC(±0.1ºC)
PT-100:-99to300ºC(±1ºC)
-PowerSupply:
-ControlTemperature:
®
-Dimensions:
-Operatingtemperature:
-Operatinghumidity:
-LoadCurrent:
CLASSIFICATIONACCORDINGTOIEC60730-2-9STANDARD:
-Temperaturelimitoftheinstallationsurface:
-Typeofconstruction:
-Automaticaction:
-Controlofpollution:
-Impulsevoltage:
-Temperatureforthetestofspherepressure:
-Insulation:
71x28x71mm
0to50ºC
10to90%RH(withoutcondensation)
5(3)A/250Vac1/8HPeachoutput
50°C
Built-inelectroniccontroller
Type1
Level2
1,5kV 75°Cand125°C
ClassII
4.PARAMETERSTABLE
Description Min Max Unit
NTC PT-100
Min Max Unit
Fun
F01
F02
F03
F04
F05
F06
F07
F08
F09
F10
F11
F12
F13
F14
-
-5.0
0
-50
-50
0.1
1
0
-50
-50
0.1
1
1
1
-
5.0
1
105
105
20.0
999
4
105
105
20.0
999
999
999
-
°C
-
°C
°C
°C
sec.
-
ºC
ºC
ºC
sec.
min.
sec.
-
-5
0
-99
-99
1
1
0
-99
-99
1
1
1
1
-
5
1
300
300
40
999
4
300
300
40
999
999
999
-
°C
-
°C
°C
°C
sec.
-
ºC
ºC
ºC
sec.
min.
sec.
Access code:123(one hundred and twenty-three)
Offset indication
Operation mode of first stage
Minimum setpoint allowed to the end user (first stage)
Maximum setpoint allowed to the end user (first stage)
Control differential (hysteresis) of first stage
Minimum delay to turn on the first stage output
Operation mode of second stage
Minimum setpoint allowed to the end user (second stage)
Maximum setpoint allowed to the end user (second stage)
Control differential(hysteresis) of second stage
Minimum delay to turn on the second stage output
Delay to enable the alarm when the instrument is powered on
Alarm Time (on cycle)
1
0
-50
-50
0.1
1
0
1
1
1
0
0
-50
-50
1
1
1
1
999
2
105
105
20.0
999
1
999
999
999
4
2
105
105
999
999
999
247
sec.
-
ºC
ºC
ºC
seg.
-
sec.
-
-
-
-
ºC
ºC
sec.
sec.
min.
-
1
0
-99
-99
1
1
0
1
1
1
0
0
-99
-99
1
1
1
1
999
2
300
300
40
999
1
999
999
999
4
2
300
300
999
999
999
247
sec.
-
ºC
ºC
ºC
sec.
-
sec.
-
-
-
-
ºC
ºC
sec.
sec.
min.
-
Alarm Time (off cycle)
Operation mode of third stage
Minimum setpoint allowed to the end user (third stage)
Maximum setpoint allowed to the end user (third stage)
Control differential (hysteresis) of third stage
Minimum delay to turn on the third stage
Time base of third stage cyclical timer
Activation time for third stage cyclical timer
Cyclical timer on third stage- time on
Cyclical timer on third stage- time off
Operation mode of cyclical timer
Operation mode of Buzzer
Acting point of Buzzer (inferior limit)
Acting point of Buzzer (superior limit)
Buzzer time on
Buzzer time off
Inhibition time of Buzzer during electrical supply
Network equipment address RS - 485
F15
F16
F17
F18
F19
F20
F21
F22
F23
F24
F25
F26
F27
F28
F29
F30
F31
F32
OBS: To inhibit the alarms OUT2 and BUZZ press simultaneously and .
SET
F01-Accesscode:123(onehundredandtwenty-three)
F02-Offsetindication
F03-Operationmodeoffirststage
F04-Minimumsetpointallowedtotheenduser(firststage)
F05-Máximumsetpointallowedtotheenduser(firststage)
F06-Controldifferential(hysteresis)offirststage
Tochangetheparametersisnecessaryusetheaccesscode.Itisnotnecessarytousetheaccesscode
tovisualizetheadjustedparameters.
Itallowstocompensateeventualshuntinglinesinthereadingofambienttemperatureproceedingfrom
theexchangeofthesensororcablelenghtalteration.
0-Refrigeration
1-Heating
Electroniclimitswhosepurposeispreventthattoohighortoolowsetpointtemperaturesareregulated.
Itisthedifferenceoftemperature(hysteresis)betweenturnONandturnOFFtheOUT1output.
F07-Minimumdelaytoturnonthefirststageoutput
F08-Operationmodeofsecondstage
F09-Minimumsetpointallowedtotheenduser(secondstage)
F10-Maximumsetpointallowedtotheenduser(secondstage)
F11-Controldifferential(hysteresis)ofsecondstage
ItistheminimumtimethatOUT1willkeepturnedoff,itmeans,spaceoftimebetweenthelaststopand
thenextstart.
0-Refrigeration
1-Heating
2-Intra-rangealarm
3-Extra-rangealarm
4-Relativeextra-rangealarm
Electroniclimitswhosepurposeispreventthattoohighortoolowsetpointtemperaturesareregulated.
Whenthesecondstage(F08)isdefinedasalarm,theactingpointsaredefinedinF09andF10.
Itisthedifferenceoftemperature(hysteresis)betweenturnONandturnOFFtheoutputOUT2.
F12-Minimumdelaytoturnonthesecondstageoutput
F13-Delaytoenablethealarmwhentheinstrumentispoweredon
F14-Alarmtime(oncycle)
F15-Alarmtime(offcycle)
F16-Operationmodeofthirdstage
ItistheminimumtimethattheoutputOUT2willkeepturnedoff,itmeans,thespaceoftimebetweenthe
laststopantthenextstart.
During this time the alarm is kept turned off waiting that the system reaches the working control
temperature.
It allows to adust the time that OUT2 output will keep turned on. This function acts only with F8
configuratedasalarm.
It allows to adust the time that OUT2 output will keep turned off.This function acts only with F8
configuratedasalarm.Tokeepthealarmalwaysactivatedjustset“0”inthisfunction.
0-Refrigeration
1-Heating
2-CyclicalTimer
F17-Minimumsetpointallowedtotheenduser(thirdstage)
F18-Maximumsetpointallowedtotheenduser(thirdstage)
F19-Controldifferential(hysteresis)ofthirdstage
F20-Minimumdelaytoturnonthethirdstage
F21-Timebaseofthirdstagecyclicaltimer
F22-Activationtimeofthirdstagecyclicaltimer
Electroniclimitswhosepurposeispreventthattoohighortoolowsetpointtemperaturesareregulated.
Itisthedifferencetemperature(hysteresis)betweenturnONandturnOFFtheoutputOUT3.
ItistheminimumtimethattheoutputOUT3willkeepturnedoff,itmeans,thespaceoftimebetweenthe
laststopandthenextstart.
0-seconds
1-minutes
ThisfunctiondependsofF25.Everytimethatthetemperaturereachtheconfiguredvaluein ,the
configuredtimeinthisfunctionisrespected,tobeactivatedthecyclicaltimerafter.Toactivatethetimer
when isreachedjustset“0”inthisfunction.
MT543V03-03T-10772