Fumex FA1 Series User manual

FA1 Series
Air Filtration System
Operations Manual
READ AND SAVE THESE INSTRUCTIONS
WARNING:
Disconnect from power supply before performing maintenance procedures
such as cabinet cleaning, changing filters or servicing of electric motor or
other electric components
WARNING:
To reduce the risk of fire or electric shock, do not use this fan with any
solid-state speed control device.
WARNING:
For general ventilating use only. Do not use to exhaust hazardous or
explosive materials or vapors.
CAUTION:
Do not operate without having all filters in place.
Do not operate any fan with a damaged cord or plug. Discard fan or return
to an authorized service facility for examination and/or repair.
Do not run cord under carpeting. Do not cover cord with throw rugs,
runners or similar coverings. Arrange cord away from traffic area and
where it will not be tripped over.

2
GETTING STARTED
I n i t i a l s e t - up
1. Open all cartons & locate inlet, hose, hose clamps and wheels.
2. Remove ALL filters & packing materials from cartons and the FA1 cabinet
3. Place the FA1 on its side & install wheels in bottom plate
4. Install the inlet to the top of the lid.
5. Remove plastic wrap from gas/odor filter (Part # FA101D or FA201D).
6. Carefully remove perforated cardboard from top and bottom of filter to expose “Green” filter media.
7. Place gas/odor filter into bottom of cabinet –note direction of airflow arrow
8. Place HEPA filter (Part # FA100 or FA100-2) on top of gas/odor filter –note airflow arrow
9. Place the pre-filter (Part # FA102B) on top of the HEPA filter.
10. Close and latch the lid.
11. Attach power cord –rear of cabinet.
L o c a t i n g t h e a i r c l e a n e r :
Placing the FA1 as close as possible to the pollution source reduces the amount of hose or duct needed,
reduces back-pressure, lowers power consumption and improves overall performance.
I n l e t h o s e a t t a c h m e n t :
The FA1 ships standard with a 1 x 2”, 2 x 2” or 1 x 3” inlet. Attach flex hose over the metal air inlet tube and
tighten securely with the stainless steel clamp.
Connect the hose to a Fumex suction hood or place as close as possible to the pollution source.
E l e c t r i c p o w e r
FA1 Series is manufactured with a universal blower/motor assembly (90-250/1/50-60). Default power
cord/plug is US (120v). Contact Fumex for additional information or options.
Confirm that correct power supply is available.

3
CONTROLS
On/Off Switch
Simple one touch controls –The green light indicating blower speed will confirm power to the unit.
Blower/Fan
The FA1 utilizes a variable speed blower with three speed settings. Press the fan button to
increase/decrease blower speed. Green light will indicate current speed setting. A flashing green light
indicates a blower failure. To reset thermal protection disconnect unit from power source and restart. If
light continues to flash contact Fumex Inc. for replacement information.
Filter monitoring
The FA1 utilizes a pressure differential switch to monitor the status of the particulate filters (3). The system
monitors across all filters simultaneously and the Orange “Change Filter” light will flash when a filter(s)
needs to be replaced. The recommended procedure is to first replace the pre-filter –(Part# FA102B) - if
light continues to flash then replace the HEPA filter. (NOTE: For heavy dust applications the polyester pre-
filter (part# FA103–located inside the FA102B) can be changed individually or use the FA102B-4 large
capacity pre-filter))
The FA1 contains a VOC indicator to detect odors/gases in the exhaust stream. When the gas/odor filter
becomes saturated (breakthrough occurs) the “Change Gas Filter” warning light will flash. (At initial start-
up or when power is disconnected the “Change Gas Filter” light will blink for a short period of time as the
voc sensor calibrates.)
GENERAL FILTER CARE
Fumex FA1 air purifiers feature a multi-stage filtration system designed to remove a wide range of
pollutants from the process plume in an extremely efficient, cost-effective manner. The sytem utilizes a
pressure differential switch to indicate a blocked / clogged filter. Once the warning light flashes, filters
should be checked and clogged filters replaced.
S T A N D A R D F I L T E R S :
Part # FA102B –Pre-filter Assembly
The pre-filter assembly is the first stage in the filtration process. The assembly is composed of high
capacity merv 11 rated filter media protected by polyester pre-filter. Unique design minimizes
operator/maintenance personnel exposure to contaminants.
Replacement:
The unique design of the pre-filter allows the filter to be changed as a complete unit or in heavy dust
applications the polyester pre-filter can be removed independently. Contact Fumex Inc. regarding any
questions/assistance.
Part # FA100 or FA100-2 HEPA Filter
The HEPA filter is 99.97% efficient in removing particles as small as 0.3from an airstream.
Particles of this size are respirable and can cause significant respiratory problems.

4
Replacement:
A HEPA’s service life is determined by the volume of sub-micron particles remaining in the airstream
after passing through the pre-filters. When properly protected, and depending on loading, HEPA filters
often provide months of service. Average service life is 2-4 months.
Part # FA101D or FA201D –Gas/Odor Filter
Most process plumes contain several gases, some odorous –some not, some toxic at elevated
concentrations –some completely harmless regardless of concentration. To ensure employee safety the
type and concentration of pollutants must be determined. Please contact Fumex Engineering for
selection assistance. For high odor applications contact Fumex for additional options.
The FA1 utilizes a blended activated carbon and activated alumina impregnated with KMnO4 filter to
capture and treat gases/odors. This combination of materials provides protection across a broad range
of gases commonly found in industrial manufacturing processes.
G E N E R A L M A I N T E N A N C E
1) The blower motor is a sealed unit, 24,000 hr. MTBF rated. It is permanently lubricated and does not
require oiling –keep it free of dust accumulations to prevent overheating.
2) Remove any loose accumulations of dust/debris from the air filter chamber periodically.
“This product employs overload protection (fuse). A blown fuse indicates an overload or short-circuit
situation. If the fuse blows, unplug the product from the outlet. Replace the fuse as per the user servicing
instructions (follow product marking for proper fuse rating) and check the product. If the replacement fuse
blows, a short circuit may be present and the product should be discarded or returned to an authorized
service facility for examination and/or repair”
Remote Start/Stop
The FA1 can be supplied with an optional remote start feature –Part # FA228. If this option is factory
installed on your unit, simply provide 24v to the red wire and the black wire is “common”. The unit will start
when the signal is applied and turn-off when signal is removed.
WARNING
“Connect Remote Starter Cable to 24v, Class 2 Power Supply Only”
WARNING
“Disconnect From All Power Supplies before Servicing”

5
R e p l a c e m e n t P a r t s
P a r t #
I t e m
P a r t #
I t e m
C a b i n e t r y
E l e c t r i c a l
FA108
Wheels, standard
FAAU500
Universal blower motor / assembly –90-250/1/50-60
FA109
Vibration Isolators
FA117
Cabinet latch
FA003
Control board assembly
FA118
Cabinet hinge
FA114
Fuse, 10 amp
FA106A
Flanged air inlet 3”
FA115
Cordset (120vac)
FA106B
Flanged air inlet 2 x 2”
FA115B
Cordset (230vac)
FA106C
Flanged air inlet 1 x 2”
FA113
Fuseholder
F i l t e r s
G a s / O d o r F i l t e r s
FA102B
Pre-Filter
FA101D
Blended carbon media –2”
FA103
Polyester pre-filter ( optional)
FA201D
Blended carbon media –6”
FA100-2
HEPA Filter
FA100
HEPA Filter
W a r r a n t y a n d L i a b i l i t y l i m i t a t i o n s :
Fumex FA1 air cleaners are guaranteed for 24 months from date of invoice to be electrically and mechanically sound. This warranty covers the
material and workmanship only. Any defective item will be repaired or replaced, at our option, free of charge provided it has not been misused,
abused, or otherwise damaged and is returned PREPAID to:
Fumex, Inc. 1150 Cobb International Pl., Kennesaw, GA 30152
There are no warranties which extend beyond the descriptions set forth in this warranty, notwithstanding any knowledge of Fumex, Inc.
regarding the use or uses intended to be made of goods, proposed changes or additions to goods, or any assistance or suggestions that may
have been made by Fumex personnel. Customer is responsible for determining the suitability of Fumex products for customer’s use or resale,
or for incorporating them into objects or applications which customer designs, assembles, constructs or manufactures.
Fumex reserves the right to discontinue any item and to make changes in the specifications, terms and conditions or prices at any time without
prior notice. Information furnished in the specifications is believed to be accurate and reliable at time of printing, however Fumex accepts no
responsibility for product use, or the effect of future design or specification changes.
For Assistance or Technical Support please Contact Fumex Inc.
phone 770-514-7907 fax 770-514-1547
USA toll-free 800-432-7550
www.fumexinc.com
Fumex, Inc.
1150 Cobb International Place
Kennesaw, GA USA 30152
Fumex, Inc., 2017, all rights reserved.
Specifications subject to change without notice

6
LEGEND
W
WHITE
1
REMOTE START CONECTOR
2
THREE PIN CONNECTOR
3
FIVE PIN CONNECTOR
FA1 UNIT
90-250/1/50-60
CONTROL PANEL
CONN #3
CONN #2
CONN #1
MOTOR
POS
NEG
F
U
S
E
W
W
W
PLUG

7
Relay activation jumper
24 volt start connector
RELAY ACTIVATION PROCEDURES FOR FA1 UNITS
1. Remove all power sources from FA1 unit
2. Locate eight screws securing cabinet bottom panel
3. Remove all and gently pry bottom panel loose
CAUTION
Do not work on panel with power applied
4. Locate relay activation Jumper on rear of control panel. (Small plastic rectangle)
5. Gently remove jumper by pulling cap off pins. Shorting cap should be installed over a single pin for
storage and to prevent loss of cap.
Once the jumper has been removed the unit will only start by applying the proper
voltage to the start stop relay. When the unit is running the on and off switch can
be used as long as start relay has power.
6. Reinstall bottom panel and screws
7. Apply power to start relay (see wiring diagram for your unit)

8
Relay activation jumper
24 volt start connector
RELAY DE-ACTIVATION
1. Disconnect all power sources to FA1 unit.
2. Locate and remove eight screws securing the bottom panel
3. Remove all eight screws and gently pry bottom panel loose
CAUTION
Do not work on panel with power applied
4.Locate relay activation Jumper on rear of control panel. (Small plastic rectangle)
5. Gently install jumper by pushing cap over pins.
Once the jumper has been installed the unit will can only be started by using the
control panel. All relays will become non-functional.
6. Reinstall control panel and screws
7. Apply power to unit
8. Start Unit