Part number: SPDCUKITT1
Description: T1,T2 & T3 SPD
T1, T2 & T3 combined Surge Protection Device (SPD) supplied
complete with 63A B Curve MCB and 16mm² connecting cables.
Type 1 SPDs shall be installed as close as possible to the origin of
the electrical installation (main distribution board) 534.4.1.1
This device must be installed and tested by a qualified electrician
in accordance with the current IET Wiring Regulations BS7671.
TECHNICAL (TABLE A)
PART NUMBER
SPDCUKITT1
BARCODE
5060523524754
DESCRIPTION
SURGE PROTECTION DEVICE T1
T2 + T3 (1+ N-PE) 36mm
Includes 63A B TYPE MCB and
cables (16mm²)
WIDTH
36mm (2 module)
STANDARD
IEC/EN 61643-11
FLAG INDICATION
GREEN: GOOD
RED: REPLACE
TECHNOLOGY
MOV (METAL OXIDE
VARISTOR) L -PE /GDT (SPARK
GAP) N - PE
VOLTAGE (Un)
230V~ 50/60Hz
SYSTEM
TN-C-S, TN-S, TT
TERMINAL CAPACITY (max.)
6mm² - 35mm²
RECOMMENDED TORQUE
2.5Nm
DEGREE OF PROTECTION
IP20
MOUNTING
35mm DIN RAIL (to EN 60715)
MAXIMUM OPERATING
VOLTAGE (Uc)
255V
RESPONSE TIME (tA)
≤100nS
MAXIMUM BACK UP FUSE
160A fuse gG
RECOMMENDED BACKUP MCB
63A
SHORT CIRCUIT WITHSTAND
(ISccR)
50kA
After installation and testing of this product it is essential
that the INSTRUCTION LEAFLET is available for reference.
TECHNICAL (TABLE B)
Lighting impulse current
(10/350µS) (L + N-PE) (Itotal)
25kA
Specific energy (L + N-PE)
(W/R)
156.25KJ/ohms
L-N MOV
(Varistors)
N-PE GDT
(Spark gap)
Max. continuous operating
voltage (AC) (Uc)
255V
(50/60Hz)
255V
(50/60Hz)
Lighting impulse current
(10/350µS) L-N / N-PE (Iimp)
12.5KA
25KA
Specific energy L-N /N-PE
(W/R)
39.06KJ/ohms
156.25KJ/ohms
Nominal discharge current
(8/20µS) L-N /N-PE (In)
12.5KA
25KA
Voltage protection level
L-N /N-PE (Up)
<1.25KV
<1.5KV
Temporary overvoltage (TOV)
L-N (UT)
440V/12 min-- withstand
Temporary overvoltage (TOV)
L-N (UT)
1200V/200ms - withstand
Voltage protection level L-PE
(Up)
2.0kV
Operating temperature range
-40〬C +80〬C
Material (housing)
Thermoplastic UL94 V0 (Black)
Weight (Kg)
0.043
CAUTION
WHEN CONDUCTING INSULATION RESISTANCE TESTING WITH SPD
FITTED IT IS RECOMMENDED EITHER THE EARTH CONNECTION OR THE
PLUG IN CARTRIDGE IS REMOVED.
IF YOU DO NOT WISH TO REMOVE THE CARTRIDGE OR EARTH
CONNECTION, THEN TESTING MUST BE AT A MAXIMUM OF 250V DC.
Before powering up the installation check all connections are
TORQUED 2.5Nm. Loose connections cause fires!
www.fusebox.co.uk
1 SYSTEM CONNECTION DIAGRAMS
1a TORQUE SETTING
Before powering up the installation check all connections are
TORQUED to 2.5Nm. Loose connections cause fires!
2 FLAG INDICATOR STATUS
•Please ensure the SPD flag indicator status is checked
regularly.
•Should the indicator change to RED the module should
be replaced ASAP to continue to provide surge
protection.
•The SPD is in parallel to the supply so in no way affects
the power to the final circuits if activated (RED).
3 SPD MODULE REPLACEMENT
•Before changing the SPD cartridge switch OFF supply.
•The 36mm module can be removed as shown below.
•Pull cartridge out of the holder firmly.
•When refitting module ensure it is pushed home firmly
and is keyed in the slots on the base.
•Once changed switch power to ON.
4 INSTALLATION IN A CONSUMER UNIT
TAIL CLAMP (ACCF) CANNOT BE USED WHEN SPDCUKITT1 IS
INSTALLED within a FuseBox consumer unit, unless an additional
mounting hole is drilled by the installer for the clamp to be fixed.
5 ENVIRONMENT
WASTE ELECTRICAL PRODUCTS SHOULD NOT BE DISPOSED OF IN
HOUSEHOLD WASTE. CONTACT YOUR RETAILER OR LOCAL
AUTHORITY FOR RECYCLING INFORMATION.
After installation and testing of this product it is essential
that the INSTRUCTION LEAFLET is available for reference.
GREEN OK
RED REPLACE
www.fusebox.co.uk

Popular Protection Device manuals by other brands

Safety 1st Oven Front Lock user guide

Safety 1st

Safety 1st Oven Front Lock user guide

GE Multilin g60 instruction manual

GE

GE Multilin g60 instruction manual

SIP Protection 2XD2 User instructions

SIP Protection

SIP Protection 2XD2 User instructions

Belkin P74976UKAP41000EA3M user manual

Belkin

Belkin P74976UKAP41000EA3M user manual

Arcteq AQ-T215 instruction manual

Arcteq

Arcteq AQ-T215 instruction manual

ABB RET615 Product guide

ABB

ABB RET615 Product guide

E.K.T. ke-DP01 quick start guide

E.K.T.

E.K.T. ke-DP01 quick start guide

Solera 706C Instructions for use and safety

Solera

Solera 706C Instructions for use and safety

ABB RED670 Relion 670 series Product guide

ABB

ABB RED670 Relion 670 series Product guide

ABB PR512 Operator's manual

ABB

ABB PR512 Operator's manual

JSP EN166: 2001 quick start guide

JSP

JSP EN166: 2001 quick start guide

GE B30 UR Series instruction manual

GE

GE B30 UR Series instruction manual

ABB Relion 670 series Commissioning manual

ABB

ABB Relion 670 series Commissioning manual

Moog G78K Series Installation and operation instruction

Moog

Moog G78K Series Installation and operation instruction

Silverline 633711 manual

Silverline

Silverline 633711 manual

nvent LANRJ45C6P instruction sheet

nvent

nvent LANRJ45C6P instruction sheet

AERMEC PRGD1 user manual

AERMEC

AERMEC PRGD1 user manual

Jatco J-7000 200 ABV installation instructions

Jatco

Jatco J-7000 200 ABV installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.