GE GTDL210ED2WW User manual

Installation
Instructions Electric Dryer
O4
In Canada, call 1.800.561.3344 or visit www.GEAppliances.ca
BEFORE YOU BEGIN
Readthese instructions completely and
corefully.
,IMPORTANT- Save these instructions
for local inspector's use.
, IMPORTANT- Observe oil governing
codes and ordinances.
, Note to Installer - Be sure to leave these
instructions with the customer.
, Note to Customer - Keep these instructions
with your Owner's Manualfor future reference.
, Before the old dryer is removed from service
or discarded, remove the dryer door.
, Service information and the wiring diagram
are located in the control console.
, Do not allow children on or in the appliance.
Close supervision of children is necessary
when the appliance isused near children.
, Install the dryer where the temperature is
above 50°F for satisfactory operation of the
dryer control system.
, Product failure due to improper installation is
not covered under the Warranty.
WARNING RiSK OF FIRE
,To reduce the risk of severe injury or death, follow all installation
instructions.
, Clothes dryer installation must be performed by u qualified installer.
Install the clothes dryer according to these instructions and in
accordance with local codes.
This dryer must be exhausted to the outdoors.
Useonly rigid metal 4" diameter ductwork insidethe dryer cabinet and use
only ULapproved transition ducting between the dryer and the home duct.
DO NOTinstall u clothes dryer with flexible plastic ducting materials. If
flexible metal (semi-rigid or foil-type) duct is installed, it must be ULlisted
and installed in accordance with the instructions found in "Connecting
The Dryer To House Vent" on pages 4-5 of this manual. Flexible venting
materials are known to collapse, be easily crushed, and trap lint. These
conditions will obstruct dryer airflow and increase the risk of fire.
Do not install or store this appliance in any locution where it could be
exposed to water and or weather.
Save these instructions. (Installers: Be sure to leave these instructions
with the customer).
NOTE: Installation and service of this dryer requires basic
mechanical and electrical skills. It is your responsibility to contact
a qualified installer to make the electrical connections.
TOOLSYOU
WILL NEED
SLIPJOINTPLIERS
FLATBLADESCREWDRIVER
PHILLIPSSCREWDRIVER
MATERIALSYOUWILL NEED
4"DAMETALDUCT
(RECOMMENDED}
)
4"DIA,FLEXIBLEMETAL(SEMI-RIGID)
ULLISTEDTRANSITIONDUCT
(IFNEEDED}
KITWXOBX!O077(INCLUDES2ELBOWS}
4"DIA.FLEXIBLEMETAL(FOILTYPE)
ULLISTEDTRANSITIONDUCT
(FNEEDED,)
#'DUCT %
4"DAMETAL
ELBOW
CLAMPS(2) EXHAUST
HOOD
OR
#'SPRING
CLAMPS(2)
DUCTTAPE GLOVES
%
SAFETY
GLASSES
3/4"STRAIN
RELIEF
ULRECOGNIZED
DRYERPOWER
CORDKIT
(NOTPROVIDED
WITHDRYER)
ULRATED
!20/240V,30A
WFH] OR4PRONGS,
IDENTIFYTHEPLUG
TYPEASPERTHE
HOUSERECEPTACLE
BEFOREPURCHASING
LINECORD,
Step 1
Step 2
Step 3
Step 4
Step 5
Step 6
Prepare the area and exhaust for installation of new dryer
(seesection 1).
Check and ensure the existing external exhaust is clean (see
section 1)and meets attached installation specifications (see
section 3).
Remove the foam shipping pads (seesection 1).
Move the dryer to the desired location.
Connect the power supply (seesection 2).
Connect the external exhaust (seesection/4).
Step 7 Levelyour dryer (seesection 5).
Step 8 Check the operation of the power supply and venting.
Step 9 Place the Owner's Manual and the Installation Instructions
in a location where they will be noticed by the owner.
For alcove or closet installation, see section 6.
For bathroom or bedroom installation, see section 7.
For mobile or manufactured home, see section 8.
For garage installation (ifallowed by local codes), see section 9.
For side or bottom exhaust, see section 10.
234D2004PO04 31-16309 03-13 GE

Installation instructions
Minimum Clearance Other Than Alcove or Closet Installation
Minimum clearance to combustible surfaces and for air opening are: 0 in.clearance both sides and 1 in. rear.Consideration
must be given to provide adequate clearance for installation and service.
[] PREPARING FOR INSTALLATION OF
NEW DRYER
TIP:Install your dryer before installing your washer. This
will allow better access when installing dryer exhaust.
REMOVING LINT FROM WALL EXHAUST
OPENING
• Remove and discard existing plastic or metal foil
transition duct and replace with UL listed transition duct.
WALL
INTERNALDUCT CHECKTHATEXHAUST
OPENING OPENS
ANDCLOSESFREEL_
TILTTHE DRYERSIDEWAYS
AND REMOVETHE FOAM
SHIPPING PADS BY
PULLING ATTHE SIDES
AND BREAKING THEM
AWAY FROM THE DRYER
LEGS.BE SURETO
REMOVEALL OF THE
FOAM PIECESAROUND
THE LEGS.
_]ELECTRICAL CONNECTION INFORMATION
WARNING - To REDUCETHERISKOF
FIRE, ELECTRICAL SHOCK AND PERSONAL iNJURY:
, DO NOT USE AN EXTENSION CORD OR AN
ADAPTER PLUG WITH THiS APPLIANCE.
Dryer must be electrically grounded in accordance with
local codes and ordinances, or in the absence of local
codes, in accordance with the NATIONAL ELECTRICAL
CODE,ANSI/NFPANO. 70.
ELECTRICAL REQUIREMENTS
This dryer must be connected to an individual branch
circuit, protected by the required time-delay fuses or
circuit breakers. A four or three-wire, single phase,
120/240V or 120/208V, 60Hz, 30 amp circuit is required.
GROUNDING INSTRUCTIONS
This dryer must be connected to a grounded metal, perma-
nent wiring system, or an equipment-grounding conductor
must be run with the circuit conductors and connected to
the equipment grounding terminal on the appliance.
CONNECTING DRYER USING 4-WIRE
CONNECTION (MUST BE USED FOR
MOBILE HOlE INSTALLATION)
NOTE: Since January 1,1996, the National Electric code
requires that the new constructions utilize a 4-wire
connection to an electric dryer.
WARNING:
Only a 4-conductor cord shall be used when the appliance
is installed in a location where grounding through the
neutral conductor is prohibited. Grounding through
the neutral is prohibited for the new branch-circuit
installations, mobile homes, recreational vehicles, and
areas where local codes prohibit grounding through the
neutral conduction.
Remove ground strap Fuse Screw Hot Relocate
and discard. Keep Wire green
green ground screw ground
screw 1
Stn 3/4" UL
Relief Recognized
Bracket Strain Relief
4 #10 AWG minimum copper conductors or 120/240V 3OApower supply
cord kit marked for use with dryers and provided with closed loop or
spade terminals with upturned ends (not supplied).
1.Turn off the circuit breaker(s) (30 amp) or remove the
dryer's circuit fuse at the electrical box.
2.Be sure the dryer cord is unplugged from the wall
receptacle.
3.Removethe power cord coverlocated at the lower back.
4. Remove and discard ground strap. Keep the green
ground screw for step 7.
5.Install 3/4 in. UL recognized strain relief to power cord
entry hole. Bring power cord through strain relief.
6.Connect power cord as follows:
A.Connect the 2 hot lines to the outer screws of
the terminal block (marked L1 and L2).
B.Connect the neutral (white) line to the center of
the terminal block (marked N).
7.Attach ground wire of power cord with the green
ground screw (hole above strain relief bracket). Tighten
all terminal block screws (3)securely.
8. Properly secure power cord to strain relief.
9. Reinstall the cover.
AIILW_KI_I||_IIO: NEVER LEAVE THE
COVER OFF OF THE TERMINAL BLOCK.

Installation instructions
CONNECTING DRYER USING 3-WIRE
CONNECTION
If required, by local code, install external
ground (not provided} to grounded metal,
cold water pipe, or other established
ground determined by a qualified
electrician. Fuse
Green Ground Screw
& Ground Strap
Screw Hot
Wire
(white}
Wire
Strain
Relief 3/4" UL
Bracket Recognized
Strain Relief
3 #10 AWG minimum copper conductors or 120/240V 30A power supply
cord kit marked for use with dryers and provided with closed loop or
spade terminals with upturned ends (not supplied).
3-wire Connection
Not for use in Canada.
DONOTuse for Mobile Home Installations.
NOTfor use on new construction.
NOTfor use on recreational vehicles.
NOTfor use in areas where local codes prohibit grounding
through the neutral conduction.
!. Turn off the circuit breaker(s) (30 amp) or remove the
dryer's circuit fuse at the electrical box.
2. Besure the dryer cord is unplugged from the wall.
3. Remove the power cord cover located at the lower
back.
4. Install 3/4 in. UL recognized strain relief to power cord
entry hole. Bring power cord through strain relief.
5. Connect power cord as follows:
A. Connect the 2 hot lines to the outer screws of the
terminal block (marked L! and L2).
B.Connect the neutral (white) line to the center of the
terminal block (marked N).
6. Be sure ground strap is connected to neutral (center)
terminal of block and to green ground screw on cabinet
rear.Tighten all terminal block screws (3)securely.
7. Properly secure power cord to strain relief.
8. Reinstall the cover.
^, l ,^,.,,, ,,,,,-.
|Wf'_K|'_||'_: NEVER LEAVE THE
COVER OFF OF THE TERMINAL BLOCK.
[-_EXHAUST INFORMATIO
, ,WARNING -IN CANADA AND IN THE
UNITED STATES,THE REQUIRED EXHAUST DUCT
DIAMETER IS4 in(102mm). DO NOT USE DUCT
LONGER THAN SPECIFIED IN THE EXHAUST
LENGTH TABLE.
Using exhaust longer than specified length will:
, Increase the drying times and the energy cost.
, Reduce the dryer life.
, Accumulate lint, creating a potential fire hazard.
The correct exhaust installation is YOUR
RESPONSIBILITY.Problems due to incorrect installation
are not covered by the warranty,
Remove and discard existing plastic or metal foil
transition duct and replace with ULlisted transition duct.
The MAXIMUM ALLOWABLEduct length and number of
bends of the exhaust system depends upon the type of
duct, number of turns, the type of exhaust hood (wall
cap), and all conditions noted below. The maximum duct
length for rigid metal duct isshown in the table below.
EXHAUST LENGTH
RECOMMENDEDMAXIMUMLENGTH
Exhaust Hood Types
Use only for short
Recommended run installations
112"
No of 90° Rigid Rigid
Elbows Metdl Met(]l
0 150 Feet 125 Feet
i 135 Feet 115 Feet
2 125 Feet 105 Feet
3115 Feet 95 Feet
4 105 Feet 85 Feet
5 95 Feet 75 Feet
, Forevery extra 90°
length by 10ft. elbow, reduce the allowable vent system
, Two 45° elbows will betreated likeone 90°elbow.
, Forthe side exhaust installations, add one 90° elbow to the
chart.
, Thetotal vent system length includes all the straight portions
and elbows of the system (transitionduct included).
EXHAUST SYSTEM CH ECK LIST
HOODORWALLCAP
, Terminate in a manner to prevent back drafts or entry of birds
or other wildlife.
, Termination should present minimal resistance to the
exhaust air flow and should require little or no maintenance
to prevent clogging.
, Neverinstall a screen in or over the exhaust duct. Thiscould
cause lintbuild up.
, Wall caps must be installed at least 12 in.above ground level
or anyother obstruction with the opening pointed down.
SEPARATIONOFTURNS
Forbest performance, separate all turns by at least 4 ft. of
straight duct, including distance between lastturn and exhaust
hood.
TURNSOTHERTHAN90°
, Oneturn of 450or lessmay be ignored.
, Two 450turns should be treated as one 900turn.
, Eachturn over 450should be treated asone 900turn.

Installation
SEALING OF JOINTS
. All joints should be tight to avoid leaks. The male end of
each section of duct must point away from the dryer.
. The duct shall not be assembled with screws or other
fastening means that extend into the duct and catch lint.
. Duct joints can be made air and moisture-tight by
wrapping the overlapped joints with duct tope.
. Horizontal runs should slope clown toward the outdoors
1/4 inch per foot.
INSULATION
Duct work that runs through on unheated area or is near
air conditioning should be insulated to reduce condensation
and lint build-up.
@ EXHAUST CONNECTION
WARNING - TO REDUCE THE RISK
OF FIRE OR PERSONAL INJURY:
.This clothes dryer must be exhausted to the outdoors.
. Use only 4" rigid metal ducting for the home exhaust
duct.
.Use only 4" rigid metal or UL-listed flexible metal
(semi-rigid or foil-type) duct to connect the dryer to the
home exhaust duct. It must be installed in accordance
with the instructions found in "Connecting the Dryer to
House Vent" on pages 4-5 of this manual.
. Do not terminate exhaust in a chimney, a wall, a
ceiling, gas vent, crawl space, attic, under an enclosed
floor, or in any other concealed space of a building. The
accumulated lint could create a potential fire hazard.
.Never terminate the exhaust into a common duct with
a kitchen exhaust system. A combination of grease
and lint creates a potential fire hazard.
. Do not use duct longer than specified in the exhaust
length table. Longer ducts can accumulate lint,
creating a potential fire hazard.
. Never install a screen in or over the exhaust duct. This
will cause lint to accumulate, creating a potential fire
hazard.
. Do not assemble ductwork with any fasteners that
extend into the duct. These fasteners can accumulate
lint, creating a potential fire hazard.
. Do not obstruct incoming or exhausted air.
. Provide an access for inspection and cleaning of the
exhaust system, especially at turns and joints. Exhaust
system shall be inspected and cleaned at least once a
year.
THIS DRYER COMES READY FOR REAR
EXHAUSTING. IF SPACE IS LIMITED,
USE THE INSTRUCTIONS IN STEP lO TO
EXHAUST DIRECTLY FROM THE SIDE OR
THE BOTTOM OF THE CABINET.
nstructions
STANDARD REAREXHAUST
{Vented at floor level}
FOR STRAIGHT LINE INSTALLATION,
CONNECT THE DRYER EXHAUST TO
THE EXTERNAL EXHAUST HOOD
USING DUCT TAPE OR CLAIqR
EXTERNAL
DUCT
OPENING
DUCT TAPE OR
DUCT CLAMP
4" METAL DUCT
(CUT TO PROPER
LENGTH) DUCT TAPE OR
DUCT CLAMP
NOTE: WE STRONGLY RECOMMEND SOLID METAL EXHAUST DUCTING.
HOWEVER, IF FLEXIBLE DUCTING IS USED IT MUST BE UL-LISTED METAL
NOT PLASTIC.
STANDARD REAR EXHAUST
{Vented above floor level}
ELBOWHIGHLY
RECOMMENDED--
RECOhdP1ENDED
CONFIGURATION
TOMINIMIZE
EXHAUST
BLOCKAGE,
NOTE: ELBOWS WILL PREVENT DUCT
KINKING AND COLLAPSING.
CONNECTING THE DRYER TO HOUSE VENT
RIGID METALTRANSITION DUCT
. For best drying performance, a rigid metal transition
duct isrecommended.
. Rigid metal transition ducts reduce the risk of crushing
and kinking.
UL-LISTEDFLEXIBLEMETAL(SEMI-RIGID}TRANSITIONDUCT
. If rigid metal duct cannot be used, then UL-listed flexible
metal (semi-rigid)ducting can be used (KitWXO8X10077).
. Never install flexible metal duct in walls, ceilings, floors or
other enclosed spaces.
. Total length of flexible metal duct should not exceed 8
feet (2.4m).

Installation instructions
. For many applications, installing elbows at both the dryer
and the wall is highly recommended (see illustrations
below). Elbows allow the dryer to sit close to the wall
without kinking and or crushing the transition duct,
maximizing drying performance.
. Avoid resting the duct on sharp objects.
UL-LISTEDFLEXIBLEMETAL(FOIL-TYPE)TRANSITIONDUCT
. In special installations, it may be necessary to connect
the dryer to the house vent using a fexible metal (foil-
type) duct. A UL-listed flexible metal (foil-type) duct may
be used ONLYin installations where rigid metal or flexible
metal (semi-rigid) ducting cannot be used AND where u 4"
diameter can be maintained throughout the entire length
of the transition duct.
. In Canada and the United States, only the flexible metal
(foil-type) ducts that comply with the "Outline for Clothes
Dryer Transition Duct Subject 2158A" shall be used.
. Never install flexible metal duct in walls, ceilings, floors or
other enclosed spaces.
. Total length of flexible metal duct should not exceed 8 feet
(2.4m).
. Avoid resting the duct on sharp objects.
ELBOW
RECOMMENDED
__S HIGHLY
RECOMMENDED
EXCESSLVE
EXHAUST
LENGTH
DO NOT)
CRUSH
FLEXIBLE
EXHAUST
AGAINST
For best drying performance
1 Slide one end of the duct over the clothes dryer outlet
pipe.
2.Secure the duct with a clamp.
3.With the dryer in its permanent position, extend the duct
to its full length. Allow 2" of duct to overlap the exhaust
pipe. Cut off and remove excess duct. Keep the duct us
straight as possible for maximum airflow.
4.Securethe duct to the exhaust pipe with the other clump.
_-_ LEVELING AND STABILIZING YOUR DRYER
Stand the dryer upright near the final location and adjust
the 4 leveling legs,at the corners, to ensure that the dryer
islevel from side to side and front to rear.
LEVEL
FRONT-T0-BACK. LEVEL
SIDE-TO-SIDE
4LEVELINGLEGS
ALCOVE OR CLOSET INSTALLATION
. If your dryer is approved for installation in an alcove or
closet, it will be stated on a label on the dryer back.
.The dryer MUST be vented to the outdoors. See the
EXHAUSTINFORMATION sections 3 & 4.
. Minimum clearance between dryer cabinet and adjacent
walls or other surfaces is:
0 in. either side
3 in.front
3 in. rear
. Minimum vertical space from floor to overhead cabinets,
ceiling, etc. is52 in.
.Closet doors must be Iouvered or otherwise ventilated
and must contain a minimum of 60 sq. in. of open area
equally distributed. If the closet contains both a washer
and a dryer, doors must contain a minimum of 120 sq. in.
of open area equally distributed.

Installation Instructions
[] BATHROOM OR BEDROOM iNSTALLATiON
.ThedryerMUST be ventedtotheoutdoors.See EXHAUST
INFORMATION section3 &4.
. The installation must conform with local codes or, in the
absence of local codes, with the NATIONALELECTRICAL
CODE,ANSI/NFPANO.70.
[_]MOBILE OR MANUFACTURED HOME
INSTALLATION
. Installation must conform to the MANUFACTUREDHOME
CONSTRUCTION& SAFETY STANDARD,TITLE 24, PART
32-80 or, when such standard is not applicable, with
AMERICAN NATIONAL STANDARD FOR MOBILE HOME,
ANSI/NFPANO.501B.
.The dryer MUST be vented to the outdoors with the
termination securely fastened to the mobile home
structure. (SeeEXHAUSTINFORMATIONsection 3 & 4).
.The vent MUSTNOT be terminated beneath a mobile or
manufactured home.
.The vent duct material MUSTBEMETAL.
. Do not use sheet metal screws or other fastening devices
which extend into the interior of the exhaust vent.
. See section 2 for electrical connection information.
[_]GARAGE INSTALLATION (IF ALLOWED
BY LOCAL CODES}
. Dryers installed in garages must be elevated 18 inches
(46cm) above the floor.
_07DRYER EXHAUST TO RIGHT OR
BOTTOM CABINET
,WARNING - BEFOREPERFORMING
THIS EXHAUST INSTALLATION, BE SURE
TO DISCONNECT THE DRYER FROM iTS
ELECTRICAL SUPPLY. PROTECT YOUR
HANDS AND ARMS FROM SHARP EDGES
WHEN WORKING iNSiDE THE CABINET.
BE SURE TO WEAR GLOVES.
REMOVE
SCREW
ANDSAVE
REMOVEDESIRED
KNOCKOUT(ONEONLY).
Detach and remove the bottom or right side knockout as
desired. Remove the screw inside the dryer exhaust duct
and save. Pull the duct out of the dryer.
FIXINGHOLE,
B n _
Cut the duct as shown and keep portion A.
TAB LOCATION
BENDTAB
UP45o
Through the rear opening, locate the tab in the middle of
the appliance base. Lift the tab to about 450 using a flat
blade screwdriver.
ADDING NEW DUCT
FiXiNG
HOLE
PORTION"A'
Reconnect the cut portion (A)of the duct to the blower
housing. Make sure that the shortened duct is aligned with
the tab in the base. Use the screw saved previously to secure
the duct in place through the tab on the appliance base.

Installation
ADDING ELBOW AND DUCT FOR
EXHAUST TO RIGHT SIDE OF CABINET
,Preassemble 4" elbow with 4" duct. Wrap duct tape
oround joint.
*Insert duct assembly, elbow first, through the side
opening and connect the elbow to the dryer internal
duct.
ACAUTION: Be sure not to pullordamage the
electrical wires inside the dryer when inserting the duct.
DUCT
TAPE
. Apply duct tape as shown on the joint between the
dryer internal duct and the elbow.
DUCT
H
CAUTION:
Internalduct jointsmust be
securedwithtape,otherwise
theymay separateand cause
a safetyhazard.
ADDING ELBOW FOR EXHAUST
THROUGH BOTTOM OF CABINET
. Insert the elbow through the rear opening and connect
it to the dryer internal duct.
Apply duct tape on the joint between the dryer internal
duct and elbow, as shown above.
J
CAUTION:
Internal duct joints must be secured with tape,
otherwise they may separate and cause a
safetyhazard.
Instructions
ADDING COVER PLATE TO REAR OF
CABINET {SIDES AND BOTTOM EXHAUST}
PLATE
{KITWEIM454)
Connect standard metal elbows and ducts to complete the
exhaustsystem.Coverback opening with a plate(KitWEIM454)
available from your local service provider. Placedryer in final
location.
_WARNING-NEVER LEAVE THE
BACK OPENING WITHOUT THE PLATE
{KIT WEIM4S4}.
[_]CHANGING DIRECTION OF DOOR
OPENING {OPTIONAL}
1.Openthe door and removethe filler plugsoppositethe hinges.
With the door completely open, remove the bottom screws
from each hinge on the dryerface. Insertthese screws about
half way into the TOP holes,for each hinge on the opposite
side (whereyou removed the filler plugs).Applyfirm pressure
to get the screwstarted.
2.Loosenthe top screws from each hinge onthe dryer face half
way.With one hand holding the top of the door and the other
hand holding the bottom, remove the door from the dryer by
lifting it UPand OUT.
3.Rotatethe door 1800.Insert the door on the opposite sideof
the opening by moving the door IN and DOWN until the top
hinge and the bottom hinge ore resting on the top screws
inserted in step 1.
4. Removethe remaining screws from the side of the opening
from which the door was removed.With these screwssecure
each hinge at the bottom. Tightenthe two top screws oneach
hinge. Reinsertthe plastic plugs on the side from which the
door was removed.
REMOVETHEBOTTOMSCREW
FROMEACHHINGEONTHE
DRYERFACE\
LOOSENTHETOPSCREWSFROMEACH
HINGE0 THEDRYERFACEHALFWAY
MOVETHEDOORINANDDOWNUNTIL SECUREEACHHINGEATTHE
THETOPHINGEANDTHEBOTTOMHINGE BOTTOMANDTIGHTENTHETWO
ARERESTINGONTHETOPSCREWS TOPSREWSOFEACHHINGE
INSERTEDINSTEP1
7

Installation
_] SERViCiNG
_,WAR NING- LABEL ALL WIRES PRIOR
TO DiSCONNECTiNG WHEN SERViCiNG
CONTROLS. WIRING ERRORS CAN CAUSE
iMPROPER AND DANGEROUS OPERATION
AFTER SERVICI NG/I NSTALLATION.
Instructions
REGISTER YOUR NEW APPLIANCE TO RECEIVE ANY
IMPORTANT PRODUCT NOTIFICATIONS.
Please go to www.GEAppliunces.com or mail in
your product registration cord.
For questions on installation, call: 800.626.2000 (US)or
800-561-3344 (Canada).
Table of contents
Other GE Dryer manuals