GE AMP1B1 User manual

AMP1B1, AMP1C2, AMP1C3
Compact Power and Energy Meter
for ReliaGear®Lighting Panels

2AMP1B1, AMP1C2, AMP1C3 Compact Power and Energy Meter
Safety
FCC PART 15 Information Note:This equipment has been tested
by the manufacturer and found to comply with the limits for a
class B digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a
residential environment. This equipment generates, uses, and can
radiate radio frequency energy and, if not installed and used in
accordance with the instruction manual, may cause harmful
interference to radio communications. This device complies with
part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) This device must accept any interference received, including
interference that may cause undesired operation.
Modifications to this product without the express authorization
of the manufacturer nullify this statement.
A qualified person is one who has skills and knowledge related to
the construction and operation of this electrical equipment
and the installation, and has received safety training to recognize
and avoid the hazards involved.
NEC2011 Article 100: No responsibility is assumed by
manufacturer for any consequences arising out of the use of
this material. Control system design must consider the potential
failure modes of control paths and, for certain critical control
functions, provide a means to achieve a safe state during and
after a path failure. Examples of critical control functions are
emergency stop and over-travel stop.
This symbol indicates an electrical shock hazard exists.
Documentation must be consulted where this symbol
is used on the product.
DANGER: Hazard of Electric Shock, Explosion or Arc Flash
Failure to follow these instructions will result in death or
serious injury.
• Follow safe electrical work practices. See NFPA 70E in the
USA, or applicable local codes.
• This equipment must only be installed and serviced by
qualified electrical personnel.
• Read, understand and follow the instructions before
installing this product.
• Turn off all power supplying equipment before working
on or inside the equipment.
• Use a properly rated voltage sensing device to confirm
power is off. DO NOT DEPEND ON THIS PRODUCT FOR
VOLTAGE INDICATION
• Only install this product on insulated conductors.
WARNING: Loss of Control
Failure to follow these instructions may cause injury,
death or equipment damage.
• Assure that the system will reach a safe state during and
after a control path failure.
• Separate or redundant control paths must be provided for
critical control functions.
• Test the effect of transmission delays or failures of
communication links.
• Each implementation of equipment using communication
links must be individually and thoroughly tested for
proper operation before placing it in service.
NOTICE:
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified
locations.
• The installer is responsible for conformance to all
applicable codes
• Mount this product inside a suitable fire and electrical
enclosure.

3
AMP1B1, AMP1C2, AMP1C3 Compact Power and Energy Meter
Measurement Accuracy
Real Power/Energy
Reactive Power/Energy
Current
Voltage
L-NL-L
Sample Rate
Data Update Rate
Type of Measurement
One to three phase AC system
Input Voltage
Measured AC
L-L) for stated accuracy
L-LL-N)
L-N
Metering Over-Range
Impedance L-NL-L
Frequency
Input Current
CT Scaling
Measured Input Range
Impedance
Control Power
AC
L-LL-N)
L-N
DC
Ride Through
Output
Alarm Contacts
(all models)
Real Energy Pulse
Contacts (all models)
AND Reactive Energy
Pulse Contacts
Mechanical
IP Degree of Protection
Display Characteristics Back-lit blue LCD
Terminal Block Screw
Torque
)
Rail
Environmental
Operating Temp Range
Storage Temp Range
Humidity Range
Altitude of Operation
Metering
North America
L-NL-L
CE L-N
Conducted and
Radiated Emissions
Class B (residential and light industrial)
Conducted and
Radiated Immunity
Compliance
Agency Approvals
US and Canada (cULus)
Europe (CE)
1External DC current limiting is required, see fuse recommendations.
Specifications

4AMP1B1, AMP1C2, AMP1C3 Compact Power and Energy Meter
AMP1
Description – DIN Mount (Meter Only)
B1 = Pulse and alarm outputs only
C2 = Modbus full data set; RS-485, pulse and alarm outputs
C3 = Modbus full data set, data logging; RS-485, pulse and alarm outputs
Dimensions
4.2”
(107mm)
3.6”
(91mm)
1.5”
(39mm)
2.3”
(59mm)
1.9”
(48mm)
1.8”
(45mm)
Bottom View
3.6”
(91 mm)
4.2”
(107 mm)
0.2”
(4 mm)
Bottom View
3.9”
(99 mm)
2.4”
(61 mm)
++
+
4.3”
(109 mm)
1.2”
(31 mm) 0.3”
(8 mm)
0.4”
(10 mm)
Product Identification
Description – DIN Mount (Meter Only)
AMP1
B1 = Pulse and alarm outputs only
C2
C3
alarm outputs
Dimensions
DIN Mount Configuration
Bottom View
Screw Mount Configuration
Bottom View
Product Overview
The AMP1 Series DIN Rail Power Meter provides a solution for
measuring energy data with a single device. Inputs include
Control Power, CT, and 3-phase voltage. The AMP1 supports
multiple output options, including solid state relay contacts,
Modbus (with or without data logging), and pulse. The LCD
screen on the faceplate allows instant output viewing.
The meter is housed in a plastic enclosure suitable for installation
on T35 DIN rail according to EN50022. The AMP1 can be mounted
with any orientation over the entire ambient temperature range,
either on a DIN rail or in a panel. The meter is not sensitive to CT
orientation to reduce installation errors.
Data Output
Full Data Set (FDS)
•
•
• Configurable for CT & PT ratios, system type, and passwords
• Diagnostic alerts
• Current: 3-phase average
• Volts: 3-phase average
• Current: by phase
• Volts: by phase Line-Line and Line-Neutral
• Power: Real, Reactive, and Apparent 3-phase total and
per phase
• Power factor: 3-phase average and per phase
• Frequency
• Power demand: most Recent and Peak
• Demand configuration: Fixed, Rolling Block, and External Sync
(Modbus only)
Data Logging (includes all FDS outputs, plus)
• Real Time Clock: user configurable
• 10 user configurable log buffers: each buffer holds 5760 16-bit
entries (user configures which 10 data points are stored in
these buffers)
• User configurable logging interval (when configured for a 15
minute interval, each buffer holds 60 days of data)
• Continuous and Single Shot logging modes: user selectable
• Auto write pause: read logs without disabling the meter’s data
logging mode
AMP1
Description – DIN Mount (Meter Only)
B1 = Pulse and alarm outputs only
C2 = Modbus full data set; RS-485, pulse and alarm outputs
C3 = Modbus full data set, data logging; RS-485, pulse and alarm outputs
Dimensions
4.2”
(107mm)
3.6”
(91mm)
1.5”
(39mm)
2.3”
(59mm)
1.9”
(48mm)
1.8”
(45mm)
Bottom View
3.6”
(91 mm)
4.2”
(107 mm)
0.2”
(4 mm)
Bottom View
3.9”
(99 mm)
2.4”
(61 mm)
++
+
4.3”
(109 mm)
1.2”
(31 mm) 0.3”
(8 mm)
0.4”
(10 mm)
AMP1
Description – DIN Mount (Meter Only)
B1 = Pulse and alarm outputs only
C2 = Modbus full data set; RS-485, pulse and alarm outputs
C3 = Modbus full data set, data logging; RS-485, pulse and alarm outputs
Dimensions
4.2”
(107mm)
3.6”
(91mm)
1.5”
(39mm)
2.3”
(59mm)
1.9”
(48mm)
1.8”
(45mm)
Bottom View
3.6”
(91 mm)
4.2”
(107 mm)
0.2”
(4 mm)
Bottom View
3.9”
(99 mm)
2.4”
(61 mm)
++
+
4.3”
(109 mm)
1.2”
(31 mm) 0.3”
(8 mm)
0.4”
(10 mm)
AMP1
Description – DIN Mount (Meter Only)
B1 = Pulse and alarm outputs only
C2 = Modbus full data set; RS-485, pulse and alarm outputs
C3 = Modbus full data set, data logging; RS-485, pulse and alarm outputs
Dimensions
4.2”
(107mm)
3.6”
(91mm)
1.5”
(39mm)
2.3”
(59mm)
1.9”
(48mm)
1.8”
(45mm)
Bottom View
3.6”
(91 mm)
4.2”
(107 mm)
0.2”
(4 mm)
Bottom View
3.9”
(99 mm)
2.4”
(61 mm)
++
+
4.3”
(109 mm)
1.2”
(31 mm) 0.3”
(8 mm)
0.4”
(10 mm)

5
AMP1B1, AMP1C2, AMP1C3 Compact Power and Energy Meter
Product Diagram Wiring Diagram Symbols
To avoid distortion, use parallel wires for control power and
voltage inputs. The following symbols are used in the wiring
diagrams on the following pages.
CAUTION: RISK OF EQUIPMENT DAMAGE
• This product is designed only for use with 1V or 0.33V
current transducers (CTs).
• DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON
THIS PRODUCT.
• Failure to follow these instructions can result in
overheating and permanent equipment damage.
Product Diagram
Alarm Energy
kW
h
12
3
4
.
4
4
5
CONTROL POWER
0.1A 50/60 Hz
ABCN 12
ABCAlarm Energy
NC NO + - S
OUTPUT
Common - 1 or 1/3VAC Input
-
+
-
+
-
+
IA
IB
IC
Phase Loss
Alarm
Output Varies
by Model1
Phase
VA
VB
VC
Neutral
Earth
Control
Power
UL: 90V
L-N
- 600V
L-L
CE: 90V
L-N
- 300VL-N
VOLTAGE INPUTS
CAT III 50/60 Hz
+
–
The red alarm LED lights when any of the 3 phase voltages drop below the
selected threshold: The green Energy LED lights momentarily each time the
Energy output pulse is active.
1Two Output Options Available
+ - S
VARh
VARh
Output
RS-485
Modbus
Shield
+ - S
AMP1B1 -Pulse AMP1Cx-RS-485
Wiring Diagram Symbols
To avoid distortion, use parallelwires for control power and
voltage inputs. The following symbols are used in the wiring
diagrams on the following pages.
Symbol Description
Voltage Disconnect Switch
Fuse (Installer is responsible for ensuring compliance
with local requirements. No fuses are included with
the meter.)
Earth Ground
X2
X1
Current Transducer
Potential Transformer
Protection containing a voltage disconnect switch
with a fuse or disconnect circuit breaker. The
protection device must be rated for the available
short-circuit current at the connection point.
hehe
CAUSION: RISK OF EQUIPMENT DAMAGE
• This product is designed only for use with 1V or 0.33V
current transducers (CTs).
• DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS
PRODUCT.
• Failureto follow these instructions can result in
overheating and permanent equipment damage.
Product Diagram
Alarm Energy
kW
h
12
3
4
.
44
5
CONTROL POWER
0.1A 50/60 Hz
ABCN 12
ABCAlarm Energy
NC NO + - S
OUTPUT
Common - 1 or 1/3VAC Input
-
+
-
+
-
+
IA
IB
IC
Phase Loss
Alarm
Output Varies
by Model1
Phase
VA
VB
VC
Neutral
Earth
Control
Power
UL: 90V
L-N
- 600V
L-L
CE: 90V
L-N
- 300VL-N
VOLTAGE INPUTS
CAT III 50/60 Hz
+
–
The red alarm LED lights when any of the 3 phase voltages drop below the
selected threshold: The green Energy LED lights momentarily each time the
Energy output pulse is active.
1Two Output Options Available
+ - S
VARh
VARh
Output
RS-485
Modbus
Shield
+ - S
AMP1B1 -Pulse AMP1Cx-RS-485
Wiring Diagram Symbols
To avoid distortion, use parallelwires for control power and
voltage inputs. The following symbols are used in the wiring
diagrams on the following pages.
Symbol Description
Voltage Disconnect Switch
Fuse (Installer is responsible for ensuring compliance
with local requirements. No fuses are included with
the meter.)
Earth Ground
X2
X1
Current Transducer
Potential Transformer
Protection containing a voltage disconnect switch
with a fuse or disconnect circuit breaker. The
protection device must be rated for the available
short-circuit current at the connection point.
hehe
CAUSION: RISK OF EQUIPMENT DAMAGE
• This product is designed only for use with 1V or 0.33V
current transducers (CTs).
• DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS
PRODUCT.
• Failureto follow these instructions can result in
overheating and permanent equipment damage.
Product Diagram
Alarm Energy
kW
h
12
3
4
.
44
5
CONTROL POWER
0.1A 50/60 Hz
ABCN 12
ABCAlarm Energy
NC NO + - S
OUTPUT
Common - 1 or 1/3VAC Input
-
+
-
+
-
+
IA
IB
IC
Phase Loss
Alarm
Output Varies
by Model1
Phase
VA
VB
VC
Neutral
Earth
Control
Power
UL: 90V
L-N
- 600V
L-L
CE: 90V
L-N
- 300VL-N
VOLTAGE INPUTS
CAT III 50/60 Hz
+
–
The red alarm LED lights when any of the 3 phase voltages drop below the
selected threshold: The green Energy LED lights momentarily each time the
Energy output pulse is active.
1Two Output Options Available
+ - S
VARh
VARh
Output
RS-485
Modbus
Shield
+ - S
AMP1B1 -Pulse AMP1Cx-RS-485
Wiring Diagram Symbols
To avoid distortion, use parallelwires for control power and
voltage inputs. The following symbols are used in the wiring
diagrams on the following pages.
Symbol Description
Voltage Disconnect Switch
Fuse (Installer is responsible for ensuring compliance
with local requirements. No fuses are included with
the meter.)
Earth Ground
X2
X1
Current Transducer
Potential Transformer
Protection containing a voltage disconnect switch
with a fuse or disconnect circuit breaker. The
protection device must be rated for the available
short-circuit current at the connection point.
hehe
CAUSION: RISK OF EQUIPMENT DAMAGE
• This product is designed only for use with 1V or 0.33V
current transducers (CTs).
• DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS
PRODUCT.
• Failureto follow these instructions can result in
overheating and permanent equipment damage.
The red alarm LED lights when any of the 3 phase voltages drop below the selected
threshold: The green Energy LED lights momentarily each time the Energy output pulse
is active.
1Two Output Options Available
AMP1B1 - Pulse AMP1Cx - RS-485
Two 5-character
rows of display text.
• Top row
alphanumeric
• Bottom row
numeric only
Symbol Description
Voltage Disconnect Switch
Fuse (Installer is responsible for ensuring compliance
with local requirements. No fuses are included with
the meter.)
Earth Ground
Current Transducer
Potential Transformer
Protection containing a voltage disconnect switch
with a fuse or disconnect circuit breaker. The
protection device must be rated for the available
short-circuit current at the connection point.
Product Diagram
Alarm Energy
kW
h
12
3
4
.
44
5
CONTROL POWER
0.1A 50/60 Hz
ABCN 12
ABCAlarm Energy
NC NO + - S
OUTPUT
Common - 1 or 1/3VAC Input
-
+
-
+
-
+
IA
IB
IC
Phase Loss
Alarm
Output Varies
by Model1
Phase
VA
VB
VC
Neutral
Earth
Control
Power
UL: 90V
L-N
- 600V
L-L
CE: 90V
L-N
- 300VL-N
VOLTAGE INPUTS
CAT III 50/60 Hz
+
–
The red alarm LED lights when any of the 3 phase voltages drop below the
selected threshold: The green Energy LED lights momentarily each time the
Energy output pulse is active.
1Two Output Options Available
+ - S
VARh
VARh
Output
RS-485
Modbus
Shield
+ - S
AMP1B1 -Pulse AMP1Cx-RS-485
Wiring Diagram Symbols
To avoid distortion, use parallelwires for control power and
voltage inputs. The following symbols are used in the wiring
diagrams on the following pages.
Symbol Description
Voltage Disconnect Switch
Fuse (Installer is responsible for ensuring compliance
with local requirements. No fuses are included with
the meter.)
Earth Ground
X2
X1
Current Transducer
Potential Transformer
Protection containing a voltage disconnect switch
with a fuse or disconnect circuit breaker. The
protection device must be rated for the available
short-circuit current at the connection point.
he
he
CAUSION: RISK OF EQUIPMENT DAMAGE
• This product is designed only for use with 1V or 0.33V
current transducers (CTs).
• DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS
PRODUCT.
• Failureto follow these instructions can result in
overheating and permanent equipment damage.
Product Diagram
Alarm Energy
kW
h
12
3
4
.
44
5
CONTROL POWER
0.1A 50/60 Hz
ABCN 12
ABCAlarm Energy
NC NO + - S
OUTPUT
Common - 1 or 1/3VAC Input
-
+
-
+
-
+
IA
IB
IC
Phase Loss
Alarm
Output Varies
by Model1
Phase
VA
VB
VC
Neutral
Earth
Control
Power
UL: 90V
L-N
- 600V
L-L
CE: 90V
L-N
- 300VL-N
VOLTAGE INPUTS
CAT III 50/60 Hz
+
–
The red alarm LED lights when any of the 3 phase voltages drop below the
selected threshold: The green Energy LED lights momentarily each time the
Energy output pulse is active.
1Two Output Options Available
+ - S
VARh
VARh
Output
RS-485
Modbus
Shield
+ - S
AMP1B1 -Pulse AMP1Cx-RS-485
Wiring Diagram Symbols
To avoid distortion, use parallelwires for control power and
voltage inputs. The following symbols are used in the wiring
diagrams on the following pages.
Symbol Description
Voltage Disconnect Switch
Fuse (Installer is responsible for ensuring compliance
with local requirements. No fuses are included with
the meter.)
Earth Ground
X2
X1
Current Transducer
Potential Transformer
Protection containing a voltage disconnect switch
with a fuse or disconnect circuit breaker. The
protection device must be rated for the available
short-circuit current at the connection point.
hehe
CAUSION: RISK OF EQUIPMENT DAMAGE
• This product is designed only for use with 1V or 0.33V
current transducers (CTs).
• DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS
PRODUCT.
• Failureto follow these instructions can result in
overheating and permanent equipment damage.
Product Diagram
Alarm Energy
kW
h
12
3
4
.
44
5
CONTROL POWER
0.1A 50/60 Hz
ABCN 12
ABCAlarm Energy
NC NO + - S
OUTPUT
Common - 1 or 1/3VAC Input
-
+
-
+
-
+
IA
IB
IC
Phase Loss
Alarm
Output Varies
by Model1
Phase
VA
VB
VC
Neutral
Earth
Control
Power
UL: 90V
L-N
- 600V
L-L
CE: 90V
L-N
- 300VL-N
VOLTAGE INPUTS
CAT III 50/60 Hz
+
–
The red alarm LED lights when any of the 3 phase voltages drop below the
selected threshold: The green Energy LED lights momentarily each time the
Energy output pulse is active.
1Two Output Options Available
+ - S
VARh
VARh
Output
RS-485
Modbus
Shield
+ - S
AMP1B1 -Pulse AMP1Cx-RS-485
Wiring Diagram Symbols
To avoid distortion, use parallelwires for control power and
voltage inputs. The following symbols are used in the wiring
diagrams on the following pages.
Symbol Description
Voltage Disconnect Switch
Fuse (Installer is responsible for ensuring compliance
with local requirements. No fuses are included with
the meter.)
Earth Ground
X2
X1
Current Transducer
Potential Transformer
Protection containing a voltage disconnect switch
with a fuse or disconnect circuit breaker. The
protection device must be rated for the available
short-circuit current at the connection point.
hehe
CAUSION: RISK OF EQUIPMENT DAMAGE
• This product is designed only for use with 1V or 0.33V
current transducers (CTs).
• DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS
PRODUCT.
• Failureto follow these instructions can result in
overheating and permanent equipment damage.
Product Diagram
Alarm Energy
kW
h
12
3
4
.
44
5
CONTROL POWER
0.1A 50/60 Hz
ABCN 12
ABCAlarm Energy
NC NO + - S
OUTPUT
Common - 1 or 1/3VAC Input
-
+
-
+
-
+
IA
IB
IC
Phase Loss
Alarm
Output Varies
by Model1
Phase
VA
VB
VC
Neutral
Earth
Control
Power
UL: 90V
L-N
- 600V
L-L
CE: 90V
L-N
- 300VL-N
VOLTAGE INPUTS
CAT III 50/60 Hz
+
–
The red alarm LED lights when any of the 3 phase voltages drop below the
selected threshold: The green Energy LED lights momentarily each time the
Energy output pulse is active.
1Two Output Options Available
+ - S
VARh
VARh
Output
RS-485
Modbus
Shield
+ - S
AMP1B1 -Pulse AMP1Cx-RS-485
Wiring Diagram Symbols
To avoid distortion, use parallelwires for control power and
voltage inputs. The following symbols are used in the wiring
diagrams on the following pages.
Symbol Description
Voltage Disconnect Switch
Fuse (Installer is responsible for ensuring compliance
with local requirements. No fuses are included with
the meter.)
Earth Ground
X2
X1
Current Transducer
Potential Transformer
Protection containing a voltage disconnect switch
with a fuse or disconnect circuit breaker. The
protection device must be rated for the available
short-circuit current at the connection point.
he
he
CAUSION: RISK OF EQUIPMENT DAMAGE
• This product is designed only for use with 1V or 0.33V
current transducers (CTs).
• DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS
PRODUCT.
• Failureto follow these instructions can result in
overheating and permanent equipment damage.
Product Diagram
Alarm Energy
kW
h
12
3
4
.
44
5
CONTROL POWER
0.1A 50/60 Hz
ABCN 12
ABCAlarm Energy
NC NO + - S
OUTPUT
Common - 1 or 1/3VAC Input
-
+
-
+
-
+
IA
IB
IC
Phase Loss
Alarm
Output Varies
by Model1
Phase
VA
VB
VC
Neutral
Earth
Control
Power
UL: 90V
L-N
- 600V
L-L
CE: 90V
L-N
- 300VL-N
VOLTAGE INPUTS
CAT III 50/60 Hz
+
–
The red alarm LED lights when any of the 3 phase voltages drop below the
selected threshold: The green Energy LED lights momentarily each time the
Energy output pulse is active.
1Two Output Options Available
+ - S
VARh
VARh
Output
RS-485
Modbus
Shield
+ - S
AMP1B1 -Pulse AMP1Cx-RS-485
Wiring Diagram Symbols
To avoid distortion, use parallelwires for control power and
voltage inputs. The following symbols are used in the wiring
diagrams on the following pages.
Symbol Description
Voltage Disconnect Switch
Fuse (Installer is responsible for ensuring compliance
with local requirements. No fuses are included with
the meter.)
Earth Ground
X2
X1
Current Transducer
Potential Transformer
Protection containing a voltage disconnect switch
with a fuse or disconnect circuit breaker. The
protection device must be rated for the available
short-circuit current at the connection point.
hehe
CAUSION: RISK OF EQUIPMENT DAMAGE
• This product is designed only for use with 1V or 0.33V
current transducers (CTs).
• DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS
PRODUCT.
• Failureto follow these instructions can result in
overheating and permanent equipment damage.
Product Diagram
Alarm Energy
kW
h
12
3
4
.
44
5
CONTROL POWER
0.1A 50/60 Hz
ABCN 12
ABCAlarm Energy
NC NO + - S
OUTPUT
Common - 1 or 1/3VAC Input
-
+
-
+
-
+
IA
IB
IC
Phase Loss
Alarm
Output Varies
by Model1
Phase
VA
VB
VC
Neutral
Earth
Control
Power
UL: 90V
L-N
- 600V
L-L
CE: 90V
L-N
- 300VL-N
VOLTAGE INPUTS
CAT III 50/60 Hz
+
–
The red alarm LED lights when any of the 3 phase voltages drop below the
selected threshold: The green Energy LED lights momentarily each time the
Energy output pulse is active.
1Two Output Options Available
+ - S
VARh
VARh
Output
RS-485
Modbus
Shield
+ - S
AMP1B1 -Pulse AMP1Cx-RS-485
Wiring Diagram Symbols
To avoid distortion, use parallelwires for control power and
voltage inputs. The following symbols are used in the wiring
diagrams on the following pages.
Symbol Description
Voltage Disconnect Switch
Fuse (Installer is responsible for ensuring compliance
with local requirements. No fuses are included with
the meter.)
Earth Ground
X2
X1
Current Transducer
Potential Transformer
Protection containing a voltage disconnect switch
with a fuse or disconnect circuit breaker. The
protection device must be rated for the available
short-circuit current at the connection point.
hehe
CAUSION: RISK OF EQUIPMENT DAMAGE
• This product is designed only for use with 1V or 0.33V
current transducers (CTs).
• DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS
PRODUCT.
• Failureto follow these instructions can result in
overheating and permanent equipment damage.

6AMP1B1, AMP1C2, AMP1C3 Compact Power and Energy Meter
Wiring
WARNING: RISK OF ELECTRIC SHOCK OR PERMANENT
EQUIPMENT DAMAGE
Failure to follow these instructions will result in
death or serious injury.
CT negative terminals are referenced to the meter’s
neutral and may be at elevated voltages.
• Do not contact meter terminals while unit
is connected.
• Do not connect or short other circuits to the
CT terminals.
Figure 1:
1-phase, Line to Neutral, 2-wire system, 1 CT
Figure 2:
1-phase, Line to Line, 2-wire system, 1 CT
USE SYSTEM TYPE 11 (2L)
Figure 3:
1-phase, direct voltage, 2-wire system connection, 2 CT
Figure 4:
3-phase, 3-wire system connection, CT no PT
USE SYSTEM TYPE 31 (3L)
Figure 5:
Figure 6:
Figure 1.
1-phase, Line to Neutral, 2-wire system, 1 CT
USE SYSTEM TYPE 10 (1L + 1n)
NL1
X2
X1 White
Black
A
B
C
N
+
-
+
-
+
-
A
B
C
Figure 2.
1-phase, Line to Line, 2-wire system, 1 CT
USE SYSTEM TYPE 11 (2L)
L1 L2
X2
X1 White
Black
A
B
C
N
+
-
+
-
+
-
A
B
C
Figure 3.
1-phase, direct voltage, 2-wire system connection, 2 CT
USE SYSTEM TYPE 12 (2L + 1n)
L1 L2
X2
X1
X2
X1
A
B
C
N
+
-
+
-
+
-
A
B
C
N
White
Black
White
Black
Figure 4.
3-phase, 3-wire system connection, CT no PT
USE SYSTEM TYPE 31 (3L)
L1 L2 L3
X2
X1
A
B
C
N
A
B
C
X2
X1
X2
X1
+
-
+
-
+
-
White
Black
White
Black
White
Black
Figure 5.
3-phase, 4-wire, wye direct voltage input connection, 3 CT
USE SYSTEM TYPE 40 (3L + 1n)
L1NL2L3
X2
X1
A
B
C
N
A
B
C
X2
X1
X2
X1
+
-
+
-
+
-
White
Black
White
Black
White
Black
Figure 6.
3-phase, 4-wire, wye connection, 3 CT 3 PT
USE SYSTEM TYPE 40 (3L + 1n)
White
Black
White
White
Black
Black
L1NL2L3
X2
X1
A
B
C
N
A
B
C
X2
X1
X2
X1
+
-
+
-
+
-
17892_DET784_AMP1_B1-C3_Install_Instructs_Printerspreads.indd 10-11
Figure 1.
1-phase, Line to Neutral, 2-wire system, 1 CT
USE SYSTEM TYPE 10 (1L + 1n)
NL1
X2
X1 White
Black
A
B
C
N
+
-
+
-
+
-
A
B
C
Figure 2.
1-phase, Line to Line, 2-wire system, 1 CT
USE SYSTEM TYPE 11 (2L)
L1 L2
X2
X1 White
Black
A
B
C
N
+
-
+
-
+
-
A
B
C
Figure 3.
1-phase, direct voltage, 2-wire system connection, 2 CT
USE SYSTEM TYPE 12 (2L + 1n)
L1 L2
X2
X1
X2
X1
A
B
C
N
+
-
+
-
+
-
A
B
C
N
White
Black
White
Black
Figure 4.
3-phase, 3-wire system connection, CT no PT
USE SYSTEM TYPE 31 (3L)
L1 L2 L3
X2
X1
A
B
C
N
A
B
C
X2
X1
X2
X1
+
-
+
-
+
-
White
Black
White
Black
White
Black
Figure 5.
3-phase, 4-wire, wye direct voltage input connection, 3 CT
USE SYSTEM TYPE 40 (3L + 1n)
L1NL2L3
X2
X1
A
B
C
N
A
B
C
X2
X1
X2
X1
+
-
+
-
+
-
White
Black
White
Black
White
Black
Figure 6.
3-phase, 4-wire, wye connection, 3 CT 3 PT
USE SYSTEM TYPE 40 (3L + 1n)
White
Black
White
White
Black
Black
L1NL2L3
X2
X1
A
B
C
N
A
B
C
X2
X1
X2
X1
+
-
+
-
+
-
17892_DET784_AMP1_B1-C3_Install_Instructs_Printerspreads.indd 10-11
Figure 1.
1-phase, Line to Neutral, 2-wire system, 1 CT
USE SYSTEM TYPE 10 (1L + 1n)
NL1
X2
X1 White
Black
A
B
C
N
+
-
+
-
+
-
A
B
C
Figure 2.
1-phase, Line to Line, 2-wire system, 1 CT
USE SYSTEM TYPE 11 (2L)
L1 L2
X2
X1 White
Black
A
B
C
N
+
-
+
-
+
-
A
B
C
Figure 3.
1-phase, direct voltage, 2-wire system connection, 2 CT
USE SYSTEM TYPE 12 (2L + 1n)
L1 L2
X2
X1
X2
X1
A
B
C
N
+
-
+
-
+
-
A
B
C
N
White
Black
White
Black
Figure 4.
3-phase, 3-wire system connection, CT no PT
USE SYSTEM TYPE 31 (3L)
L1 L2 L3
X2
X1
A
B
C
N
A
B
C
X2
X1
X2
X1
+
-
+
-
+
-
White
Black
White
Black
White
Black
Figure 5.
3-phase, 4-wire, wye direct voltage input connection, 3 CT
USE SYSTEM TYPE 40 (3L + 1n)
L1NL2L3
X2
X1
A
B
C
N
A
B
C
X2
X1
X2
X1
+
-
+
-
+
-
White
Black
White
Black
White
Black
Figure 6.
3-phase, 4-wire, wye connection, 3 CT 3 PT
USE SYSTEM TYPE 40 (3L + 1n)
White
Black
White
White
Black
Black
L1NL2L3
X2
X1
A
B
C
N
A
B
C
X2
X1
X2
X1
+
-
+
-
+
-
17892_DET784_AMP1_B1-C3_Install_Instructs_Printerspreads.indd 10-11
Figure 1.
1-phase, Line to Neutral, 2-wire system, 1 CT
USE SYSTEM TYPE 10 (1L + 1n)
NL1
X2
X1 White
Black
A
B
C
N
+
-
+
-
+
-
A
B
C
Figure 2.
1-phase, Line to Line, 2-wire system, 1 CT
USE SYSTEM TYPE 11 (2L)
L1 L2
X2
X1 White
Black
A
B
C
N
+
-
+
-
+
-
A
B
C
Figure 3.
1-phase, direct voltage, 2-wire system connection, 2 CT
USE SYSTEM TYPE 12 (2L + 1n)
L1 L2
X2
X1
X2
X1
A
B
C
N
+
-
+
-
+
-
A
B
C
N
White
Black
White
Black
Figure 4.
3-phase, 3-wire system connection, CT no PT
USE SYSTEM TYPE 31 (3L)
L1 L2 L3
X2
X1
A
B
C
N
A
B
C
X2
X1
X2
X1
+
-
+
-
+
-
White
Black
White
Black
White
Black
Figure 5.
3-phase, 4-wire, wye direct voltage input connection, 3 CT
USE SYSTEM TYPE 40 (3L + 1n)
L1NL2L3
X2
X1
A
B
C
N
A
B
C
X2
X1
X2
X1
+
-
+
-
+
-
White
Black
White
Black
White
Black
Figure 6.
3-phase, 4-wire, wye connection, 3 CT 3 PT
USE SYSTEM TYPE 40 (3L + 1n)
White
Black
White
White
Black
Black
L1NL2L3
X2
X1
A
B
C
N
A
B
C
X2
X1
X2
X1
+
-
+
-
+
-
17892_DET784_AMP1_B1-C3_Install_Instructs_Printerspreads.indd 10-11
Figure 1.
1-phase, Line to Neutral, 2-wire system, 1 CT
USE SYSTEM TYPE 10 (1L + 1n)
NL1
X2
X1 White
Black
A
B
C
N
+
-
+
-
+
-
A
B
C
Figure 2.
1-phase, Line to Line, 2-wire system, 1 CT
USE SYSTEM TYPE 11 (2L)
L1 L2
X2
X1 White
Black
A
B
C
N
+
-
+
-
+
-
A
B
C
Figure 3.
1-phase, direct voltage, 2-wire system connection, 2 CT
USE SYSTEM TYPE 12 (2L + 1n)
L1 L2
X2
X1
X2
X1
A
B
C
N
+
-
+
-
+
-
A
B
C
N
White
Black
White
Black
Figure 4.
3-phase, 3-wire system connection, CT no PT
USE SYSTEM TYPE 31 (3L)
L1 L2 L3
X2
X1
A
B
C
N
A
B
C
X2
X1
X2
X1
+
-
+
-
+
-
White
Black
White
Black
White
Black
Figure 5.
3-phase, 4-wire, wye direct voltage input connection, 3 CT
USE SYSTEM TYPE 40 (3L + 1n)
L1NL2L3
X2
X1
A
B
C
N
A
B
C
X2
X1
X2
X1
+
-
+
-
+
-
White
Black
White
Black
White
Black
Figure 6.
3-phase, 4-wire, wye connection, 3 CT 3 PT
USE SYSTEM TYPE 40 (3L + 1n)
White
Black
White
White
Black
Black
L1NL2L3
X2
X1
A
B
C
N
A
B
C
X2
X1
X2
X1
+
-
+
-
+
-
17892_DET784_AMP1_B1-C3_Install_Instructs_Printerspreads.indd 10-11
Figure 1.
1-phase, Line to Neutral, 2-wire system, 1 CT
USE SYSTEM TYPE 10 (1L + 1n)
NL1
X2
X1 White
Black
A
B
C
N
+
-
+
-
+
-
A
B
C
Figure 2.
1-phase, Line to Line, 2-wire system, 1 CT
USE SYSTEM TYPE 11 (2L)
L1 L2
X2
X1 White
Black
A
B
C
N
+
-
+
-
+
-
A
B
C
Figure 3.
1-phase, direct voltage, 2-wire system connection, 2 CT
USE SYSTEM TYPE 12 (2L + 1n)
L1 L2
X2
X1
X2
X1
A
B
C
N
+
-
+
-
+
-
A
B
C
N
White
Black
White
Black
Figure 4.
3-phase, 3-wire system connection, CT no PT
USE SYSTEM TYPE 31 (3L)
L1 L2 L3
X2
X1
A
B
C
N
A
B
C
X2
X1
X2
X1
+
-
+
-
+
-
White
Black
White
Black
White
Black
Figure 5.
3-phase, 4-wire, wye direct voltage input connection, 3 CT
USE SYSTEM TYPE 40 (3L + 1n)
L1NL2L3
X2
X1
A
B
C
N
A
B
C
X2
X1
X2
X1
+
-
+
-
+
-
White
Black
White
Black
White
Black
Figure 6.
3-phase, 4-wire, wye connection, 3 CT 3 PT
USE SYSTEM TYPE 40 (3L + 1n)
White
Black
White
White
Black
Black
L1NL2L3
X2
X1
A
B
C
N
A
B
C
X2
X1
X2
X1
+
-
+
-
+
-
17892_DET784_AMP1_B1-C3_Install_Instructs_Printerspreads.indd 10-11

7
AMP1B1, AMP1C2, AMP1C3 Compact Power and Energy Meter
Control Power
Direct Connect Control Power, Line to Line
Line to Line from 90 VAC to 600 VAC (UL) (520 VAC for CE). In UL
installations the lines may be floating (such as a delta). If any
lines are tied to an earth (such as a corner grounded delta),
see the Line to Neutral installation limits. In CE compliant
installations, the lines must be neutral (earth) referenced at
less than 300VACL-N.
Direct Connect Control Power, Line to Neutral
Direct Connect Control Power (DC Control Power)
DC Control Power from 125 VDC to 300 VDC (UL and CE max.)
Control Power Transformer (CPT) Connection
The Control Power Transformer may be wired L-N or L-L.
Output to meet meter input requirements.
Fuse Recommendations
Keep the fuses close to the power source (obey local and national
code requirements).
For selecting fuses and circuit breakers, use the following
criteria:
• Select current interrupt capacity based on the installation
category and fault current capability.
• Select over-current protection with a time delay.
• Use a voltage rating sufficient for the input voltage applied.
• Provide overcurrent protection and disconnecting means to
protect the wiring. For DC installations, provide external circuit
protection. Suggested: 0.5A, time delay fuses rated for DC
operation at or above the supply voltage.
• Use the earth connection for electromagnetic compatibility
(EMC), not a protective earth ground.
Control Power
Direct Connect Control Power, Line to Line
L1
12G
L2 L3
Direct Connect Control Power, Line to Neutral
L1NL2L312G
Line to Neutral from 90 VAC to 347 VAC (UL) or 300 VAC (CE).
Direct Connect Control Power (DC Control Power)
12G
DC Control Power from 125 VDC to 300 VDC (UL and CE max.)
Control Power Transformer (CPT) Connection
L1NL2L3
12G
Control Power
Direct Connect Control Power, Line to Line
L1
12G
L2 L3
Direct Connect Control Power, Line to Neutral
L1NL2L312G
Line to Neutral from 90 VAC to 347 VAC (UL) or 300 VAC (CE).
Direct Connect Control Power (DC Control Power)
12G
DC Control Power from 125 VDC to 300 VDC (UL and CE max.)
Control Power Transformer (CPT) Connection
L1NL2L3
12G
Control Power
Direct Connect Control Power, Line to Line
L1
12G
L2 L3
Direct Connect Control Power, Line to Neutral
L1NL2L312G
Line to Neutral from 90 VAC to 347 VAC (UL) or 300 VAC (CE).
Direct Connect Control Power (DC Control Power)
12G
DC Control Power from 125 VDC to 300 VDC (UL and CE max.)
Control Power Transformer (CPT) Connection
L1NL2L3
12G
Control Power
Direct Connect Control Power, Line to Line
L1
12G
L2 L3
Direct Connect Control Power, Line to Neutral
L1NL2L312G
Line to Neutral from 90 VAC to 347 VAC (UL) or 300 VAC (CE).
Direct Connect Control Power (DC Control Power)
12G
DC Control Power from 125 VDC to 300 VDC (UL and CE max.)
Control Power Transformer (CPT) Connection
L1NL2L3
12G

8AMP1B1, AMP1C2, AMP1C3 Compact Power and Energy Meter
Solid State Output
AMP1 Series meters have one normally open (N.O.) KY Form A
output and one normally closed (N.C.) output.3One is dedicated
provides an additional N.O. reactive energy (VARh) contact.
See the Setup section for configuration information.
The solid state pulse outputs are rated for 30 VAC/DC nom.
1 The over-current protective device must be rated for the
short circuit current at the connection point.
2 All pulse outputs and communication circuits are only intended to be connected to
non-hazardous voltage circuits (SELV or Class 2). Do not connect to hazardous voltages.
phase, when the meter is powered, or loss of power when the meter is not. The contacts
are open when the meter is powered and no phase loss alarm conditions are present.
User Interface Menu Abbreviation Defined
The user can set the display mode to IEC or IEEE notation in the
SETUP menu.
~
=
~
=
≤ 100 mA
≤ 100 mA
≤ 100 mA
~
=
Alarm Energy Output
+ – S
LOAD
LOAD
LOAD
Over-Current Protective
Device1
(not supplied)
Power Source2
3-30 VDC
6-30 VAC
(AMP1B1 and AMP1Cx)
(AMP1B1 only) Power Source
2
3-30 VDC
6-30 VAC
Power Source2
3-30 VDC
6-30 VAC
Main Menu
IEC IEEE Description
DDDemand
MAX MMaximum Demand
PPresent Real Power
QVAR Present Reactive Power
SVA Present Apparent Power
AAAmps
UAB, UBC, UAC VAB, VBC, VAC Voltage Line to Line
VVLN Voltage Line to Neutral
PF PF Power Factor
UVLL Voltage Line to Line
HZ HZ Frequency
KSh KVAh Accumulated Apparent Energy
KQh KVARh Accumulated Reactive Energy
KPh Accumulated Real Energy
PLOSS PLOSS Phase Loss
Low Power Factor Error
F ERR F ERR Frequency Error
I OVR I OVR Over Current
V OVR V OVR Over Voltage
PULSE PULSE
(configuration error)
_PHASE _PHASE
active phases
ALERT ALERT Diagnostic Alert Status
INFO INFO Unit Information
MODEL MODEL Model Number
OS OS Operating System
RS RS Reset System
SN SN Serial Number
RESET RESET Reset Data
Enter Reset or Setup Password
ENERG ENERG Reset Energy Accumulators
DEMND DEMND Reset Demand Maximums

9
AMP1B1, AMP1C2, AMP1C3 Compact Power and Energy Meter
User Interface for Data Configuration
_PHAS
APHAS
BPHAS
CPHAS
3 A 3 VLL 3 VLN 3 KW
A A A VAB A KW
1, 2, or 3 Phase
Summary Data
Phase A:
All Systems
Phase B:
2 & 3 Phase
Systems Only
Phase C:
3 Phase
Systems Only
A VLN
Volts Line-Line (U)
(Average of Active
Phases)
Amps (A)
(Average of
Active Phases)
Volts Line-Neutral (V)
(Average of Active
Phases)
Total Real
Power (P)
Power Factor
(Average of
Active Phases)
3 KVA
Total Apparent
Power (S)
B A B VBC B KWB VLN
C A C VAC C KWC VLN
A KVA
B KVA
C KVA
A PF
3 PF
B PF
C PF
3KVAR
Total Reactive
Power (Q)
AKVAR
BKVAR
CKVAR
KVARh KVAh
Accumulated
Reactive Energy
(Qh)
Accumulated
Apparent Energy
(Sh)
DEMND D KW
Present
Real Power
Demand (P)
M KW MKVAR M KVA
Maximum
Apparent Power
Demand (S)
Maximum
Reactive Power
Demand (Q)
Maximum
Real Power
Demand (P)
DKVAR
Present
Reactive Power
Demand (Q)
D KVA
Present
Apparent Power
Demand (S)
DEMND
Demand
>>> Scroll When Idle >>>
To:
SETUP
APHAS
BPHAS
CPHAS
A KWh
3 KWh
B KWh
C KWh
_PHAS
HZ
Frequency
Accumulated
Real Energy
ENRGY
To:
ALERT
Energy
Accumulators
and Counters
ENRGY
PULS1
Pulse Counter 1
(Wh if present)
PULS2
Pulse Counter 2
(VARh if present)
KWh
Accumulated
Real Energy
(Ph)

10 AMP1B1, AMP1C2, AMP1C3 Compact Power and Energy Meter
Alert/Reset Information
PASWD – Enter the Reset Password
(configured in the setup menu).
ENERG – Reset all Energy
DEMND – Reset all Maximum
COUNT – Reset the pulse counters.
Alert/Reset Information
SETUP
ALERT
RESET
Back
Display “nOnE” if no alerts
To Setup
Setup
Meter
Reset
Data
Phase Loss
A B C
Low Power Factor
A B C
Frequency Out
of Range
A
Current
Out of Range
Voltage
Out of Range
A B C A B C
INFO MODEL OS SNRS
Serial
Number
Reset
System
Operating
System
ALERT
INFO
PLOSS
--------
A b C
LOWPF
--------
A b C
F ERR
--------
A
I OVR
--------
A b C
V OVR
--------
A b C
PASWD
--------
00000
PASWD
--------
00000
Model
Number
Energy Pulse Output:
Error = Overrun Error
ConF = Con guration Error
PULSE
--------
Error
ENERG
--------
rES
Reset Energy
Accumulators to 0
Unit
Information
Alert Status
(check if
Wrench on
LCD)
RESET
Enter Reset
Password
Enter Setup
Password
To: ENRGY
To: DEMND
COUNT
--------
rES
Reset Pulse
Counters to 0
DEMND
--------
rES
Reset Demand
Maximums to Present

11
AMP1B1, AMP1C2, AMP1C3 Compact Power and Energy Meter
User Interface for Setup
Set Communications Parameters:
ADDR - Modbus Address:
- selects the digit to the left.
BAUD - Baud Rate
PAR - Parity: Odd, Even, None
Set Current Transducer:
CT V
CT SZ - CT Size: in Amps. Maximum is 32000 Amps.
Set System Configuration:
SYSTM
Set Potential Transfomer Ratio:
RATIO – Potential transformer step down is RATIO:1. Default is 1:1
(No PT installed). See Install for wiring diagrams. This value must
be set before the System Voltage (if used).
Set System Voltage:
V LL – The nominal Line to Line Voltage for the system. This is
used by the meter to calculate the theoretical maximum system
power, and as the reference voltage for setting the Phase Loss
will reject settings that are not within the meter’s operating
range when divided by the PT ratio.
System Power:
MX KW – The theoretical Maximum System Power is calculated by
the meter from the System Voltage, CT size, and System Type.
Power Factor is assumed to be unity. The value of System Power
is used to determine which combinations of pul se weight and
duration are valid and will keep up with the maximum power the
meter will see. This value is read only.
†
changes made have been accepted.
System CTs Description
3L-1n
Single Split Phase: A & B with Neutral
Single Phase: A to Neutral
User InterfaceforSetup
Next
Next
From:
SETUP > PASWD
ADDR
--------
001
BAUD
--------
38400
19200
9600
4800
2400
1200
PAR
--------
nOnE
EvEn
Odd
System
Type
Current
Transformer
S SYS
Next
S CT
CT V
--------
1.0
.33
CT SZ
--------
200
SYSTM
--------
3L-1n
3L
2L-1n
2L
1L-1n
Back To SETUP
Back
Back
Back S COM
To Setup p. 2 “SPLOS”
Next
S PT
Potential
Transformer
RATIO
--------
001
.00
Back
S V
Back
System
System
Voltage Next
V LL
--------
00480
S PWR
Back
Voltage
MX KW
--------
103.92
Next
To Setup p. 2 “SPASS”
RS-485
Output

12 AMP1B1, AMP1C2, AMP1C3 Compact Power and Energy Meter
Set Phase Loss:
VOLTS - Phase Loss Voltage: The fraction of the system voltage
below which Phase Loss Alarm is on. For system types with
neutral, the Line to Neutral voltage is also calculated and tested.
If the System Voltage is 600 and the fraction is set to 0.10, then
the Phase Loss threshold will be 60 volts.
IMBAL - Phase Loss Imbalance : The fractional difference in Line
to Line voltages abov e which Phase Loss Alarm is on. For system
types with neutral, the Line to Neutral voltages are also tested.
Set Pulse:
The System Type , CT size, PT Ratio, and System Voltage must all
be configured before setting the Pulse Energy. If any of these
parameters are changed, the meter will hunt for a new Pulse
Duration, but will not change the Pulse Energy. If it cannot find a
ALARM -> PULSE screen, and enable Energy pulse output
configuration error bit in the Modbus Diagnostic Alert Bitmap
(if equipped).
Wh/P - Set Pulse Energy
not allow the selection if it cannot find a pulse duration that will
allow the pulse output to keep up with Theoretical Maximum
energy, the meter will jump to the first value where it can and a
valid solution.
mS/P – Minimum Pulse Duration Time: This read only value is set
by the meter to the slowest duration (in mS per closure) that will
keep up with the Theoretical Maximum System Power. The open
time is greater than or equal to the closure time. The maximum
Pulses Per Second (PPS) is shown in yellow.
Set Demand Interval:
INTRV - The number of Sub-Intervals (1 to 6) in a Demand Interval.
Default is 1 (block demand).
SEC - Sub-Interval length in seconds. Default is 900 (15 minutes).
Set to 0 for external sync-to-comms (Modbus units only).
Set Display Units
IEEE
IEC - U V P Q S Units.
Set Passwords:
SETUP - The Password to enter the SETUP menu.
RESET - The Password to enter the RESET menu.
†
changes made have been accepted.
Next
RESET
--------
00000
SPASS
Setup
Passwords
SETUP
--------
00000
Back
Next
SDMND
INTRV
--------
6
5
4
3
2
1
Demand
SEC
--------
00900
Back
Next
S DIS
Display
Units
UNITS
--------
IEEE
IEC
Back
To Setup p. 1 “S PWR”
Max
PPS
--------
1
2
5
10
20
50
Pulse
Output
Next
mS/P
--------
500
250
100
50
25
10
SPULS
Back
Wh/P
--------
10000
1000
100
10
SPLOS
Back
IMBAL
--------
0.25
Next
VOLTS
--------
0.10
Phase
Loss
Back To SETUP
BDS
–
+
S
Shield Wire
Display Screen Diagram
Tx
Rx
ERR
Screen Name or Units
Diagnostic
Alert
Logo
Numeric Data
Alive Indicator
Transmit Data
RS-485 Equipped
Units Only
Receive Data
Error
Receive Data
00.0
.0
.0
00 0 0 0
00
.
0
.
0
.
0
(Right) Next(Left) Back
(Up) Select
(Down) Select
+
–

13
AMP1B1, AMP1C2, AMP1C3 Compact Power and Energy Meter
RS-485 Communications (AMP1Cx Only)
Daisy-chaining Devices to the Power Meter
connected in a daisy chain with up to 63 2-wire devices.
NOTES:
• The terminal’s voltage and current ratings are compliant with
•
•
•
of the bus (not included).
• Shield is not internally connected to Earth Ground.
•
(only at one point).
For all terminals
•
ft·lb (0.5-0.6 N·m).
• 2) wire.
Display Screen Diagram
LCD Screen
Buttons
Next
RESET
--------
00000
SPASS
Setup
Passwords
SETUP
--------
00000
Back
Next
SDMND
INTRV
--------
6
5
4
3
2
1
Demand
SEC
--------
00900
Back
Next
S DIS
Display
Units
UNITS
--------
IEEE
IEC
Back
To Setup p. 1 “S PWR”
Max
PPS
--------
1
2
5
10
20
50
Pulse
Output
Next
mS/P
--------
500
250
100
50
25
10
SPULS
Back
Wh/P
--------
10000
1000
100
10
SPLOS
Back
IMBAL
--------
0.25
Next
VOLTS
--------
0.10
Phase
Loss
Back To SETUP
BDS
–
+
S
Shield Wire
Display Screen Diagram
Tx
Rx
ERR
Screen Name or Units
Diagnostic
Alert
Logo
Numeric Data
Alive Indicator
Transmit Data
RS-485 Equipped
Units Only
Receive Data
Error
Receive Data
00.0
.0
.0
00 0 0 0
00
.
0
.
0
.
0
(Right) Next(Left) Back
(Up) Select
(Down) Select
+
–
Next
RESET
--------
00000
SPASS
Setup
Passwords
SETUP
--------
00000
Back
Next
SDMND
INTRV
--------
6
5
4
3
2
1
Demand
SEC
--------
00900
Back
Next
S DIS
Display
Units
UNITS
--------
IEEE
IEC
Back
To Setup p. 1 “S PWR”
Max
PPS
--------
1
2
5
10
20
50
Pulse
Output
Next
mS/P
--------
500
250
100
50
25
10
SPULS
Back
Wh/P
--------
10000
1000
100
10
SPLOS
Back
IMBAL
--------
0.25
Next
VOLTS
--------
0.10
Phase
Loss
Back To SETUP
BDS
–
+
S
Shield Wire
Display Screen Diagram
Tx
Rx
ERR
Screen Name or Units
Diagnostic
Alert
Logo
Numeric Data
Alive Indicator
Transmit Data
RS-485 Equipped
Units Only
Receive Data
Error
Receive Data
00.0
.0
.0
00 0 0 0
00
.
0
.
0
.
0
(Right) Next(Left) Back
(Up) Select
(Down) Select
+
–
(0.5 to 0.6 N-m)
Use 14 to 24 gauge wire
Red
Black
Gray
Next
RESET
--------
00000
SPASS
Setup
Passwords
SETUP
--------
00000
Back
Next
SDMND
INTRV
--------
6
5
4
3
2
1
Demand
SEC
--------
00900
Back
Next
S DIS
Display
Units
UNITS
--------
IEEE
IEC
Back
To Setup p. 1 “S PWR”
Max
PPS
--------
1
2
5
10
20
50
Pulse
Output
Next
mS/P
--------
500
250
100
50
25
10
SPULS
Back
Wh/P
--------
10000
1000
100
10
SPLOS
Back
IMBAL
--------
0.25
Next
VOLTS
--------
0.10
Phase
Loss
Back To SETUP
BDS
–
+
S
Shield Wire
Display Screen Diagram
Tx
Rx
ERR
Screen Name or Units
Diagnostic
Alert
Logo
Numeric Data
Alive Indicator
Transmit Data
RS-485 Equipped
Units Only
Receive Data
Error
Receive Data
00.0
.0
.0
00 0 0 0
00
.
0
.
0
.
0
(Right) Next(Left) Back
(Up) Select
(Down) Select
+
–
Next
RESET
--------
00000
SPASS
Setup
Passwords
SETUP
--------
00000
Back
Next
SDMND
INTRV
--------
6
5
4
3
2
1
Demand
SEC
--------
00900
Back
Next
S DIS
Display
Units
UNITS
--------
IEEE
IEC
Back
To Setup p. 1 “S PWR”
Max
PPS
--------
1
2
5
10
20
50
Pulse
Output
Next
mS/P
--------
500
250
100
50
25
10
SPULS
Back
Wh/P
--------
10000
1000
100
10
SPLOS
Back
IMBAL
--------
0.25
Next
VOLTS
--------
0.10
Phase
Loss
Back To SETUP
BDS
–
+
S
Shield Wire
Display Screen Diagram
Tx
Rx
ERR
Screen Name or Units
Diagnostic
Alert
Logo
Numeric Data
Alive Indicator
Transmit Data
RS-485 Equipped
Units Only
Receive Data
Error
Receive Data
00.0
.0
.0
00 0 0 0
00
.
0
.
0
.
0
(Right) Next(Left) Back
(Up) Select
(Down) Select
+
–

14 AMP1B1, AMP1C2, AMP1C3 Compact Power and Energy Meter
9. Press to go to the SV(Set System Voltage) screen.
a. Press to go to the VLL (or VLN if system is 1L-1N) screen
and through the digits. Use the or buttons to select the
Line to Line System Voltage.
b. Press to go back to the SVscreen.
10. Use the button to exit the setup screen and then SETUP.
11. Check that the wrench is not displayed on the LCD.
a. If the wrench is displayed, use the or buttons to find the
ALERT screen.
b. Press to go through the screens to see which alert is on.
For full setup instructions, see the configuration instructions.
Quick Setup
These instructions assume the meter is set to factory defaults. If
it has been previously configured, all optional values should be
checked.
1. Press or repeatedly until SETUP screen appears.
2. Press to get to the PASWD screen.
3. Press to move through the digits. Use the or buttons to
enter your password (the default is 00000).
Exit the screen to the right.
is S COM (set communications).
a. Press to go to the ADDR screen and through the address
digits. Use or to select the Modbus address.
b. Press to accept the value and go to the BAUD screen.
Use or to select the baud rate.
c. Press to go to the PAR screen. Use or to select
the parity.
d. Press to go back to the S COM screen.
6. Press to go to the S CT (Set Current Transducer) Setup
first screen.
a. Press to go to the CT V screen. Use or to select the
voltage mode Current Transducer output voltage.
b. Press to go to the CT SZ screen and through the digits.
Use or to select the CT size in amps.
c. Press to accept the value and go back to the S CT screen.
7. Press to go to the S SYS (Set System) Setup screen.
a. Press to go to the SYSTM screen. Use or to select the
System type (see wiring diagrams).
b. Press to go back to the S SYS screen.
S PT (Set Potential Transformer)
screen. If PTs are not used, then skip this step.
a. Press to go to the RATIO screen and through the digits.
Use the or buttons to select the Potential Transformer
step down ratio.
b. Press to go back to the S PT screen.

15
AMP1B1, AMP1C2, AMP1C3 Compact Power and Energy Meter
Data Logging
The AMP1C3 includes a data logging feature that records 10 meter
parameters, each in its own buffer.
Configuration
to the storage buffer is triggered by the subinterval timer. The
default subinterval is 15 minutes (at a 15 minute interval setting,
the buffers hold 60 days of data). An external timer can be used
over Modbus by setting this register to 0.
Use register 159 to turn on data logging and select either Single
Shot or Continuous mode. (default is data logging on, Continuous
mode). In Single Shot mode, the meter records data until the
new readings. Data for this time period is kept, but newer energy
information is lost. In Continuous mode, the meter continues to
record energy data as long as the meter is operating. The buffer
can only hold 5760 entries at one time, however, so when the
number of records exceeds 5760, the oldest entry is deleted to
make room for the newest.
Each buffer is user- configurable with the Modbus address of the
16-bit data output to be stored. 32-bit data, such as floating
point data or 32-bit integer energy accumulators, require two
buffers. However, the lower 16 bits of an integer energy
accumulator can be stored in a single buffer (optional).
the buffer is reset at any point, all entries in the buffers are
invalid data is overwritten as the meter fills the buffer with new
data entries.
Reading Data
register value is set to 0, the meter is in data logging mode.
Changing this value from 0 to (1 through 10) switches the meter
to reading mode and selects a buffer to read. Data from the
Read/Write Collision
If the demand sub-interval timeout occurs while the user is
until the next demand subinterval. At that time, both the saved
data from the previous cycle and the new data will be written to
the log, whether the page register has been set back to 0 or not.
Error bits in the Log Status Register (160) track these conditions.
Subsequent log writes will proceed normally. Provided the log
read is concluded in less time than the demand sub- interval, this
mechanism handles the occasional collision and prevents the user
from reading data as the buffer is being updated.
The Log Status Register has additional error flag bits that
indicate whether logging has been reset or interrupted (power
cycle, etc.) during the previous demand sub- interval, and
whether the Real-Time Clock has been changed (re-initialized
to default date/time due to a power-cycle or modified via
Modbus commands).
Standard Modbus Default Settings
Setting Value Modbus
Register
Setup Password –
Reset Password –
System Type
CT Primary Ratio
(if CTs are not included)
CT Secondary Ratio
PT Ratio
System Voltage
Max. Theoretical Power
(Analog Output: full scale
Display Mode
Phase Loss
Phase Imbalance
Pulse Energy
Demand: number of
sub-intervals per interval
Demand: sub-interval length
Modbus Address –
Modbus Baud Rate –
Modbus Parity None –
Log Read Page
Logging Configuration
Register

16 AMP1B1, AMP1C2, AMP1C3 Compact Power and Energy Meter
Modbus Point Map
The AMP1C2 Full Data Set (FDS) features data outputs such as
demand calculations, per phase VA and VAR, and VAh VARh
accumulators. The AMP1C3 Data Logging model adds
AMP1 models are protected by a user configurable passcode. The
meter supports variable CTs and PTs, allowing a much wider
range of operation from 90V x 5A up to 32000V x 32000A. To
promote this, the meter permits variable scaling of the 16-bit
integer registers via the scale registers. The 32-bit floating point
registers do not need to be scaled.
Integer registers begin at 001 (0x001). Floats at 257 (0x101).
in Integer Registers, 0x7FC00000 in Floating Point Registers).
Supported Modbus Commands
Note: ID String information varies from model to model. Text
shown here is an example.
Legend
The following table lists the addresses assigned to each data
point. For floating point format variables, each data point
appears twice because two 16-bit addresses are required to hold
a 32-bit float value.
R/W
write only to integer format.
NV Value is stored in non-volatile memory. The value will still be
available if the meter experiences a power loss and reset.
Format
UInt
SInt
ULong
in lowest-numbered / first listed register
Float
Units Lists the physical units that a register holds.
Scale
Factor
Some Integer values must be multiplied by a constant scale
factor (typically a fraction), to be read correctly. This is done
to allow integer numbers to represent fractional numbers.
Range Defines the limit of the values that a register can contain.
Command Description
Read Holding Registers
Read Input Registers
Preset Single Register
Preset Multiple Registers
Report ID
Return string:
Read Device Identification, BASIC implementation
Object values:
(reformatted version of the Modbus register

17
AMP1B1, AMP1C2, AMP1C3 Compact Power and Energy Meter
AMP1C2 FDS
AMP1C3 Log
AMP1xx REG.
R/W NV Format Units Scale Range Description
•• RNV ULong E Real Energy Consumption (MSR) Clear via reset register
•• Real Energy Consumption (LSR)
•• R – UInt
•• R – UInt kVAR
•• R – UInt kVA
•• R – UInt Ratio
•• R – UInt Volt V
•• R – UInt Volt V
•• R – UInt Amp I
•• R – UInt Real Power, Phase A
•• R – UInt Real Power, Phase B
•• R – UInt Real Power, Phase C
•• R – UInt Ratio Power Factor, Phase A
•• R – UInt Ratio Power Factor, Phase B
•• R – UInt Ratio Power Factor, Phase C
•• R – UInt Volt V Voltage, Phase A-B
•• R – UInt Volt V Voltage, Phase B-C
•• R – UInt Volt V Voltage, Phase A-C
•• R – UInt Volt V Voltage, Phase A-N
•• R – UInt Volt V Voltage, Phase B-N
•• R – UInt Volt V Voltage, Phase C-N
•• R – UInt Amp I Current, Instantaneous, Phase A
•• R – UInt Amp I Current, Instantaneous, Phase B
•• R – UInt Amp I Current, Instantaneous, Phase C
•• R – UInt – – –
•• R – UInt Hz Frequency (derived from Phase A)
•• RNV ULong kVAh E Apparent Energy Consumption (MSR) Clear via reset register
•• Apparent Energy Consumption (LSR)
•• RNV ULong kVARh E Reactive Energy Consumption (MSR) Clear via reset register
•• Reactive Energy Consumption (LSR)
•• R – UInt kVA Apparent Power, Phase A
•• R – UInt kVA Apparent Power, Phase B
•• R – UInt kVA Apparent Power, Phase C
•• R – UInt kVAR Reactive Power, Phase A
•• R – UInt kVAR Reactive Power, Phase B
•• R – UInt kVAR Reactive Power, Phase C
•• R – UInt Total Real Power Present Demand
•• R – UInt kVAR Total Reactive Power Present Demand
•• R – UInt kVA Total Apparent Power Present Demand
•• RNV UInt Total Real Power Max Demand
• • RNV UInt kVAR Total Reactive Power Max Demand
•• RNV UInt kVA Total Apparent Power Max Demand

18 AMP1B1, AMP1C2, AMP1C3 Compact Power and Energy Meter
AMP1C2 FDS
AMP1C3 Log
AMP1xx REG.
R/W NV Format Units Scale Range Description
••
RNV ULong –– MSR Contact Closure Counters.
Valid for both Pulse inputs
counts are shown in (). See
Inputs are user defined.
••LSR
••
RNV ULong ––
MSR
••LSR
••
RNV ULong E Real Energy Consumption
Phase A
MSR
Clear via reset register
••LSR
••
RNV ULong E Real Energy Consumption
Phase B
MSR
••LSR
••
RNV ULong E Real Energy Consumption
Phase C
MSR
••LSR
Configuration
•• –UInt ––N/A
Command Register:
•• NV UInt – –
System Type
(See Manual. Note: only
the
•• NV UInt Amps – CT Ratio – Primary
Current Inputs
•• NV UInt ––
may not be user configurable)
•• NV UInt –
is with no PT attached. Set this value before setting the system
voltage (below).
•• NV UInt –
line to neutral. The meter uses this value to calculate the full
scale power for the analog outputs and pulse configuration
meter will refuse voltages that are outside the range of
•• RNV UInt
Theoretical Maximum System Power:
This read-only value is the theoretical max. power the meter can expect to see
the CT size, system type, or system voltage. This integer value has the same
•• R – UInt –––
•• NV UInt ––
•• R – SInt –
Scale Factor I (Current) Scale Factors
Note: These registers contain
a signed integer, which scales
the corresponding integer
registers. Floating point
registers are not scaled.
Scaling is recalculated when
the meter configuration
is changed.
•• R – SInt – Scale Factor V (Voltage)
•• R – SInt –
•• R – SInt – Scale Factor E (Energy)

19
AMP1B1, AMP1C2, AMP1C3 Compact Power and Energy Meter
AMP1C2 FDS
AMP1C3 Log
AMP1xx REG.
R/W NV Format Units Scale Range Description
•• NV UInt –
Phase Loss Voltage Threshold in percent of system voltage
be true.
Phase Loss Output
Note: The phases tested
are determined by the
System Type.
•• NV UInt –
just the line to neutral voltage are compared.
•• NV UInt –
Output Contact Closure. If the meter cannot find a pulse
duration that will keep up with the max. system power
value.
contact can keep up with
a maximum power
pulse weight ÷ contact
closure duration (in mses)
•• RNV UInt ms –
Pulse Contact Closure Duration in msec. Read-only. Set to
the slowest duration that will keep up with the theoretical
closure time, so the max. pulse rate (pulses per sec) is the
inverse of double the pulse time.
•• R – UInt – – –
determine frequency.
to mis-wiring of phases
•• RNV UInt – – Count of Energy Accumulator resets
•• R – UInt – – –

20 AMP1B1, AMP1C2, AMP1C3 Compact Power and Energy Meter
AMP1C2 FDS
AMP1C3 Log
AMP1xx REG.
R/W NV Format Units Scale Range Description
•• NV UInt – –
Number of Sub-Intervals per Demand Interval. Sets the
number of subintervals that make a single demand
Demand
Calculation
•• NV UInt Seconds –
Sub-Interval Length in seconds. For sync-to-comms, set
logging interval.
•• –UInt – –
•• NV UInt – – Power Up Counter.
•• RNV UInt – –
open) energy contact and NC (normally closed) (Normally Open - Form A or Normally
is Normally Closed (contacts are closed when the meter is not powered), closure
or loss of power when the meter is not. The contacts are open when the meter is
powered and no phase alarm conditions are present.
•• R – UInt – – –
Logging Configuration and Status
– • NV UInt Day /
Month – See Bytes Most Significant Byte (MSB) Least Significant Byte (LSB)
Date / Time Clock.
Following a power cycle,
resets to:
– • NV UInt Hour /
Year – See Bytes
– • NV UInt Seconds /
Minutes – See Bytes
– • NV UInt – –
Logging Read Page Register. Selects which of the Register Logs to read (see registers
resumes. The meter will buffer one set of log entries while in reading mode if a
WARNING: This buffered data will be written to the log and logging will resume on the
following sub-interval timeout whether the page register has been cleared or not,
resulting in the appearance of data moving in the buffer during reads. To avoid this,
– • NV UInt – – –
Logging Configuration Register (Bit Mapped):
– • RNV UInt – – –
Logging Status Register (Bit Mapped):
the user was reading the log (Logging Page Register has been set to
the next sub-interval and then writes the saved data to the log as well as the
the user is reading the log (Logging Page Register is set to something other
write, first of the values saved from the previous cycle, and then the present
values. If the read condition is not removed the meter continues to write the
sub-interval.
configuration change, etc.) during the previous demand sub-interval.
demand sub-interval.
be re-initialized.
This manual suits for next models
2
Table of contents
Other GE Measuring Instrument manuals

GE
GE DigitalFlow GF868 Owner's manual

GE
GE CTF878 Troubleshooting guide

GE
GE RHM 30 User manual

GE
GE PanaFlow HT User manual

GE
GE RHM 40 User manual

GE
GE Dresser Series B3 Owner's manual

GE
GE Bently Nevada 3300/16 User manual

GE
GE Precision 500D User manual

GE
GE MAC 800 User manual

GE
GE Druck DPI 705 User manual
Popular Measuring Instrument manuals by other brands

Dwyer Instruments
Dwyer Instruments WDPM-002 Specifications-installation and operating instructions

Hach
Hach WDMP sc user manual

Autometers Systems
Autometers Systems HORIZON HT-35 manual

MRC
MRC CD-4309 Operation manual

Calculated Industries
Calculated Industries Laser Dimension Master 165-BT manual

Projecta
Projecta BM320 instruction manual