gefran 1200 User manual

1200 / 1300
TEMPERATURE CONTROLLER
Software Version 4.0x
code 81801G / Edition 08 -07/2011 ENGLISH
INSTRUCTIONS FOR USE
AND WARNINGS
GENERAL INDEX
page
Graphic symbol used 2
1 Preliminary instructions 2
General description 2
Basic version controller 2
Options 2
Operator interface 2
Electrical interface 3
Preliminary warnings 3
2 Installation and connection 4
Electrical power supply 4
Notes concerning electrical safety and
Electromagnetic compatibility 4
Advice for correct installation
for EMC 4
Instrument power supply 5
Inputs and outputs connection 6
Dimensions and cut-out 6
Installation with panel mounting 6
Warnings and instructions for
mounting to the panel 6
Nominal ambient conditions 6
Electrical connections 7
Example of connection with TC input
Electric heating with power solid state relay
and water cooling with solenoid valve 9
3 Functions 10
Operator interface 10
General operating notes 11
Navigating through the controller menu 12
4 Configuration and programming 13
EASY
Configuration/Programming 14
EXTENDED
Configuration/Programming 19
page
Application notes 30
HB Alarm 30
HOLD function 30
Alarms 30
Control actions 30
Manual tuning 31
Multiset function,Set gradient 31
Twin setpoint application (Ramp +
Hold + Time expiration alarm) 31
Software ON/OFF switching function 32
Self-Tuning 32
Auto-Tuning 33
Controls 33
Heating/Cooling control with
Relative gain 33
5 Technical specifications 34
6 Maintenance 35
Cleaning the controller 35
Repairs 35
Checking the jumpers 35
Troubleshooting Guide 35
7 Technical-Commercial information 36
Order code 36
Accessories
Current transformer 37
PTC 37
RS232/TTL interface for Gefran
Instrument configuration 37
Appendix 38
The contents of each section are summarized
immediately following the section heading
1
81801G_MHW_1200-1300_07-2011_ENG

Graphic symbols used
To distinguish between the type and importance of the information provided in these instructions for use, graphic
symbols have been used as a reference to make interpreting the information clearer.
Indicates the contents of the various manual sections,
the general warnings, notes, and other points to
which the reader’s attention should be drawn.
Indicates a particularly delicate situation that
could affect the safety and correct working ope-
ration of the controller, or a rule that must be
strictly observed to avoid dangerous situations
Indicates a condition of risk for the safety of the
user, due to the presence of dangerous voltages
at the points shown
Indicates a suggestion based on the experien-
ce of the GEFRAN Technical Staff, which could
prove especially useful under given cir-
cumstances
Indicates a reference to Detailed Technical
Documents available on the GEFRAN web
site www.gefran.com
In the programming and configuration flows
for the controller, indicates the typical
parameters of the “Easy” configuration,
i.e. the minimum controller configuration
optimized for the basic version that uses
just 2 outputs (OUT1 , OUT2)
In the programming and configuration flows
for the controller, indicates all the parame-
ters that can be set in the “Extended” con-
figuration.
AL.1
AL.2
1 • PRELIMINARY INSTRUCTIONS
This section contains information and warnings of a
general nature which should be read befo-
re proceeding with controller installation,
configuration and use.
General Description
GEFRAN series 1200 / 1300 digital controllers
have been designed for temperature control in
any applications involving heating or cooling
processes. They represent an exclusive combination
of performance, reliability and applicational
flexibility. In particular, this new line of Gefran tempera-
ture controllers is the ideal solution for application
in sectors where performance and service continuity are
important, including:
• extrusionlines
• injectionmoldingforplasticmaterials
• thermoformers
• pressesforrubber
• wrappingandpackagingmachines
• processingplantforthefoodindustry
• coolingswitchboards
• climaticchambersandtestbenches
• ovens
• paintplants
• etc.
The 1200/1300 series temperature controllers are
made on an extremely versatile hardware and software
platform, that allows the most suitable I/O composition
for the plant to be chosen from a series of options, up to
a maximum of:
• 4outputs
• 3inputs(2ofwhichareauxiliary)
• 1RS485interface.
Basic Version Controller
• 1 universal input for TC, 2/3 wire RTD, PTC, NTC,
and linear thermocouples, supplied with current and
voltage with accuracy better than 0.2% f.s.
• 2 standard outputs: one relay and the other
relay/logic/triac (depending on request)
• functions heat/cool, self tuning, autotuning, soft start
• alarm for interrupted load or short-circuited probe
• serviceserial line for configuration by PC (Winstrum)
Options
• 3rd output retransmission relay/
logic/continuous/analogue
• 4th output relay/logic
• 2 auxiliary digital inputs with configurable function,
or 1 auxiliary digital input + current transformer input
to control the load current
• serialoptoisolatedRS485interface
281801G_MHW_1200-1300_07-2011_ENG

Operator Interface
All the operator interface devices are concentrated
on the controller faceplate, suitably protected by a mem-
brane in Lexan that guarantees IP65 level protection.
• 4buttonstobeusedformanualregulation/
configuration/selection
• 2greenfour-digitdisplays
(Process Variable and Set point Variable)
• 4redLEDsforstatusindicationofsamenumberof
relay/logic outputs
• 3LEDswithprogramfunctiontoindicatecontroller
operating mode.
Electrical Interface
All connection terminals (power supply, inputs, outputs,
options) are grouped together on the back of the
controller.
For technical specifications and performance details
refer to Section 5 “Technical Specifications”.
Preliminary Warnings
The following preliminary warnings should
be read before installing and using the series
1200/1300 controller . This will allow the control-
ler to be put into service more quickly and will
avoid certain problems which may mistakenly
be interpreted as malfunctions or limitations of
the controller.
• Immediatelyafterunpackingthecontroller,makea
note of the order code and the other identification
data given on the label affixed to the outside of the
container and copy them to the table below.
These details must always be kept close at hand and
referred to the personnel involved in the event of
help from Gefran Customer Service Assistance.
• Checkalsothatthecontrolleriscompleteandhas
not been damaged at all during transit, and that the
package contains not only the controller and these
Instructions for Use, but also the two brackets for
fixing to the panel and the dust protection seal - see:
Installation with Panel Fixing in Section 2.
Any inconsistencies, omissions or evident signs of
damage should be reported immediately to your
Gefran sales agent.
• Checkthattheordercodecorrespondswiththe
configuration requested for the application the
controller is needed for, referring to Section 7:
“Technical - Commercial Information”.
• No.andTypeofInputs/Outputsavailable
• Presenceofthenecessaryoptionsand
accessories
• Mainsvoltagesupply
Example: 1200 – RT – RR – 00 – 0 – 1
Model 1200 controller
Output 1 - Relay; Output 2 - Triac (1A)
Output 3 - Relay; Output 4 - Relay
No Digital Input
No Digital Communication
Mains Voltage 100...240Vac/dc
• Beforeinstallingtheseries1200/1300controlleron
the control panel of the machine or host system,
refer to the paragraph “Dimensions and Cut-out” in
Section 2 “Installation and Connection”.
• WhereconfigurationbyPCisprovidedfor,make
sure the interface RS232 cable is available and the
CD- ROM containing the WINSTRUM software.
For the order code refer to Section 7 “Technical -
Commercial Information”.
Users and/or system integrators who wish
to know more about the concepts of serial com-
munication between standard PC and/or
Gefran Industrial PC and Gefran Programmable
Instruments (including the series 1200/1300
controller), can access the various technical
reference Documents in Adobe Acrobat format
available in the Download section of the Gefran
Web Site www.gefran.com including:
•SerialCommunication
•MODBusProtocol
In the same Download section of the Gefran
Web Site www.gefran.com the 1200/1300
Temperature Controller reference manual is
available in Adobe Acrobat format, containing a
detailed description of all the adjustable
parameters and procedures for the Controller.
In the event of presumed instrument malfunction,
before contacting Gefran Technical Service
Assistance, refer to the Troubleshooting Guide
given in Section 6 “Maintenance”, and if
necessary refer to the F.A.Q. Section (Frequently
Asked Questions) on the Gefran Web Site
www.gefran.com
SN: ......................... (Serial no.)
CODE: ......................... (Finished product code)
TYPE: ......................... (Order Code)
SUPPLY: ......................... (Type of electrical power supply)
VERS: ......................... (Software version)
3
81801G_MHW_1200-1300_07-2011_ENG

2 • INSTALLATION AND CONNECTION
This section contains the instructions necessary
for correct installation of the 1200/1300
controllers into the machine control panel or the
host system and for correct connection of the controller
power supply, inputs, outputs and interfaces.
Before proceeding with installation read the
following warnings carefully!
Remember that lack of observation of these
warnings could lead to problems of electrical
safety and electromagnetic compatibility, as well as
invalidating the warranty.
Electrical power supply
• thecontrollerisNOTequippedwithanOn/Offswitch:
the user must provide a two-phase disconnecting
switch that conforms to the required safety standards
(CE marking), to cut off the power supply upstream of
the controller.
The switch must be located in the immediate vicinity of
the controller and must be within easy reach of the
operator. One switch may control more than one
controller.
• ifthecontrollerisconnectedtoNOTisolatedelectri-
cal equipment (e.g. thermocouples), the earth
connection must be made with a specific conductor
to prevent the connection itself from coming directly
through the machine structure.
• ifthecontrollerisusedinapplicationswithriskof
damage to persons, machinery or materials, it is
essential to connect it up to auxiliary alarm
equipment. It is advisable to make sure that alarm
signals are also triggered during normal operation.
The controller must NOT be installed in flammable or
explosive environments; it may be connected to
equipment operating in such atmospheres only by
means of appropriate and adequate types of
interface, conforming to the applicable safety
standards.
Notes Concerning Electrical Safety and
Electromagnetic Compatibility:
CE MARKING:
The instrument conforms to the European Directives
2004/108/CE and 2006/95/CE with reference to the
generic standards: EN 61000-6-2 (immunity in industrial
environment) EN 61000-6-3 (emission in residential envi-
ronment) EN 61010-1 (safety).
Series 1200/1300 temperature controllers are mainly
designed to operate in industrial environments, installed
on the switchboards or control panels of productive
process machines or plants.
As regards electromagnetic compatibility, the strictest
generic standards have been adopted, as indicated in
the table below.
EMC conformity has been tested with the following
connections.
Function Cable type Length
Power supply cable 1mm21m
Relay output cables 1mm23.5m
Serial connection wire 0,35mm23.5m
C.T. connection cables 1,5mm23.5m
Thermocouple input probe 0,8mm2compensated 5m
“PT100” temperature resistance input probe 1mm23m
481801G_MHW_1200-1300_07-2011_ENG

Generic standards, emission standard for residential commer-
cial and light industrial environments
Emission enclosure
Emission AC mains
Radiated emission
EN 61000-6-3
EN 61000-6-3
EN 61000-6-3
EN 61326 CISPR 16-2
Gruppo1 Classe B
Gruppo1 Classe B
Classe B
EMC Emission
EMC Immunity
Generic standards, immunity standard for industrial envi-
ronments
Immunity ESD
Immunity RF interference
Immunity conducted disturbance
Immunity burst
Immunity pulse
Immunity Magnetic fields
Voltage dips, short interruptions and voltage immunity tests
EN 61000-6-2
EN 61000-4-2
EN 61000-4-3 /A1
EN 61000-4-6
EN 61000-4-4
EN 61000-4-5
EN 61000-4-8
EN 61000-4-11
4 kV contact discharge level 2
8 kV air discharge
level 3
10 V/m amplitude modulated
80 MHz-1 GHz
10 V/m amplitude modulated
1.4 GHz-2 GHz
10 V/m amplitude modulated
0.15 MHz-
80 MHz (level 3)
2 kV power line (level 3)
2 kV I/O signal line (level 4)
Power line-line 1 kV (level 2)
Power line-earth 2 kV (level 3)
Signal line-earth 1 kV (level 2)
100 A/m (level 5)
100%U, 70%U, 40%U,
LVD Safety
Safety requirements for electrical equipment for measurement,
control and laboratory use
EN 61010-1
Advice for Correct Installation for EMC
Instrument power supply
• Thepowersupplytotheelectronicequipmentonthe
switchboards must always come directly from an
isolation device with a fuse for the instrument part.
• Theelectronicinstrumentsandelectromechanical
power devices such as relays, contactors, solenoid
valves, etc., must always be powered by separate
lines.
• Whentheelectronicinstrumentpowersupplyis
strongly disturbed by the commutation of transistor
or power units or motors, an isolation transformer
should be used for the controllers only, earthing the
screen.
• Itisessentialthattheplanthasagoodearthcon-
nection:
- the voltage between neutral and earth must not be >1V
- the Ohmic resistance must be <6W;
• Ifthemainsvoltagefluctuatesstrongly,useavolta-
ge stabilizer.
• Intheproximityofhighfrequencygeneratorsorarc
welders, use adequate mains filters.
• Thepowersupplylinesmustbeseparatefromthe
instrument input and output ones.
Inputs and outputs connection
• Theexternallyconnectedcircuitsmustbedoubly
isolated.
• Toconnecttheanalogueinputs(TC,RTD)the
following is necessary:
- physically separate the input cables from those of
the power supply, the outputs and the power connec-
tions.
- use woven and screened cables, with the screen
earthed in one point only
• Toconnecttheregulatingandalarmoutputs
(contactors, solenoid valves, motors, fans, etc.), fit
RC groups (resistance and condensers in series) in
parallel to the inductive loads that operate in
Alternating Current.
(Note: all the condensers must conform to VDE
(class X2) standards and withstand a voltage of at
least 220V AC. The resistances must be at least 2W).
• Fita1N4007diodeinparallelwiththecoilofthe
inductive loads that operate in Direct Current.
GEFRAN S.p.A. declines all responsibility for
any damage to persons or property caused
by tampering, neglect, improper use or any
use which does not conform to the characte-
ristics of the controller and to the indica
tions given in these Instructions for Use.
5
81801G_MHW_1200-1300_07-2011_ENG

Dimensions and cut-out
1200 1300
A
A
Installation with panel mounting
As well as the actual controller and these instructions
for use, the controller package also contains:
•2panelfixingbrackets(A)
•1protectivesealagainstdustandwaterspray(B)
Fit the controller to the panel as shown in the figure.
Warnings and instructions for mounting to the panel
Instructions for installation category II,
pollution level 2, double isolation.
• onlyforlowpowersupply:supplyfromClass2or
low voltage limited energy source.
• thepowersupplylinesmustbeseparatefromthe
controller input and output ones
• grouptheinstrumentstogetherkeepingthem
separate from the powered part of the relay
• donotinstallhigh-powerremoteswitches,
contactors, relays, thyristor power units (especially
the “phase angle” type), motors, etc. in the same
switchboard
• avoiddust,humidity,corrosivegassesandheat
sources
• donotblocktheventilationholes:theworking
temperature must be between 0...50°C
• surroundingair:50°C
• use60/75°Ccopper(Cu)conductoronly,wiresize
range 2x No 22 - 14AWG, Solid/Stranded
• useterminaltighteningtorque0.5Nm
Nominal ambient conditions
Before supplying the Controller with power,
make sure that the mains voltage is the
same as that shown in the last number of
the order code.
Example:
1200/1300 – xx – xx – xx – x – 1 = 100..240Vac/dc
1200/1300 – xx – xx – xx – x – 0 = 11..27Vac/dc
A
B
A
B
Altitude Up to 2000m
Working/storage 0..50°C/-20...70°C
temperature
Non condensing 20...85%
relative humidity
681801G_MHW_1200-1300_07-2011_ENG

Electrical Connections
PWR
Outputs
Out1 - Out2
Inputs
Serial line
Digital inputs
/
CT Input
Outputs
Out3 - Out4
1200
Always make the connections using cable types suitable for the voltage and current limits given in
Section 5 - Technical Specifications.
If the Controller has faston terminals these must be protected and isolated.
If it has screw terminals, the wires must be attached, at least in pairs
Power Supply
Inputs
+
24V
4..20mA
VT +
+
+
S
24VVT +
+
+
+
Standard: 100...240Vac/dc ±10% , max 18VA
Optional: 11...27Vac/dc ±10% , max 11VA
50/60 Hz
Available thermocouples:
J, K, R, S, T
(B,E, N, L, U, G, D, C
possible by inserting a
custom linearization)
- Observe polarities
- For extensions, use the
correct compensating cable
for the type of TC used
Connect for 0/4..20mA
input
Jumper S3 closed on CPU
board
(see CAP. 6 Maintenance)
Linear input in
Direct Current
0/4..20mA, Ri = 50W
TC Input Linear input with 3-wire transmitter supplied from
the instrument
Linear input with 2-wire Transmitter supplied
from the instrument
Linear input (I)
~
~
PWR
7
81801G_MHW_1200-1300_07-2011_ENG

Inputs
+
Linear input in
Direct Current
60 mV, 1V (Ri > 1MW)
5V, 10V (Ri > 10KW)
Linear input (V) PTC/NTC/Pt100/JPT100 input
T
Jumper S2 closed
on CPU board
(see CAP. 6
Maintenance)
Use wires of
adeguate diameter
(min. 1mm2)
2-wire connection 3-wire connection
Outputs Out1, Out 2 User configurable generic outputs
C
NO
NC - Relay 5A
250Vac/30Vdc
NC not
available if
Out2 is triac
type
Out 1
-
+
C
NO
- Relay 5A
250Vac/30Vdc
- Logic 24V
(10V a 20mA)
Out 2
~
~
load
Triac
20...240Vac,
max. 1A ± 10%
Out 2
Outputs Out3, Out 4 User configurable generic outputs
- Relay 5A 250Vac/30Vdc
- Logic 24V 10V a 20mA
- Direct 0...10V, 0/4...20mA
- Analogue 0...10V, 0/4...20mA
- 0/2...10V (S1-ON),
0/4...20mA (S1-OFF)
S1 is a jumper on the board
for continuous or analogic
output
Out 3
- Relay 5A 250Vac/30Vdc
- Logic 24V (10V a 20mA)
Out 4
Digital input 24V 5mA
(Jumpers S1, S2 in position P)
or from non-powered terminal
(Jumpers S1, S2 in position N)
Hrd Menù configuration
Parameter diG or di2 = +16
IN1, IN2 digital inputs
- Input from current transformer
50mAac, 10W50/60Hz
- Digital input 24V 5mA
(Jumpers S1, S2 in position P)
or from non-powered terminal
(Jumpers S1, S2 in position N)
Hrd Menù configuration
Parameter diG or di2 = +16
CT, IN1 inputs
T
S1
Out3
+
Out4
+
IN2
IN1
COM
TA
IN1
COM
S1
S2
N P S1
S2
N P
Digital inputs / CT Input User configurable generic inputs
881801G_MHW_1200-1300_07-2011_ENG

Example of connection with TC Input
Electric heating with power solid state relay and water cooling with solenoid valve
EV
L1
L2
OUT2 logic
OUT1 relay
AUX
PWR
-
+
Serial line
(data +)
(data -)
GND
B
A
RS485 isolated serial line
Modbus 2 wires (Standard)
Tx
+
Rx
+RS485 isolated serial line
For configuration
Modbus 4 wires/Cencal.
Modbus 4 wires / Cencal
S1 S1
9
81801G_MHW_1200-1300_07-2011_ENG

PV : Shows the process variable, the menu identification, the
parameters identification and the error codes
SV : Shows the setpoint value, the value of the parameter displayed in
PV and three dashes (- - -) when PV contains a menu heading
Increases/Decreases the value of the parameter displayed in SV until
the max/min. value is reached.
Held down: progressively increases the speed of increasing/decreasing
the value displayed in SV.
Used to move between the various menus and parameters of the controller.
Confirms the value of the current parameter (or parameter edited using
) and selects the next parameter.
Button with configurable function: with standard configuration commutes the
controller operating mode (MANUAL/AUTOMATIC).
Is only on when the display shows the process variable.
(for configuration see parameter BVT in the KRD menu)
Confirms the value of the current parameter (or parameter edited using
) and selects the previous parameter.
Output status indicators:
OUT1 (AL1), OUT2 (Main), OUT3 (HB), OUT4
Function indicators: with standard configuration they show the controller
operating status
For configuration see parameter LD.1, LD.2, LD.3 in the KRD menu
L1 MAN/AUTO = OFF (automatic control)
ON (manual control)
L2 SETPOINT 1/2 = OFF (IN1= OFF local Setpoint 1)
ON (IN1=ON local Setpoint 2)
L3 SELFTUNING = ON (Self activated)
OFF(Self deactivated)
3 • FUNCTIONS
This section illustrates the functions and operating modes of the displays, the indicator lights and the
buttons that make up the operator interface of series 1200/1300 controllers. It is therefore an essential
requirement for programming and configuring the controllers correctly.
Operator Interface
ID Symbol Function
+
10 81801G_MHW_1200-1300_07-2011_ENG

General Operating Notes
• Immediatelyafterswitchingonthecontrollercarriesoutaself-diagnostictest.
During the test, all the display segments and the 7 indicator lights will flash.
• Iftheself-diagnosticsproceduredoesnotdetectanyerrorsthecontrollerenters
the normal working status (Level 1)
• Anyerrorsfoundbytheself-diagnosticsarememorizedinarecordandcanbe
displayed with the
ERR function in the INF menu
PV Displays the value of the Process Variable.
SV Displays the Setpoint value or the Control Output value if in the Manual
working mode.
• BypressingbrieflyitispossibletoseeinsequenceonthePVdisplay
(and if necessary edit) the significant values that condition the way the
controller works in Level 1 (Setpoint, Alarm threshold, Control Output, etc.)
• Keepingpresseddownfor3secondsweenterthe
Programming/Configuration menu - see Navigation in the Controller Menus for
further details.
• Bypressingitispossibletoincrease/decreasetheSetpointvalue,
until the required value is reached.
In the event of errors during normal working:
PV Displays the error identification.
SV Continues to display the Setpoint or Control Output value.
LO process variable< min. scale limit (param. LOS in the INP menu)
HI process variable> max. scale limit (param. K’Sin the INP menu)
SBR broken probe or input values higher than maximum limits
ERR third wire broken for PT100,PTC or input values lower than minimum
limits (e.g. for TC with wrong connection)
To solve the problem, refer to the paragraph: Troubleshooting Guide in Section 6 Maintenance
Switching on and using the Controller
Self-diagnostics
Normal Working - Level 1
Errors while working
399 PV
SV
400
11
81801G_MHW_1200-1300_07-2011_ENG

Navigating through the Controller Menu
Keep pressed down to scroll through the menus in sequence and release it when the required menu appears.
Press to access the parameters of the selected menu.
Keep + to return immediately to level 1.
Level 1 Display Menu
PV
SV
39.9
40.0
PV
SV
n
IF
---
PV
SV
P
S
PV
SV
P
S.I
PV
SV
P
S.2
PV
SV
n
I.2
AL.I PV
SV
PV
SV
K
A.b
PV
SV
v
0.P
Local Setpoint
Setpoint 1
Setpoint 2
Amperometric input value
(with CT input present)
Alarm point 1
(scale points)
Alarm point 2
(scale points)
Alarm point 3
(scale points)
HB Alarm point (amperometric
input scale points)
Control outputs value in %
(+Heat / - Cool)
Timed return to level 1 disabled.
(*)
(*)
Information display
Jumper S4 on soldered side of
CPU board
See Section 6 - Maintenance
PV
SV
F
GG
---
OK
S4 ON ?
NO
PV
SV
E
SR
---
PV
SV
n
IP.
---
PV
SV
v
0t
---
PV
SV
A
PS
99
OK
PAS=99 ?
NO
PV
SV
r
Po
---
PV
SV
r
Kd
---
PV
SV
i
Ln
---
PV
SV
UGA
---
.
Configuration
Serial
Communication
Inputs setting
Outputs setting
Password
Protection Code
Hardware
Configuration
Input
Linearization
User Calibration
The parameters and menus not significant for a given configuration are NOT displayed
If the keys , are not pressed within approx. 15 seconds, the display returns to level 1
- set the PAS parameter to the
value “99”
- press “F” key once to access
PRO parameter
- keep “F” key pressed to access
the protected menu
These menus
are only
displayed if
Pro = 128
12 81801G_MHW_1200-1300_07-2011_ENG
PV
SV
L
A.2
PV
SV
L
A.3

4 • CONFIGURATION / PROGRAMMING
This section contains the instructions necessary to
configure the 1200/1300 Controller according to the
needs of the application..
Optimal working operation of the 1200/1300 Controller in the
field of application it is intended for depends largely on correct
configuration and programming of the relevant control
parameters.
The flexibility and high performance level of these instruments
is in fact based on the numerous parameters that can be
programmed directly by the user with the buttons on the con-
trol panel, or transferred from a PC, in the form of configu-
ration files, by means of the RS485 interface available as an
option on 1200/1300 Controllers.
Easy configuration
To simplify the Controller configuration and programming pro-
cess in the most common temperature control applications,
that do not require very complex controls, there is a simplified
level of configuration (“Easy”) suitable for the basic instrument
versions, with just two outputs (Out1 - Out2).
The Easy configuration essentially has three menus:
(FG : general Controller configuration
INP : input functioning mode
0VT : output functioning mode
which involve setting a limited number of parameters
(maximum 13), as well as setting the AL.1 alarm point that
can be done directly in level 1.
Extended Configuration
Access to all the configuration / programming menus and to all
the parameters available for the 1200/1300 controllers in
extended configuration, allows every detail of the Controller to
be configured, to satisfy all application requirements.
Correct setting of the parameters involved in the
extended configuration presumes a high level of
knowledge regarding temperature control problems
and techniques, and so it is recommended that these
parameters are not changed unless the user is fully
aware of the consequences, that could arise form
incorrect settings.
It is the user’s responsibility to check that the
parameters are set correctly before putting the
Controller into service, in order to avoid damage to
persons or property.
For any doubts or clarification needed, please visit the
Web Site www.gefran.com and if necessary contact
the Gefran Customer Care service..
To select the Extended configuration mode, 128 must be
added to the value of the PRO parameter that appears when
scrolling through the Controller menu - see Navigating through
the Controller Menus.
The following pages describe one by one the various
Controller menus and show for each parameter the concise
description of the function performed, any default values and
the range of values that can be set.
Example: H.IT parameter in the (FG menu
Integral heating time
[0.0 ... 99.99] % f.s.
(default value)
Supplementary notes on consulting the Configuration/
Programming pages
To set some particularly complex parameters certain tables or
detailed explanatory notes must be referred to.
These tables or explanatory notes are shown directly on the
right of the page next to the parameter in question.
Application notes
The detailed explanations of certain functioning modes
or special techniques the result Gefran’s lengthy
experience in the field of temperature control are inste-
ad contained at the end of the Configuration/Programming
Section and can represent a valuable reference tool for
the user.
Where necessary, in the configuration / programming
flows the appropriate referrals to these Application
Notes are provided.
Password: PAS
When scrolling through the menu (keeping pressed
down), following the 0VT menu, the word PAS appears.
Access to the next menus is only possible if the PAS = 99
parameter is set to 99 by pressing .
Having set the value to 99, press and keep it pressed
down to access the next menus.
Protection code: PRO
The PRO parameter is used to choose between the “Easy” and
the “Extended” configuration, and is also used to enable or
disable the display and/or the possibility of editing certain
parameters. For further details refer to the description of the
PRO parameter in the configuration flows..
Jumper S4 on CPU Board
The absence of jumper S4 on the CPU board of the Controller
prevents access to all the menus when the hardware
configuration of the instrument does not require the pre-set
parameters to be changed.
This jumper is engaged or disengaged during production and
normally does not need to be modified by the final user.
For further information, refer to Section 6 - Maintenance.
4.00
h.It PV
SV
13
81801G_MHW_1200-1300_07-2011_ENG

EASY Configuration/Programming
Standard for instrument with 2 Outputs: OUT1 = AL1 / OUT2 = MAIN HEAT
In the EASY configuration, the general navigation flow shown at the end of Section 3 - Functions is considerably
simplified, as illustrated in the following figure.
Level 1 display Menu
PV
SV
39.9
40.0 3 sec.
Jumper S4 on soldered side
of CPU board
See Section 6 - Maintenance
PV
SV
F
GG
---
OK
S4 ON ?
NO
PV
SV
n
IP.
---
PV
SV
v
0t
---
PV
SV
A
PS
99
Configuration
Inputs Setting
Outputs Setting
Password
AL.I PV
SV
Alarm point 1
(scale points)
PV
SV
r
Po
---
OK
PAS = 99 ?
NO
Protection code
14 81801G_MHW_1200-1300_07-2011_ENG

(FG Configuration Fourth menu to set up -Easy-
This menu is used to configurare the control parameters in the Easy mode.
PV
SV
F
GG
---
1.0
h.Pb PV
SV
4.00
h.It PV
SV
Proportional band for heating
or hysteresis for ON/OFF control
[0 ... 999.9] % f.s.
Integral time for heating
[0.00 ... 99.99] min.
1.00
h.dt PV
SV
100.0
h.P.K PV
SV
- 1
KY.i PV
SV
MAX power limit for heating
[0.0 ... 100.0] %
Hysteresis for Alarm 1
[±999] scale points
Derivative time for heating
[0.00 ... 99.99] min.
Adding +32 to the value of A 1.T in the 0VT menu,
the setting range is [0 … 999] sec.
Adding +64 to the value of A 1.T in the 0VT menu,
the setting range is [0 … 999] min.
Please note.:
If HEAT/COOL double action control type is ena-
bled (parameter [TR in menù KRD) then the COOL
action parameters cPb , cIt, cdt, cPK are displa-
yed, with the same ranges as the equipment
HEAT action parameters.
PV
SV
t
S. v
0
Enabling self-tuning, autotuning,
softstart (**)
S.tun Continuous Selftuning Softstart
autotunig
0 NO NO NO
1 YES NO NO
2 NO YES NO
3 YES YES NO
4 NO NO YES
5 YES NO YES
6 - - -
7 - - -
S.tun Single action Selftuning Softstart
Autotuning
8* WAIT NO NO
9 GO NO NO
10* WAIT YES NO
11 GO YES NO
12* WAIT NO YES
13 GO NO YES
*) By adding the following figures to the value indicated in the
table it is possible to enable a series of supplementary functions:
+16 with automatic switch to GO if PV-SP > 0.5%
+32 with automatic switch to GO if PV-SP > 1%
+64 with automatic switch to GO if PV-SP > 2%
+128 with automatic switch to GO if PV-SP > 4%
**) For more information on the Self Tuning, Auto
Tuning, Soft Start functions, refer to the
Operational Notes paragraph.
15
81801G_MHW_1200-1300_07-2011_ENG
With the time scales 0-999sec/0-999min the decimal point has no
meaning ( for dP.S different from 0”)

INP Inputs Settings Third menu to set up -Easy-
PV
SV
n
IP.
---
0
tYP PV
SV
Type of probe, signal, custom line-
arization enabling and main scale input
TYP Probe type Without dec. With dec.
point point
DP.S = 0 DP.S = 1
Sensore: TC
0 TC J °C 0/1000 0.0/999.9
1 TC J °F 32/1832 32.0/999.9
2 TC K °C 0/1300 0.0/999.9
3 TC K °F 32/2372 32.0/999.9
4 TC R °C 0/1750 0.0/999.9
5 TC R °F 32/3182 32.0/999.9
6 TC S °C 0/1750 0.0/999.9
7 TC S °F 32/3182 32.0/999.9
8 TC T °C -200/400 -199.9/400.0
9 TC T °F -328/752 -199.9/752.0
30 PT100 °C -200/850 -199.9/850.0
31 PT100 °F -328/1562 -199.9/999.9
32 JPT100 °C -200/600 -199.9/600.0
33 JPT100 °F -328/1112 -199.9/999.9
34 PTC °C -55/120 -55.0/120.0
35 PTC °F -67/248 -67.0/248.0
36 NTC °C -10/70 -10.0/70.0
37 NTC °F 14/158 14.0/158.0
38 0...60 mV -1999/9999 -199.9/999.9
40 12...60 mV -1999/9999 -199.9/999.9
42 0...20 mA -1999/9999 -199.9/999.9
44 4...20 mA -1999/9999 -199.9/999.9
46 0...10 V -1999/9999 -199.9/999.9
48 2...10 V -1999/9999 -199.9/999.9
50 0...5 V -1999/9999 -199.9/999.9
52 1...5 V -1999/9999 -199.9/999.9
54 0...1 V -1999/9999 -199.9/999.9
56 200 mV...1 V -1999/9999 -199.9/999.9
CUSTOM linearization:
L0 appears when the variable takes on values lower than the
LO.S parameter or the minimum calibration value.
KI appears when the variable takes on values higher than the
K’.S parameter or the maximum calibration value.
Maximum Non Linearity error for Thermocouples (TC),
Temperature resitances (Pt100) and Thermistors (PTC, NTC).
The error is calculated as differing from the theroetical value
with reference in % of the full scale value, expressed in degre-
es Celsius (°C)
Decimal Point Pos.
for Input Scale
Probe type Probe Error
Thermocouples TC type J, K < 0,2 % f.s.
TC type S, R with scale 0..1750 °C: < 0.2 % f.s.
(t > 300 °C); for other scales: < 0.5 % f.s.
TC type T < 0.2 % f.s. (t > -150 °C)
Thermistors NTC < 0.5 % f.s.
JPT100 / PTC < 0.2 % f.s.
Temperature Pt100 with scale -200..850 °C: accur. better
than resistances 0.2 % f.s.
DP.S Format
0 xxxx
1 xxx.x
2 xx.xx (*)
3 x.xxx (*)
Main Input Scale MAX Limit Valore
Min..Max value assigned to input
selected with the TYP parameter
Lower limit for SP and absolute
alarms LO.S ... KI.S
Upper limit for SP and absolute alarms
LO.S ... KI.S
Main Input Scale MIN Limit
Min..Max value assigned to input
selected with the TYP parameter
(*) not available for TC, RTD, PTC, NTC probes.
0
dP.S PV
SV
0
Lo.S PV
SV
1000
Ki .SPV
SV
0
LoL PV
SV
1000
Ki .LPV
SV
16 81801G_MHW_1200-1300_07-2011_ENG

0VT Outputs Settings Second menu to set up -Easy-
This menu is used to configure the type of Alarm 1 and the Output 2 cycle time.
PV
SV
v
0t
---
0
AI.t PV
SV Alarm type 1
If more alarms are
enabled *, please set
them using the same
table
* (A2t, A3t).
A1.T Direct
(high limit Normal
Inverse Absolute/Relative Symmetric
(low limit) to active Setpoint (window)
0 Direct Absolute Normal
1 Inverse Absolute Normal
2 Direct Relative Normal
3 Inverse Relative Normal
4 Direct Absolute Symmetric
5 Inverse Absolute Symmetric
6 Direct Relative Symmetric
7 Inverse Relative Symmetric
By adding the following amounts to the values shown in
the table a series of supplementary functions can be
enabled
+8: to disable on power up until first interception.
+16: to enable alarm memory.
+32: KY.1 menu [FG = alarm trigger delay time
([0..999] sec. (excluding absolute symmetric)
+64: KY.1 menu [FG = alarm trigger delay time
([0..999] min. (excluding absolute symmetric)
20
Gt.2 PV
SV OUT 2 Cycle time (HEAT or COOL)
[1 ... 200] sec.
the same setting range is valid also for
Ct1, Ct3, Ct4.
PV
SV
L.
r
2
1OUT 1
Allocation of reference signal
If more outputs are available *, plea-
se set them using the same table
* (rL2, rL3, rL4)
RL.1; RL.2
RL.3; RL.4 Function
0 HEAT (control output for heating)
1 COOL (control output for cooling)
2 AL1 – alarm 1
3 AL2 – alarm 2
4 AL3 – alarm 3
5 AL. HB – HB alarm
6 LBA – LBA alarm
7 IN – repetition of logic input 1
8 Repeat but key (if BVT menu KRD = 8)
9 AL1 or AL2
10 AL1 or AL2 or AL3
11 AL1 And AL2
12 AL1 and AL2 and AL3
13 AL1 or AL. HB
14 AL1 or AL2 or AL. HB
15 AL1 and AL. HB
16 AL1 and AL2 and AL. HB
Add +32 to the values indicated in the table to obtain the denied
logic level in output, except for codes 0..1 with continuous output
64 * RL.2 HEAT: heat control output with fast cycle time
(0.1 ... 20.0 sec.)
RL.3 HEAT: continuous output 2 – 10 V
65 * RL.2 COOL: cool control output with fast cycle
time (0.1 ... 20.0 sec.)
RL.3 COOL: continuous output 2 – 10 V
*) only for RL.3 o RL.2 if continuous OUT3 is not present
17
81801G_MHW_1200-1300_07-2011_ENG

PRO Protection code -Easy-
This menu is used to enable or disable the display and/or editing of certain parameters and to access the exten-
ded configuration.
PV
SV
r
Po
0
PRO Display Modification
0 SP, alarms SP, alarms
1 SP, alarms SP
2 SP
By adding the following amounts to the values shown
in the table a series of supplementary functions can be
enabled:
+4: to disable INP, 0VT
+8: to disable [FG
+128: to enable the display of all the parameters
and menus.
18 81801G_MHW_1200-1300_07-2011_ENG

19
81801G_MHW_1200-1300_07-2011_ENG
INF Information display Extended programming configuration
PV
SV
n
IF
---
PV
SV
P
Ud
2.0i Software version
This menu provides information on the status and hardware configuration of the controller (number and type of inputs/outputs,
software version, etc.).
Instrument code
0 no error
1 Lo
2 Hi
3 ERR
4 SBR
Configuration
hrd 1
Configuration
hrd 2
Where there is an error in recognising the boards the value
displayed is increased by +8:
PV
SV
o
Gd
1
PV
SV
r
Er
0
PV
SV
K
G. d
1311
PV
SV
K
G. 2
601
Self diagnostic error code
1311
OUTPUT 1
0 = None
1 = Relay
OUTPUT 2
0 = None
1 = Relay
2 = Logic
3 = Triac
OUTPUT 3
0 = None
1 = Relay
2 = Logic
4 = Continuous
5 = Analog
OUTPUT 4
0 = None
1 = Relay
2 = Logic
601
DIGITAL INPUT
2/TA
0 = None
6 = CT
7 = Digital 2
DIGITAL
INPUT 1
0 = None
7 = Digital 1
SERIAL
0 = None
1 = RS 485

(FG Configuration Fourth menu to set up
This menu makes it possible to configure various control parameters.
PV
SV
F
GG
---
1.0
h.Pb PV
SV
4.00
h.It PV
SV
Proportional band for heating or hysteresis
for ON/OFF control
[0 ... 999.9] % f.s.
Integral time for heating
[0.00 ... 99.99] min.
PV
SV
t
S. v
0
1.00
h.dt PV
SV
100.0
h.P.K PV
SV
Maximum power limit
for heating [0.0 ... 100.0] %
Derivative time for heating
[0.00 ... 99.99] min.
Enabling self-tuning, autotuning,
softstart (**)
PV
SV
U
G. E
0
PV
SV
S
c. P
0
Cooling medium
[0 ... 2]
Setpoint for cooling relative to
heating setpoint
[±25.0] % f.s.
PV
SV
P.
h. L
0.0
Integral time for cooling
[0.00 ... 99.99] min.
Proportional band for cooling or
hysteresis for ON-OFF control
[0 ... 999.9] % f.s.
Minimum power limit for heating (not
available for double heat/cool action)
[0.0 ... 100.0] %
Derivative time for cooling
[0.00 ... 99.99] min.
Maximum power limit for cooling
[0.0 ... 100.0] %
S.tun Continuous Selftuning Softstart
autotunig
0 NO NO NO
1 YES NO NO
2 NO YES NO
3 YES YES NO
4 NO NO YES
5 YES NO YES
6 - - -
7 - - -
S.tun Single action Selftuning Softstart
Autotuning
8* WAIT NO NO
9 GO NO NO
10* WAIT YES NO
11 GO YES NO
12* WAIT NO YES
13 GO NO YES
*) By adding the following figures to the value indicated in the
table it is possible to enable a series of supplementary fun-
ctions:
+16 with automatic switch to GO if PV-SP > 0.5%
+32 with automatic switch to GO if PV-SP > 1%
+64 with automatic switch to GO if PV-SP > 2%
+128 with automatic switch to GO if PV-SP > 4%
**) For more information on the Self Tuning, Auto
Tuning, Soft Start functions, refer to the
Operational Notes paragraph.
[ME Type Relative gain (rG)
(see paragraph “Application Notes”)
0 AIR 1
1 OIL 0,8
2 WATER 0,4
Read only parameters if the Heat/Cool control typology
is enabled
(parameter CTR = 14 in the HRD menu)
A
PV
SV
P
c. b
1.0
PV
SV
I
c. t
4.00
PV
SV
d
c. t
1.00
PV
SV
P.
c. K
100,0
20 81801G_MHW_1200-1300_07-2011_ENG
Other manuals for 1200
1
This manual suits for next models
1
Table of contents
Other gefran Temperature Controllers manuals