gefran 400 User manual

Relay contact NO (NC), 5A, 250V cosϕ=1
Logic output for static relays 10Vdc, Rout = 100Ω(6V/20mA),4V/20mA x OUT3
Cycle time 0...200 sec
Type of main output relay, logic
Control outputs on / off, pwm
Limitation Max power heat / cool 0,0...100,0 %
°C / °F selection Faceplate configurable
Linear scale ranges -1999 to 9999 configurable decimal point position
Control actions Pid, Autotune, on-off
pb 0,0...999,9 %
dt 0,00...99,99 min
di 0,00...99,99 min
Action heat or cool
Softstart 0,0...500,0 min
Configurable alarms Up to 3 alarm functions assignable to an output
and configurable as: maximum, minimum,
symmetrical, absolute/relative, LBA
Fault power setting -100,0...100,0 %
Power off function Maintains PV display; can be excluded
Alarm masking exclude on power-up
Optional current transformer input
(Mod. 401) T.A. 50mAac, 50/60Hz, Ri = 2Ω
Faceplate protection IP65
Working / Storage temperatures 0...50°C / -20...70°C
Relative humidity 20 to 85%, non-condensing
Installation Panel mounting, extractable from front
Weight 210g for the complete version
Power supply
(standard) 100...127Vac (220...240vac) ± 10%
(optional) 11...14Vac (22...27Vac) ± 10%
(optional) 11...27Vac/dc (not isolated)
50/60Hz, 5.5 VA max.
Safety detection of short circuit or opening of sensors,
LBA alarm
RTD type (scale configurable within indicated
range, with or without decimal point)
Max. RTD line resistance
DIN 43760 (Pt100)
20Ω
Cold junction error 0,1° / °C
PTC type (on request) 990Ω, 25°C
400 / 401
SINGLE DISPLAY TEMPERATURE CONTROLLER WITH UNIVERSAL INPUT
SOFTWARE VERSION 3.0x
code 81500D / edition 12 -05/04
USER’S MANUAL
For correct and safe
installation, follow the
instructions and observe
the warnings contained in
this manual.
Thermocouples IEC 584-1 (J, K, R, S, T, B, E, N)
Display 4 digit green LED’s, digit height 10mm
Keys 4 mechanical keys (Man/Aut, Raise, Lower, F)
Accuracy 0.25% f.s. at 25°C ambient temperature
Main input TC, RTD (Pt100), PTC
60mV, 10V, Ri ≥1MΩ; 20mA, Ri = 50Ω
1 •INSTALLATION
•Dimensions and cut-out: Panel mounting
Panel mounting:
Fix the device with the bracket provided before making any electrical connections.
To mount two or more devices side by side, use the cut-out dimensions shown above.
CE MARKING: EMC (electromagnetic compatibility) conformity to EEC Directive
89/336/CEE with reference to the generic Standard EN61000-6-2 (immunity in
industrial environments) and EN50081-1 (emission in residential environments). BT
(low voltage) conformity to Directive 73/23/CEE as modified by Directive 93/68.
MAINTENANCE: Repairs must be done out only by trained and specialized personnel.
Cut power to the device before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene, etc.).
Use of these solvents can reduce the mechanical reliability of the device. Use a cloth
dampened in ethyl alcohol or water to clean the external plastic case.
SERVICE: GEFRAN has a service department. The warranty excludes defects caused
by any use not conforming to these instructions.
2 •TECHNICAL SPECIFICATIONS
FUNCTION CABLE LENGTH USED
TC input probe 0,8 mm2compensated 5 m
“PT100”input probe 1 mm23 m
Power supply cable 1 mm21 m
Relay output cables 1 mm23,5 m
Current transformer cables 1,5 mm23,5 m
EMC conformity has been tested with the following connections
!
10
99
10
45
45
48
70
70
63
48
Environmental conditions of use for internal use only, altitude up to 2000m

Short Operating Instruction
for temperature regulator 400
We deliver our temperature regulator in its basic adjustment for the control of heaters. For other applications, the
parameters should be accordingly modified with the help of the attached operating instruction.
1. Link: There is a link for the thermocouple (NiCr Ni, type K) on the front plate. Laterally, heaters can be
steered through the automatic controller. The permissible power for each power connection amounts to 5 A
with 230 ~V. Attention the output is only for resistive load!
2. Display: The temperature (actual value) measured at the thermocouple is displayed. Heater switching
impulses (220 V at the plug sockets) are displayed by a red LED down/up OUT 2. If the actual value is
below the set point, this is displayed by a red LED arrow directing to the left (LOW); if the actual value
exceeds the set point, this is indicated by a red LED arrow directing right (HIGH) OUT 2 turn off; no 220 V
at the plug sockets). If the actual value is within the range of tolerance of the set point, a green beam-LED
lights up.
3. Temperature adjustment: Through pressing key >F< on the front plate „-SP“ appears, alternating with the
set point actually given. With the arrow keys > v/ ^< the desired set point can be set. After the
modification press key >F< again to transfer the new set point (display: > AL.1<). After 5 seconds the
instrument switches back into the initial state and the modified set point is taken over. If the desired value is
modified and there is no acknowledgement by key >F< after 5 seconds, the instrument again switches back
into the initial state, but the set point is reduced to the lower alarm value. By pressing key >F< second time
(next of the set point), further values such as alarm value 1 and 2 (optionally) and the placing degrees (not
by automatic, only by manual) can be called up. Note: if key >F< is initially pressed longer than 2 seconds,
you achieve a level on which there is the danger of an unintentional change of the functional parameters.
4. Temperature control: Thermocouple NiCr Ni type K, without self-optimization and auto optimization,
proportional temperature control, with soft start function (note: heating regulates the full heating power after
approximately 3-5 minutes; in any case soft start for the protection of the heating cartridge).
Important adjustments for modifications of the temperature control:
Blocked: Pass: 99 (protection: 28)
by parameter CFG (press >F< key for 2 seconds, press twice afterwards, CFG appears)
S.tu: Adjustment whether working with optimization (see instruction)
h.Pb: Value of heating in proportion to the final value of the thermocouple; i.e. the regulation starts 1 % of
the thermocouple’s final value below the set point. Example: adjustment: 1,0, thermocouple type K: 1300°C
= 1 % = 13 °C, set point: 500 °C; this means that the temperature control is started at 487°C.
h.It: the smaller the value, the more an adaptation value to the set point is attempted. If the value is small,
there is the danger of over swing.
h.dt: the larger the value, the more an over swing is prevented; this affects a dampening of the controlling
action. The relation of the values h.It to h.dt should always be 4:1.
5. Manual regulation: Through pressing key > O< you can choose between automatic and manual operation.
In case of manual operation the instrument is only used as a momentum generator and there is no need for a
thermocouple (important when sensor breaks). After reversing, all LED light up and the position can be
chosen. Value 100 means constant heating, value 50 means that the processes of turning on and turning off
take equally long. The clock speed is entered. A set point is not considered. The temperature and the set
value are displayed alternately. Change over to the automatic mode by pressing key > O<.
6. Turning on/Turning off: The instrument can be turned on and off by plucking in the power supply plug or
pulling it off. Furthermore, there is the possibility of turning the instrument off while it is connected with the
voltage supply. Therefore, key >F< and key > ^< have to be pressed at the same time and for 5 seconds.
After turning the instrument off, only a decimal point can be seen. The instrument is turned on by pressing
key >F< for 5 seconds.
7. Alarm outputs: Optionally the instrument can also be delivered with a socket for alarm outputs. The contact
is closed by alarm (alarm 1, 2 and sensor breaks).
8. A fuse is installed inside as protection, if the current is more than 5 amperes. Attention: The relay can
switch only resistive load (ohm-resistance)! Don’t regulate transformer and systems with more as 5
amperes. Working temperature: -10 to +40°C
We recommend the adjustment with auto- and self-optimization respectively; for further information please see
attached instruction.
Paul-Gothe-GmbH V.45/05/NCN
t regler-nicrni-3.doc

Paul Gothe GmbH
Temperaturregler - Schutz vor Verstellen der Parameter
Temperature controller – Protection against manipulation of the parameters
Deutsch:
Der Temperaturregler kann mit einer einfachen Einstellung vor ungewolltes Verstellen der
Parameter geschützt werden.
Den Schutz stellen Sie wie folgt ein:
Die F-Taste solange drücken bis „PAS“ erscheint. Mit den Auf- und Ab – Tasten die Zahl 99
einstellen, anschließend die Taste F drücken bis „Pro“ erscheint. Jetzt die Zahl 28 einstellen.
Nach erneutem langen Drücken der F-Taste wird das Menü verlassen und der Schutz ist
aktiviert.
Desaktivieren des Schutzes:
Die F-Taste solange drücken bis „PAS“ erscheint. Mit den Auf- und Ab – Tasten die Zahl 99
einstellen, anschließend die Taste F drücken bis „Pro“ erscheint. Jetzt die Zahl 00 einstellen.
Nach erneutem langen Drücken der F-Taste wird das Menü verlassen und der Schutz ist
desaktiviert.
A
nzeige
A
nzeige der Heizintervalle
Anzeige Regelabweichung
Auto/Manuell Funktionstaste
A
uf und Ab Tasten
English:
The temperature controller can be protected against inadvertent manipulation of the
parameters with a simple change of the parameter.
You activate the protection like follows:
Press the F-key as long as „PAS“ appears. With the up and down key type the number 99,
afterwards press F key until „Pro“ appears. Type there the number 28.
After renewed long pressing of the F-key, the menu is left and the protection is activated.
To deactivate the protection:
Press the F-key as long as „PAS “appears. With the up and down key type the number 99,
afterwards press F key until „Pro“ appears. Type there the number 00.
After renewed long pressing of the F-key, the menu is left and the protection is deactivated.
• Beim Anschließen des Gerätes sind die in der Bedienungsanleitung enthaltenen Anweisungen
sorgfältig zu befolgen.
• Das Gerät verfügt über KEINEN EIN/AUS - Schalter und wird daher unmittelbar nach dem Anschluß
an die Betriebsspannung aktiviert.
Die Firma PAUL GOTHE übernimmt in keinem Fall die Haftung für Sach- oder Personenschäden, die
auf unbefugte Eingriffe, sowie unsachgemäße oder den technischen Eigenschaften des Gerätes nicht
angemessene Bedienung oder Anwendung zurückzuführen sind.
Paul Gothe GmbH Wittener Str. 82, D-44789 Bochum, phone: ++49-234 - 33 51 80, www.paulgothe.com

dc current
linear input
0 ... 20mA, 4 ... 20mA
•Linear (I)
4
1
2
-
+
•Linear (V)
•PTC / Pt100 2-3 wires
“Raise”and “Lower”keys:
These keys are used for any operation that requires a numerical parameter to be raised or lowered. ••The speed of change is
proportional to the time the key is pressed. •• The operation is not cyclic: once the maximum (minimum) limit is reached, there will be no
further increase (decrease) of the value, even if the key remains pressed.
3 •DESCRIPTION OF FACEPLATE
Automatic/Manual setting selection
In Manual, corresponds to flashing of deviation
indicator
Display
Displays process variable, set point and
configuration parameters
Function key
Gives access to different configuration stages ••
Confirms any parameter changes
Deviation indicator
On if deviation is <0.25% f.s.
Indication of output states
OUT 1 (Main); OUT 2 (AL1); OUT 3 (AL2)
Standard:
100...127Vac (220...240Vac) ±10%
Optional
11...14Vac (22...27Vac) ±10%
11...27Vac/dc (not isolated)
Max. power 5.5VA; 50/60Hz
4 •CONNECTIONS
•Current transformer outputs / inputs
+
-
Generic user-configurable
output
- relay 5A/250Vac
- logic 10V, (20mA/6V)
Rout=100Ω
- relay 5A/250Vac
- logic 5V,Rout=22Ω(4V/20mA)
Current transformer
50mAac, 2Ω50/60Hz
Available thermocouples:
J, K, R, S, T, B, E, N
- Respect polarities
- For extensions, use
compensated cable
appropriate for
thermocouple.
•Inputs
•TC
Use wires of
adequate thickness
(min. 1mm2)
PT100, PTC
6
5
4
3
2
1
7
8
9
10
11
12
18
17
16
15
14
13
19
20
21
22
23
24
2
1
3
1
2
dc voltage
linear input
0...60mV, 0...10V,
12...60mV, 2...10V 2
1+
-
19
21
20
22
-
+
Out2 (Al1)
-
+
Out1 (Main)
•Power supply
23
24
~
~
TOP
6
5
-
+
Out3 (Al2)
Ing. T.A.
only for mod. 401
!
LED on during Self-tuning or Softstart;
LED flashes during Auto-tuning
LED flashes during software shutdown
PWR
11
Device structure: identification of boards
Pt100 3 wires
PTC / Pt100 2 wires
TT
Deviation indicator
On if deviation is between 0.25 and 5% f.s.
Flashes if deviation is >5% f.s.
POWER SUPPLY (Components Side)
S3
S2
Jumpers
on Sealing
Side
S2, S3 (LS) = Selection of contacts
NO, NC for Out1/Out2
S1, S4 = Selection of Power Range
220...240Vac
(22...27Vac)
100...127Vac
(11...14Vac)
S4 S1
VH
VL
!
S4
S5
S6
S7
J9
TX
RX
GND
S9
S1
CPU BOARD (Sealing Side)
S6 = ON Enable Calibration
S6
S3
S2
2NO
2NC
1NO
1NC
K2
K1 S4S1
TRANSFORMER

OUT 1
Attribution of
reference signal:
HEAT, COOL,
AL1, AL2, AL3
+ 16 for logic level denied at output
OUT 2
Attribution of
reference signal:
HEAT, COOL,
AL1, AL2, AL3
r.o.x MAIN logic output function, relay (OUT1)
0 HEAT (heating control output)
1 COOL (cooling control output)
2 AL1 - alarm 1
3 AL2 - alarm 2
4 AL3 - alarm 3 [A.Hb mod. 401])
5-
6 LBA - alarm LBA
7 (AL1) OR (AL2)
8 (AL1) OR (AL2) OR (AL3 [A.Hb mod. 401])
9 (AL1) AND (AL2)
10 (AL1) AND (AL2) AND (AL3 [A.Hb mod. 401])
2
0
Cycle time OUT1 relay or
logic = HEAT or COOL 0. ... 200 sec10
See table on Out
menu
Alarm type 1
0
Out Output settings
Default Custom
Configurat.
12
See table on InP
menu
See table on InP
menu
5 •Standard Configuration Menu
Enable
selftuning,
autotuning,
softstart
Proportional heating
range or hysteresis in
regulation ON/OFF
Integral heating time
Derived heating time
Maximum limit heating
power
S.tu Autotuning Selftuning Softstart
continuous
0NO NO NO
1 YES NO NO
2 NO YES NO
3 YES YES NO
4 NO NO YES
0 ... 999,9% f.s.
0,00 ... 99,99 min
0,00 ... 99,99 min
0,0 ... 100,0%
0
10.0
4.0
1.0
100.0
Default Custom
Configurat.
Control type
[0...11]
22
Type of sensor, signal
and main input scale
0
Position of decimal point
for main input scale
Minimum limit of main
input scale
Maximum limit of main
input scale
dP.S Format
0 xxxx
1 xxx.x
2xx.xx (*)
3x
.xxx (*)
min...max of input
selected in tyP
min...max of input selected
in tyP
0
0
1000
CFG Setting Parameters
InP Input settings
Default Custom
Configurat.
± 999
scale points
Hysteresis for alarm 1
-1

•CFG
Enable
selftuning,
autotuning,
softstart
CFG Setting parameters
Proportional heating
range or hysteresis in
ON/OFF
Integral heating time
Derived heating time
Maximum limit heating
power
Cooling setpoint relative
to heating set
Proportional cooling
range or hysteresis in
ON/OFF
S.tu Autotuning Selftuning Softstart
continuous
0NO NO NO
1 YES NO NO
2 NO YES NO
3 YES YES NO
4 NO NO YES
0 ... 999,9% f.s.
0,00 ... 99,99 min
0,00 ... 99,99 min
0,0 ... 100,0%
-999 ... 999
scale points
0 ... 999,9% f.s.
0
10.0
4.0
1.0
100.0
Default Custom
Configurat.
N.B. S.tu functions are cancelled when switching to MAN.
Wait time for tripping
of LBA alarm
(setting 0 disables LBA alarm)
Limit of power supplied
under LBA alarm
conditions
Fault Action power
(supplied in case of sensor
fault)
(*)If the LBA alarm is active (display flashing alternately with 4 decimal points),
you can cancel it by pressing keys ∆+ ∇when OutP is seen, or by switching
to Manual.
± 999
scale points
0,0...500,0 min
(*)
-100,0 ... 100,0%
c.on / OFF / h.on (*)
-100,0 ... 100,0%
c.on / OFF / h.on
Softstart time 0,0 ... 500,0 min
Reset power -100,0 ... 100,0%
± 999
scale points
Hysteresis for alarm 2
Hysteresis for alarm 1
± 999
scale points
Hysteresis for alarm 3
0...999 sec
Delay for tripping of Hb
alarm
Integral cooling time 0,00 ... 99,99 min
Derived cooling time 0,00 ... 99,99 min
Manual reset -999 ... 999
scale points
Maximum limit cooling
power 0,0 ... 100,0%
mod. 401
N.B.: the LBA alarm is excluded for ON/OFF controls
13
6 •PROGRAMMING and CONFIGURATION
F
If the Inc, Dec, F keys are not pressed within 15 sec.,
the display returns to the P.V. value
UPd
P.V. Process variable (display PV)
Setting output values
(+Heat / -Cool)
Pressed for
approx.
2 sec.
Setting parameters
CFG
InP
Out
PASS = 99
Prot
Input settings
Output settings
_CAL Select calibration menu [ 0...6 ]
YES
NO
Keep the F key
pressed to scroll
the menus
Release the F key
to select the
displayed menu
Press the F key to
access the
parameters
Keep the F key
pressed to exit any
menu
Keep F + Auto/Man
keys pressed for 2
sec. on any menu
to go immediately
to level 1 display
Pressing the
Auto/Man + F keys
on any menu
immediately returns
you to the previous
parameter.
NB: Parameters not required for a particular configuration are not displayed
(*)
Setpoint variable
LEVEL 1 DISPLAY
PASS
S6 = ON
YES
NO
Password
Protection code
(*) Timed return to PV disabled
1
7
Software version
Alarm threshold 1
Alarm threshold 2
Alarm threshold 3
PASS = 199
YES
NO
C.T. Current transformer input variable
Alarm HB limit (scale points current
transformer input)
(Displayed if a value >3 in Al.n is set)
mod. 401
mod. 401
(*)
Select calibration menu [ 0...7 ] mod. 401

•Out
•InP
Lo.S ... Hi.S
Type of probe, signal and scale of main input
tYP Type of probe Scale Max. scale range Max. scale range
(C/F) without decimal point with decimal point
0 J (Fe-CuNi) C 0 / 1000 0,0 / 999,9
1 J (Fe-CuNi) F 32 / 1832 32,0 / 999,9
2 K (NiCr-Ni) C 0 / 1300 0,0 / 999,9
3 K (NiCr-Ni) F 32 / 2372 32,0 / 999,9
4 R (Pt13Rh - Pt) C 0 / 1750 0,0 / 999,9
5 R (Pt13Rh - Pt) F 32 / 3182 32,0 / 999,9
6 S (Pt10Rh - Pt) C 0 / 1750 0,0 / 999,9
7 S (Pt10Rh - Pt) F 32 / 3182 32,0 / 999,9
8 T (Cu-CuNi) C -200 / 400 -199,9 / 400,0
9 T (Cu-CuNi) F -328 / 752 -199,9 / 752,0
10 B (Pt30Rh - Pt6Rh) C 44 / 1800 44,0 / 999,9
11 B (Pt30Rh - Pt6Rh) F 111 / 3272 111,0 / 999,9
12 E (NiCr-CuNi) C -100 / 750 -100,0 / 750,0
13 E (NiCr-CuNi) F -148 / 1382 -148,0 / 999,9
14 N (NiCrSi-NiSi) C 0 / 1300 0,0 / 999,9
15 N (NiCrSi-NiSi) F 32 / 2372 32,0 / 999,9
tYP Type of probe Scale Max. scale range Max. scale range
(C/F) without decimal point with decimal point
16 PT100 C -200 / 850 -199,9 / 850,0
17 PT100 F -328 / 1562 -199,9 / 999,9
SENSOR: RTD 3 wires (CAL = 2)
tYP Type of probe Scale Max. scale range Max. scale range
(C/F) without decimal point with decimal point
18 PTC C -55 / 120 -55.0 / 120.0
19 PTC F -67 / 248 -67.0 / 248.0
SENSOR PTC (CAL = 3)
tYP Signal type Scale Max. scale range
20 0...60mV linear -1999 / 9999
21 12...60mV linear -1999 / 9999
SENSOR: VOLTAGE 60Mv (CAL = 4)
tYP Signal type Scale Max. scale range
22 0...20mA linear -1999 / 9999
23 4...20mA linear -1999 / 9999
SENSOR: CURRENT 20mA or TRANSMITTER (CAL = 5)
tYP Signal type Scale Max. range scala
24 0...10V linear -1999 / 9999
25 2...10V linear -1999 / 9999
SENSOR: VOLTAGE 10V or TRANSMITTER (CAL = 6)
InP Input settings
Minimum limit of main
input scale
Maximum limit of main
input scale
Main input offset
correction
Lower limit for local setpoint
and absolute alarms
SENSOR: TC (CAL = 1)
min…max scale of input
selected in tyP
min…max scale of input
selected in tyP
-999 ... 999
scale points
Lo.S ... Hi.S
Upper limit for local setpoint
and absolute alarms
Type of control
[0...91]
CtrL Type of control
0 P hot
1 P cold
2 P hot / cold
3 PI hot
4 PI cold
5 PI hot / cold
6 PID hot
7 PID cold
8 PID hot / cold
9 ON-OFF hot
10 ON-OFF cold
11 ON-OFF hot / cold
0
0
1000
22
Default Custom
Configurat.
0,0...99,9
Max. current transformer
input scale
Out Output settings
+ 8 to disable on power-up until first alarm
AL.x Direct Absolute Normal
(maximum) Relative Symmetrical
Inverse to active (window)
(minimum) setpoint
0 direct absolute normal
1 inverse absolute normal
2 direct relativo normal
3 inverse relativo normal
4 direct absolute symmetrical
5 inverse absolute symmetrical
6 direct relativo symmetrical
7 inverse relativo symmetrical
0 ... 3
Number of alarms
Alarm
type 1
Alarm
type 2
Alarm
type 3
Default Custom
Configurat.
0
4, 5, 6 to select HB alarm as alternative to alarm 3
Function of
HB alarm
+0 assigned to OUT1 (only for Hb_F = 0, 1, 2)
+4 assigned to OUT2 (only for Hb_F = 0, 1, 2)
+16 alarm HB reverse
Hb_F Description
0 Relay, logic output: alarm active
with load current value below
limit set in ON time
of control output
1 Relay, logic output: alarm active
with load current value above
limit set in OFF time
of control output
2 Alarm active if one of functions 0 and 1
is active (OR logic for functions 0 and 1) (*)
3 Alarm HB continuous heating (**)
7 Alarm HB continuous cooling (**)
mod. 401
mod. 401
With mod. 401, set CAL=7 to calibrate the current transformer input
SENSORE TA: CORRENTE 50mAac (CAL = 7)
Signal type Scale Max. range scala
0 ... 50mAac linear 0 ... 99,9
0 ... 6
mod. 400 mod. 401
+16 disable parameters
CFG: rst, PrE, SoF, Lbt, Lbp, FAP,
HY.2, HY.3 (only for model 400)
InP: FLt, FLd, oFS, LoL, HIL
Out: ALn, A2t, A3t (only for model 400), rEL
FLt, FLd, oFS stay at set value.
ALn is forced to 1 (only for mod. 400)
All other parameters are considered 0.
14
Default: derived action sample time = 1 sec
+32: derived action sample time = 8sec
+64: derived action sample time = 240msec with derived action filter assigned
to Flt parameter (time filter)
(*) minimum limit is set = 12.5% of current transformer f.s.
(**) As type 0 without reference to cycle time .
Digital filter
on main input
Digital filter on display of
process variable; acts as
hysteresis
Decimal point position for
main input scale
(*) not available for
TC, RTD, PTC scales
0,0 ... 20,0 sec
0 ... 9,9
scale points
dP.S Format
0 xxxx
1 xxx.x
2xx.xx (*)
3x.xxx (*)
0
Max. non-linearity error
for thermocouples (TC),
resistors (PT100) and
thermistors (PTC).
The error is calculated
as deviation from
theoretical value and is
expressed as
percentage of full scale
(in °C
S, R range 0...1750°C; error < 0.2% f.s. (t > 300°C) /
for other range; error < 0.5% f.s.
Terror < 0.2% f.s. (t > -150°C)
Brange 44...1800°C; error < 0.5% f.s. (t > 300°C) /
range 44,0...999,9; error < 1% f.s. (t > 300°C)
Tc: J, K, E, N, error < 0,2% f.s.
PTC error < 0,2% f.s.
PT100 scale -200...850°C
Precision better than 0,2% f.s. at 25°C

This type of alarm is conditioned by use of the current transformer input. (T.A.)
It signals variations of load absorption by discriminating the level of current at the transformer input in the range (0...HI.A). It is
enabled with configuration code (AL.n); in this case the alarm trip value is expressed in HB scale points.
Select the type of functioning and the assigned control output by means of code Hb.F (“Out”phase).
The alarm limit setting is A.Hb.
The direct HB alarm trips if the value of the current transformer input is below the set limit for Hb.t seconds inclusive of “ON”
time of the selected output.
The HB alarm can be activated only with ON times longer than 0.4 seconds.
HB alarm function also includes control of load current in the OFF interval of the cycle time for the selected output: the HB
alarm will trip if the measured current exceeds approximately 12.5% of the full scale set (parameter HI.A in InP) for Hb.t
seconds inclusive of the OFF state of the output.
The alarm is reset automatically if the cause of the alarm is eliminated.
Setting a limit of A.Hb = 0 disables both types of HB alarms, with de-energizing of the assigned relay.
Indication of load current is displayed by selecting term C.T. (level 1).
NOTE: ON/OFF times refer to the cycle time set for the selected output.
Alarm Hb_F = 3 (7) continuous is active for a load current value below the set limit; it is disabled if the value of the
heating(cooling) output is less than 2%.
FUNCTION OF HB ALARM (only for mod. 401)
Fault action
(definition of state
in case of broken
sensor) alarms
AL1, AL2, AL3.
Select intrinsic
safety.
1) In case of broken sensor, the logic state of the alarm assumes the logic value selected without consideration of
alarm type (direct or reverse): ON = alarm active, OFF = alarm inactive.
2) Alarms are assigned to available outputs by setting codes r.o.1, r.o.2, r.o.3.
rEL Alarm Alarm Alarm
123
0 OFF OFF OFF
1 ON OFF OFF
2 OFF ON OFF
3 ON ON OFF
4 OFF OFF ON
5 ON OFF ON
6 OFF ON ON
7ONONON
Cycle time OUT1 relay or
logic = HEAT or COOL
Cycle time OUT2 relay or
logic = HEAT or COOL
1. ... 200 sec
1. ... 200 sec
10
Cycle time OUT3 relay or
logic = HEAT or COOL 1. ... 200 sec
•Prot
Pro Protection code
Pro Display Change
0 SP, alarms, OutP SP, alarms
1 SP, alarms, OutP SP
2SP SP
3SP
+4 disables InP, Out
+8 disables CFG
+16 disables “SW turn on - turn off”
+32 disables MAN/AUTO key
+ 64 to disable manual power modification
mod. 401
To activate the turn off SW function, press keys F
F + ∆for 5 secs. in P.V.
To return to normal functioning, press key F for 5
secs.
15
OUT 1
Attribution of reference
signal: HEAT, COOL, AL1,
AL2, AL3
+ 16 for logic level denied at output
OUT 2
Attribution of reference
signal: HEAT, COOL, AL1,
AL2, AL3
r.o.x MAIN logic output function, relay (OUT1)
0 HEAT (heating control output)
1 COOL (cooling control output)
2 AL1 - alarm 1
3 AL2 - alarm 2
4 AL3 - alarm 3 [A.Hb mod. 401])
5-
6 LBA - alarm LBA
7 (AL1) OR (AL2)
8 (AL1) OR (AL2) OR (AL3 [A.Hb mod. 401])
9 (AL1) AND (AL2)
10 (AL1) AND (AL2) AND (AL3 [A.Hb mod. 401])
2
0
OUT 3
Attribution of reference
signal: HEAT, COOL, AL1,
AL2, AL3
mod. 401
N.B. When T.A. input is present, Out3
(if configured) is limited to indication of
corresponding LED.

•RS232 / TTL interface cable for configuration of GEFRAN instruments
COD. WSK- 0 - 0 - 0 Interface Cable + CD
Winstrum
•ORDER CODE
•Current transformer
7 •ACCESSORIES
50 / 0.05 A
152050 9640
12
12
5,5 27 5,5
920 19
48
88
38
1
13
20
2
In
4430
1010
Hole for 2.9 x 9 self-
threading screws
These transformers are used to measure currents of 50 ÷60Hz from 25A to 600A
(nominal primary current). The peculiar characteristic of these transformers is the high
number of secondary turns. This provides a very low secondary current, suitable for an
electronic measurement circuit. The secondary current may be detected as voltage on a
resistor.
CODE Ip / Is ØSecondary n OUTPUTS Ru Vu ACCURACY
Wire
TA/152 025 25 / 0.05A 0.16 mm n1-2 = 500 1 - 2 40 Ω2 Vac 2.0 %
TA/152 050 50 / 0.05A 0.18 mm n1-2 = 1000 1 - 2 80 Ω4 Vac 1.0 %
IN = 25Aac
OUT = 50mAac
COD. 330200 IN = 50Aac
OUT = 50mAac
COD. 330201
•ORDER CODE
N.B.: The RS232 interface for configuration from PC is supplied along with the programming software.
Connect with the instrument powered and with inputs and outputs not connected.
16

TA input 50mAac H
11...27Vac/dc (not isolated) 9
ORDER CODE
400/401
OUTPUT 1
Relay
Logic R
D
OUTPUT 2
Relay
Logic R
D
POWER SUPPLY
11...14Vac, (22...27Vac)
100...127Vac, (220...240Vac) 0
1
OUTPUT 3 / TA INPUT (only for mod. 401)
Relay
Logic R
D
MODEL
Single-display controller
Single-display controller with
auxiliary input for current
transformer or output 3
400
401
•WARNINGS
Read the following warnings before installing, connecting or using the device:
•follow instructions precisely when connecting the device.
•always use cables that are suitable for the voltage and current levels indicated in the technical specifications.
•the device has no ON/OFF switch: it switches on immediately when power is turned on. For safety reasons, devices permanently connected to the power
supply require a two-phase disconnecting switch with proper marking. Such switch must be located near the device and must be easily reachable by the
user. A single switch can control several units.
•if the device is connected to electrically NON-ISOLATED equipment (e.g. thermocouples), a grounding wire must be applied to assure that this
connection is not made directly through the machine structure.
•if the device is used in applications where there is risk of injury to persons and/or damage to machines or materials, it MUST be used with auxiliary alarm
units. You should be able to check the correct operation of such units during normal operation of the device.
•before using the device, the user must check that all device parameters are correctly set in order to avoid injury to persons and/or damage to property.
•the device must NOT be used in inflammable or explosive environments. It may be connected to units operating in such environments only by means of
suitable interfaces in conformity to local safety regulations.
•the device contains components that are sensitive to static electrical discharges. Therefore, take appropriate precautions when handling electronic circuit
boards in order to prevent permanent damage to these components.
Installation: installation category II, pollution level 2, double isolation
•power supply lines must be separated from device input and output lines; always check that the supply voltage matches the voltage indicated on the
device label.
•install the instrumentation separately from the relays and power switching devices
•do not install high-power remote switches, contactors, relays, thyristor power units (particularly if “phase angle”type), motors, etc... in the same cabinet.
•avoid dust, humidity, corrosive gases and heat sources.
•do not close the ventilation holes; working temperature must be in the range of 0...50°C.
If the device has faston terminals, they must be protected and isolated; if the device has screw terminals, wires should be attached at least in pairs.
•Power: supplied from a disconnecting switch with fuse for the device section; path of wires from switch to devices should be as straight as possible; the
same supply should not be used to power relays, contactors, solenoid valves, etc.; if the voltage waveform is strongly distorted by thyristor switching units
or by electric motors, it is recommended that an isolation transformer be used only for the devices, connecting the screen to ground; it is important for the
electrical system to have a good ground connection; voltage between neutral and ground must not exceed 1V and resistance must be less than 6Ohm; if
the supply voltage is highly variable, use a voltage stabilizer for the device; use line filters in the vicinity of high frequency generators or arc welders;
power supply lines must be separated from device input and output lines; always check that the supply voltage matches the voltage indicated on the
device label.
•Input and output connections: external connected circuits must have double insulation; to connect analog inputs (TC, RTD) you have to: physically
separate input wiring from power supply wiring, from output wiring, and from power connections; use twisted and screened cables, with screen connected
to ground at only one point; to connect adjustment and alarm outputs (contactors, solenoid valves, motors, fans, etc.), install RC groups (resistor and
capacitor in series) in parallel with inductive loads that work in AC (Note: all capacitors must conform to VDE standards (class x2) and support at least 220
VAC. Resistors must be at least 2W); fit a 1N4007 diode in parallel with the coil of inductive loads that operate in DC.
GEFRAN spa will not be held liable for any injury to persons and/or damage to property deriving from tampering, from any incorrect or
erroneous use, or from any use not conforming to the device specifications.
!WARNING: this symbol indicates danger.
It is seen near the power supply circuit and near high-voltage relay contacts.
17
Please, contact GEFRAN sales people for the codes availability.

1
Proportional Action:
action in which contribution to output is proportional to deviation at input (deviation = difference between controlled variable and setpoint).
Derivative Action:
action in which contribution to output is proportional to rate of variation input deviation.
Integral Action:
action in which contribution to output is proportional to integral of time of input deviation.
Influence of Proportional, Derivative and Integral actions on response of process under control
* An increase in P.B. reduces oscillations but increases deviation.
* A reduction in P.B. reduces the deviation but provokes oscillations of the controlled variable (the system tends to be unstable if P.B. value is
too low).
* An increase in Derivative Action corresponds to an increase in Derivative Time, reduces deviation and prevents oscillation up to a critical
value of Derivative Time, beyond which deviation increases and prolonged oscillations occur.
* An increase in Integral Action corresponds to a reduction in Integral Time, and tends to eliminate deviation between the controlled variable
and the setpoint when the system is running at rated speed.
If the Integral Time value is too long (Weak integral action), deviation between the controlled variable and the setpoint may persist.
Contact GEFRAN for more information on control actions.
•CONTROL ACTIONS
•MANUAL TUNING
A) Enter the setpoint at its working value.
B) Set the proportional band at 0.1% (with on-off type setting).
C) Switch to automatic and observe the behavior of the variable. It will be similar to that in the figure:
D) The PID parameters are calculated s follows: Proportional band
Peak
P.B.= ---------------------------------------- x 100
(V max - V min)
(V max - V min) is the scale range.
Integral time: It = 1.5 x T
Derivative time: dt = It/4
E) Switch the unit to manual, set the calculated parameters. Return to PID action by setting
the appropriate relay output cycle time, and switch back to Automatic.
F) If possible, to optimize parameters, change the setpoint and check temporary response.
If an oscillation persists, increase the proportional band. If the response is too slow, reduce
it.
Process
Variable
Time
T
Peak
PIN1
LOC/REM
(*) if the set gradient is
set

2
The function works for single output systems (heating or cooling). The self-tuning action calculates optimum control parameter values during
process startup. The variable (for example, temperature) must be that assumed at zero power (room temperature).
The controller supplies maximum power until an intermediate value between starting value and setpoint is reached, after which it zeros power.
PID parameters are calculated by measuring overshoot and the time needed to reach peak. When calculations are finished, the system
disables automatically and the control proceeds until the setpoint is reached.
How to activate self-tuning:
A. Activation at power-on
1. Set the setpoint to the required value
2. Enable selftuning by setting the Stun parameter to 2 (CFG menu)
3. Turn off the instrument
4. Make sure the temperature is near room temperature
5. Turn on the instrument again
)
.
.)
The procedure runs automatically until finished, when the new PID parameters are stored: proportional band, integral and derivative times
calculated for the active action (heating or cooling).
.
When finished, the Stun code is automatically cancelled.
Notes :
-The procedure does not start if the temperature is higher than the setpoint (heating control mode) or if the temperature is lower than the
setpoint (cooling control mode). In this case , the Stu code is not cancelled.
-
.
•SELF-TUNING
Peak
T
S.P.
t.a. Time
Process
Variable
S.P. + t.a.
2
•AUTO-TUNING
Enabling the auto-tuning function blocks the PID parameter settings.
It can be one of two types: permanent (continuous) or single-action
(one-shot).
* Continuous auto-tuning is activated via the Stu parameter (values 1,
3, 5). It continuously reads system oscillations, immediately seeking
the PID parameter values that reduce the current oscillation. It does
not engage if the oscillations drop below 1.0% of the proportional
band. It is interrupted if the set-point is changed, and automatically
resumes with a constant set-point. The calculated parameters are not
saved if the instrument is switched off, if the instrument is switched to
manual, or if the configuration code is disabled. The controller
resumes with the parameters programmed before auto-tuning was
enabled.
p .
* One-shot auto-tuning can be enabled manually or automatically. It is
activated via the Stu parameter (as can be seen on the table, the
values to be set depend on whether Self-tuning or Soft-start is
enabled.). It is useful for calculation of PID parameters when the
system is around the set-point. It produces a variation on the control
output at a maximum of ± 100% of the current control power limited by
h.PH - h.PL (hot), c.PH - c.PL (cold), and assesses the effects in timed
overshoot. The calculated parameters are saved.
.
.
.
.
.
.
.
time
PV
c_Pb
h_Pb
SP+cSP
SP
+100%
Control output
0%
-100%
Control output with proportional action only if proportional heating band
overlaps proportional cooling band. Control output with proportional action only if proportional heating band
overlaps proportional cooling band.
time
PV
c_Pb
h_Pb
SP+cSP
SP
+100%
Control output
0%
-100%
PV = Process Value SP = Heating Setpoint
SP+cSP = cooling setpoint h_Pb = proportional heating band
c_Pb = Proportional cooling band
•CONTROLS
Other manuals for 400
1
This manual suits for next models
1
Table of contents
Other gefran Temperature Controllers manuals