Section A-2 GE-NUTRI
WARNINGS AND PRECAUTIONS
Although the manufacturer has made every effort to ensure the accuracy of the
information contained herein, this document is subject to change without notice due to
ongoing product development.
WARNINGS AND PRECAUTIONS
Equipment, probe failure, blown fuses and/or tripped breakers may prove harmful to the
contents of the building. Therefore it is strongly recommended to install backup devices
and alarm or warning devices. Spare equipment should also be available at the owner’s
site. Equipment manufactured by the manufacturer is protected against normal line
surges. High surges caused by thunderstorms or power supply equipment may damage
this equipment. For added security against line voltage surges it is recommended that
surge and noise suppression devices be installed at the electrical distribution panel. Use
of shielded cable for probes is recommended for protection against lightning. These
devices are available from most electrical supply distributors.
RECOMMENDATIONS
The manufacturer recommends that all installation procedures described herein be
performed by a qualified electrician or installation technician. Furthermore the
manufacturer recommends testing all the functions and equipment connected to the GE-
NUTRI Controller, including the alarm system and backup devices, after installation,
after changes to the installation and every month after that.
Fuse verification and replacement, as well as the proper setting of control values shall
be the responsibility of the owner of this equipment.

GE-NUTRI WIRING DIAGRAM
GE-NUTRI Section A-3
WIRING DIAGRAM
GE-NUTRI
SECTION A

GE-NUTRI WIRING DIAGRAM
Section A-4 GE-NUTRI
Board Layout and actuator Identification
WARNING!!!
MAKE SURE THE
VOLTAGE SELECTOR
MATCHES THE
VOLTAGE
LINE.
BOARD LAYOUT AND ACTUATOR IDENTIFICATION
GE- NUTRI ( 1HP RELAY )
LI
NE
VOLTAGE
SELECTOR
230V
5
OPEN
OUVREFERM
E
POS 3
OPENCLOSE
POS 2
OPENCLOSE42
3
1
OPEN
FERME
POS 1
OPENCLOSE
POS 4
OPENCLOSE

GE-NUTRI WIRING DIAGRAM
GE-NUTRI Section A-5
Board Layout and relay Identification
WARNING!!!
MAKE SURE THE
VOLTAGE SELECTOR
MATCHES THE
VOLTAGE
LINE.
BOARD LAYOUT AND RELAY IDENTIFICATION
GE- NUTRI ( 1HP RELAY )
LI
NE
VOLTAGE
SELECTOR
230V
5
42
3
1
POS 1POS 2POS 5POS 6POS 7POS 8
POS 3POS 4POS 9POS 10POS 11POS 12

GE-NUTRI WIRING DIAGRAM
Section A-6 GE-NUTRI
Wiring Diagram (Input Board)
WIRING DIAGRAM GE-NUTRI (INPUT BOARD)
GE-NUTRI
PR B 1
GND
MGCB3
PLS
+
8VAC
MGCB1
MGCB2
SEE NOTE ON PAGE 9
L2/N
L1
ALARM
N0
C
NC
LINE
115/230V
THE GE- NUTRI MUST BE ON
INDEPENDENT CIRCUIT
LINE VOLTAGE
SELEC TOR
230V X1317
PRB 6 PRB 5 PRB 3 PRB 2PR B 4
WARNING!!!
MAKE SURE THE
VOLTAGE SELECTOR
MATCHES
THE VOLTAGE
LINE.
PR B 7PRB 8
FEEDER, FEED AUGER,
MICRO-SWITCH
POTENTIOMETER
FOR
POSITIONER
C1
B1
A1
POS1
POT 1
3
9
POT 2
C2
B2
A2
POS2
C3
B3
A3
POS3
POT 3
6
POT 4
C4
B4
A4
POS4
9
7
6
8
WIRING DIAGRAM
CONFIGURATION
GE-NUTRIWIRREV
0
15091
7
//
BA
FEEDER, FEED AUGER,
MICRO-SWITCH
FEEDER, FEED AUGER,
MICRO-SWITCH
FEEDER, FEED AUGER,
MICRO-SWITCH
FEEDER, FEED AUGER,
MICRO-SWITCH
FEEDER, FEED AUGER,
MICRO-SWITCH
FEEDER, FEED AUGER,
MICRO-SWITCH
FEEDER, FEED AUGER,
MICRO-SWITCH

GE-NUTRI WIRING DIAGRAM
GE-NUTRI Section A-7
Wiring Diagram (1 HP Relay)
WIRING DIAGRAM
CONFIGURATION
GE-NUTRI WIR REV
0
SEE NOTE ON PAGE 9
WIRING DIAGRAM GE-NUTRI (1 HP RELAY)
REL 1 REL 2
X1314/R4
6 5
ON-OFF BOARD
L2/N
L1
L2/N
L1
REL 3 REL 4
L2/N
L1
L2/N
L1
REL 1 REL 2 REL 3 REL 4
X1314/R4
65
ON-OFF BOARD
L2/N
L1
L2/N
L1
L2/N
L1
3
REL 1 REL 2
X1314/R2
6 5
ON-OFF BOARD
42
L2/N
L1
L2/N
L1
REL 1 REL 2
X1314/R2
6 5
ON-OFF BOARD
5
L2/N
L1
L2/N
L1
L2/N
L1
POS 1 OPEN,
FEEDER, FEED AUGER
15 09 17/ /
POS 1 CLOSE,
FEEDER, FEED AUGER
POS 2 OPEN,
FEEDER, FEED AUGER
POS 2 CLOSE,
FEEDER, FEED AUGER
POS 3 OPEN,
FEEDER, FEED AUGER
POS 3 CLOSE,
FEEDER, FEED AUGER
POS 4 OPEN,
FEEDER, FEED AUGER
POS 4 CLOSE,
FEEDER, FEED AUGER
FEEDER, FEED AUGER
FEEDER, FEED AUGER
FEEDER, FEED AUGER
FEEDER, FEED AUGER

GE-NUTRI WIRING DIAGRAM
Section A-8 GE-NUTRI
Wiring Diagram (8 Input Board MGCB)
WIRING DIAGRAM
CONFIGURATION
GE-NUTRI15 09 17/ / WIR REV
0
SEE NOTE ON PAGE 9
WIRING DIAGRAM GE-NUTRI (8 INPUT BOARD MGCB)
JP1
ST
ANDARD
4 -20m
A
JP2
J
P1 J
P2
(PRB7
) (PRB8)
8-I NPUT BOARD
PRB 1 PR B 2 PRB 3 PRB 4 PRB 6 PRB 7 PRB 8
9
PRB 5
SHEILD
(JP1) (JP2)
12VDC
X1399
8
M GC B
P 0
INPUT
+DC
12V
JP3
ID=1
ID=2
JP
4
JP324
00
192
00
J
P4
10
10
B A
FEEDER, FEED AUGER, MICRO-SWITCH
EXTE RNA L
TRAN SFO
12 VAC / 0.7 A
11
6
FEEDER, FEED AUGER, MICRO-SWITCH
FEEDER, FEED AUGER, MICRO-SWITCH
FEEDER, FEED AUGER, MICRO-SWITCH
FEEDER, FEED AUGER, MICRO-SWITCH
FEEDER, FEED AUGER, MICRO-SWITCH
FEEDER, FEED AUGER, MICRO-SWITCH
FEEDER, FEED AUGER, MICRO-SWITCH

GE-NUTRI WIRING DIAGRAM
GE-NUTRI Section A-9
Electrician’s notes
(PROBE WIRING) SHIELDED WIRE AWG #22 WITH 16/30 STRANDING, 500ft
(150m) MAXIMUM LENGTH (Ex.: DECA 73-310).
For other probe, refer to specific probe manual for appropriate maximum length
and wire size or use AWG #22, 500ft (150m) MAXIMUM LENGTH.
(COMMUNICATION WIRING) SHIELDED, TWISTED PAIR (8 TWIST/FT). MAX
LENGTH FOR 350PF/M CABLE : 500FT (150M). MAX LENGTH FOR 89PF/M
CABLE : 820FT (250M).
HIGH VOLTAGE WIRE INSTALLED ACCORDING TO LOCAL WIRING CODE.
INSTALL LOW VOLTAGE WIRES (PROBES, COMPUTER LINK OR
POTENTIOMETER WIRES) AT LEAST 12 INCHES (30cm) AWAY FROM
HIGH VOLTAGE WIRES (120/230VAC, 24VDC). ALWAYS CROSS HIGH AND
LOW VOLTAGE WIRES AT A 90-DEGREE ANGLE.
RELAYS: 12A @ 240VAC RESISTIVE, MOTOR 1HP @ 240VAC, 1/2HP @
120VAC AT EACH OUTPUT.
1 WIRE ONLY PER GREEN TERMINAL. USE WIRE CONNECTOR IF YOU
WANT TO CONNECT MORE THAN 1 WIRE, NO BIGGER THAN AWG #12,
NO SMALLER THAN AWG #28.
CHECK INSTALLATION SECTION FOR ALARM WIRING.
USE SHIELD FOR SHIELDING PURPOSE ONLY. CONNECT 1 END AND 1
END ONLY OF THE SHIELD TO THE CONTROL CIRCUIT COMMON END .
NEVER LEAVE BOTH ENDS OF THE SHIELD UNCONNECTED. NEVER
CONNECT BOTH ENDS OF THE SHIELD TO COMMON . THE USE OF A
SHIELD FOR ALL PROBES AND POTENTIOMETERS IS MANDATORY.
COMMUNICATION WIRING SHIELDED, TWISTED PAIR (8 TWIST/FT). MAX
LENGTH FOR 350PF/M CABLE : 160FT (50M). MAX LENGTH FOR 89PF/M
CABLE : 650FT (200M).
JP1 – JUMPER MUST BE INSTALLED ON PIN 1-2 (STANDARD)
JP2 – JUMPER MUST BE INSTALLED ON PIN 1-2 (STANDARD)
JP3 – JUMPER MUST BE INSTALLED ON PIN 1-2 (ID 1)
JP4 – JUMPER MUST BE INSTALLED ON PIN 2-3 (19200bp)
X1399 BOARD PROGRAM VERSION MUST BE V4 OR HIGHER.
1
2
3
5
8
9
4
6
7
10
11

GE-NUTRI INSTALLATION
Section B-10 GE-NUTRI
INSTALLATION
GE-NUTRI
SECTION B

GE-NUTRI INSTALLATION
GE-NUTRI Section B-11
This section will inform the electrician on proper wiring and installation
procedures for the GE-NUTRI Controller.
The manufacturer recommends that the following installation instructions be
followed to as closely as possible, and that all work be performed by a certified
electrician. Failure to do so may void the warranty.
Unpacking
Unpack the GE-NUTRI Controller and inspect contents for damage. Should the
contents appear to be damaged, contact your local distributor to return the
equipment.
The package should contain the following standard items:
1 GE-NUTRI control
4 Brackets / 4 screws
1 Installation / User’s Guide
Mounting hardware required
This is the list of the mounting hardware needed, which is not included with the
product:
Shielded two-wire cable, AWG #22 (to extend probes)
Shielded two-wire twisted pair cable, AWG #22 (used for communication)
see electrician note for capacitance selection.
4 screws (to hang the unit onto the wall)
Screwdrivers
Soldering iron kit or approved sealed connectors
Drill and hole saw kit

GE-NUTRI INSTALLATION
Section B-12 GE-NUTRI
General installation guidelines
GE-NUTRI Controller
- It is recommended to install the unit in a hallway to limit the GE-NUTRI
Controller exposure to noxious gases.
- In order to avoid condensation problems inside the controller, it is
recommended to install the GE-NUTRI Controller on an inside wall. If it is not
possible, use spacers to have an air gap between the wall and the GE-NUTRI
Controller.
- It is required to install the GE-NUTRI Controller right side up with the cable
entry holes facing down.
- The enclosure is watertight, but do not spray water or submerge the GE-
NUTRI Controller in water. Cover it carefully with plastic when cleaning the
room.
- The GE-NUTRI Controller should be installed in easy-access location but
away from damaging elements (heat, cold, water, direct sunlight, …).
- Do not drill the face, the side, the top or the underside of the control.
- Do not install the GE-NUTRI Controller near high-voltage equipment, power
supply or transformer.
Electrical cables
- All electrical cables must be installed according to local wiring codes.
- All cable shields must be connected to the shield terminal on the cord to
which the cable is connected, except for the cable connected to the optional
PC interface. The shield is needed to protect the GE-NUTRI Controller and
the modules against any electromagnetic interference generated by lightning
or nearby operating machinery.
- Never use the shield as a conductor.
- Connect only one end of the shield to the GE-NUTRI Controller.
- Use separate conduits for the low voltage cables (communication and probes)
and the high voltage cables. There must be at least 1 foot (30 cm) between
low-voltage and high-voltage conduits.
- If a low voltage cable has to cross over a high voltage cable, make this
crossing at 90°.
- All cable connections must be soldered or done with approved sealed
connectors.
- Probe cables must be 500’ (150m) or less.
- Communication cables must be 820’ (250m) or less.
- It is prohibited to use overhead cables outside the building.
Electrical power
- Protection from electrical surges should be included in the planning of each
installation.
- Every module should have a separate breaker to avoid unwanted
consequences.

GE-NUTRI INSTALLATION
GE-NUTRI Section B-13
- The backup system and alarm must be thoroughly tested and verified as
working properly before using the ventilation system.
Mounting
- The enclosure must be mounted in a location that will allow the cover to be
completely opened.
- Fasten the four brackets to the four mounting holes on the back of the
enclosure using the four screws provided with the brackets.
- Then mount the enclosure on the wall by inserting screws through the
brackets’ adjustment slots, into the wall. Make sure to position the enclosure
so that all wires extend out of the bottom section of the enclosure.
- The bracket slots serve to adjust the position of the controller.
- Once you have adjusted the controller position, tighten the four mounting
screws. (see figure 1).
FIGURE NO. 1 Mounting Position and Devices

GE-NUTRI INSTALLATION
Section B-14 GE-NUTRI
Connection procedure
Detailed wiring diagrams
Typical positioner wiring
Follow the calibration procedure in the user guide, otherwise the positioner
positioning will be erratic.
FIGURE NO. 2 Typical 115V-Positioner Wiring
CLOSE
OPEN
COM
WINCH
L2/N
L1
C1
B1
A1
ACT 1
RELAY BOARD
FEEDBACK
POTENTIOMETER
C
-
+
X1317
REL 1 REL 2

GE-NUTRI INSTALLATION
GE-NUTRI Section B-15
Typical power backup wiring
A backup relay (DPDT) is connected to the power source 1 in normal operation
but will switch to the power source 2 if source 1 is disabled. The backup relay
should be selected to ensure it is able to support the required power load.
FIGURE NO. 3 Typical Power Backup Wiring
8 PIN RELAY DPDT
(OMRON model MK2EP-UA-AC120)
3
4
5
6
2
1
8
7
NO 2
NO 1
NC 1
NC 2
COM 2
COM 1
L2/N GND
L1
3
4
5
6
2
1
8
7
L2 L1
GND
source 1
DISTRIBUTION
PANEL
L2 L1
N
LINE
115/230 VAC
source 2
DISTRIBUTION
PANEL
LINE
115/230 VAC

GE-NUTRI INSTALLATION
Section B-16 GE-NUTRI
Typical alarm connection wiring
The GE-NUTRI Controller provides a normally open and normally closed dry
contact to set off an alarm in case low or high temperature condition occurs.
Moreover, this same contact can be used to signal a power failure or other
malfunctions. It may be connected to an alarm system or directly to a siren and/or
auto-dialer.
Make the normally closed (NC) or normally open (NO) connections as indicated
in figures 10 and 11.
FIGURE NO. 4 Typical Alarm Connection Wiring
ALARM SYSTEM /
AUTO DIALER
ALARM
N0
C
NC
X1317
FIGURE NO. 5 Siren Connection Wiring
Normally closed
manual OFF switch
X1317
ALARM
N0
C
NC

GE-NUTRI INSTALLATION
GE-NUTRI Section B-17
Powering up procedure
Once the GE-NUTRI controller is properly mounted on the wall and all modules
and sensors are connected to the terminal block, perform the following steps:
Verify all connections
Seal all cable entry holes.
Hermetically close the GE-NUTRI Controller
Close the front panel and the lower access cover.
Put the power on
Secure the front panel with a lock
GE-NUTRI Controller compatible probes
This is the list of all compatible probes that can be connected with the GE-NUTRI
controller and a short description of their function.
Micro Switch
On/off switch read by the controller
CSD-1
Current detector for feed augers.
GE-NUTRI Controller compatible modules
This is the list of all the compatible modules that can be connected with the GE-
NUTRI Controller with a short description of their function.
GE-NUTRI computer interface
Communication card (card inserted into the Genius Controller to
communicate with the computer interface)
RF-IN2 Communication Module (Module inserted into the Genius Controller
for a wireless communication with the computer interface)
PC interface (Separate box allowing different communication options to a PC
interface)
Additional Probes
8 Inputs Board (X1399)

GE-NUTRI INSTALLATION
Section B-18 GE-NUTRI
Specifications
Storage temperature -4°F to 131°F (-20°C to 55°C)
Operating temperature 32°F to 122°F (0°C to 50°C)
Humidity 90% maximum Non-condensing
Weight 9 lb (4.1 kg)
Size 14 1/2” x 13 1/4” x 5.5” (36 cm x 33 cm x 13.9 cm)
Protection index IP 66
Warranty 2 years
POWER SUPPLY
Operational voltage range 90 to 250 VAC
Operational frequency range 45 to 65 Hz
Power supply circuit consumption (CPU Board) 65 W maximum
SOURCE 8VAC
Voltage Range 6.5 to 13VAC
Maximum current allowed 50mA
PROBE INPUTS
Input measuring range 0 Ohm, open circuit
0-5000 mV
0-20 mA (PRB 7 and 8)
Maximum frequency for the water counter
(50% cycle)
4 Hz
Maximum wire length 500 feet (150 m)
Recommended wires 2 strands, shielded, AWG #22
8-INPUT MGCB BOARD (X1276)
PROBE INPUTS (PRB1-PRB8)
Input measuring range 0 Ohm, open circuit
0-5000 mV
0-20 mA (PRB 7 and 8)
Maximum frequency for the water meter
(50% cycle)
4 Hz
Maximum wire length 150 m (500 feet)
Recommended wires 2 strands, shielded, AWG #22
SOURCE 12 VDC (12VDC)
Maximum current allowed 100mA
ALARM RELAY
Maximum current 1 A at 30 VDC
Fuse 1A 250VAC
COMMUNICATIONS PORTS (MGCB)
Maximum wire length (2400 bps) 820 feet (250 m)
Maximum wire length (19200 bps) 6.5 feet (2 m)
Recommended wire 2 strands, twisted pair, low capacity, shielded,
AWG #22
OUTPUT RELAYS (1HP)
Maximum Load
1HP @ 240VAC, 1/2HP @ 120VAC,
12A@240VAC
Notice These relays are rated by UL and CSA at 1HP @
240VAC, 1/2HP @ 120VAC. However, for outputs
requiring frequent activation (ex: minimum
ventilation fans working on a timer) it is
recommended not to use more than 1/2HP @
240VAC, 1/4HP @ 120VAC per relay.

GE-NUTRI INSTALLATION
GE-NUTRI Section B-19
OUTPUT RELAYS (2HP)
Maximum Load
2HP @ 240VAC, 1HP @ 120VAC, 12A@240VAC
Notice These relays are rated by UL and CSA at 2HP @
240VAC, 1HP @ 120VAC. However, for outputs
requiring frequent activation (ex: minimum
ventilation fans working on a timer) it is
recommended not to use more than 1HP @
240VAC, 1/2HP @ 120VAC per relay.
VARIABLE OUTPUTS
Maximum Allowable Current (Fuse value) 15A, 250VAC
Recommended maximum current for fans 12A, 120 / 208 / 240VAC
Minimum load 300mA @ 230VAC
PLS OUTPUTS
Recommended wires 2 conductors, twisted pair (8 twist /ft), AWG #22
Maximum wire length (350pF/m cable) 160ft (50m)
Maximum wire length (89pF/m cable) 650ft (200m)
Important Notice:
- It is important to have a backup system in case of a system failure.
- Low-voltage and high-voltage wires must be passed through different
conduits at least 1 foot (30 cm) apart. If low-voltage and high-voltage
conduits must be crossed, the crossing must be at a 90-degree angle.
- All wiring must be made by a certified electrician and conform to local
electrical regulations.

GE-NUTRI INSTALLATION
Section B-20 GE-NUTRI
Troubleshooting
SYMPTOM CAUSE SOLUTION
Screen is blank GE-
NUTRI Controller is not
powered.
The
connector between the
top and the main boards or
between the relay control
and the main boards of the
GE-NUTRI Controller
is
disconnected.
Make sure the control is
powered.
Make sure both
connectors are properly
connected.
Table of contents